Operation And Display Elements - ACS GWA-250 Technical Manual

Limit value switch
Table of Contents

Advertisement

Operation and display elements

Function indicator
3 LED's for indication
of operating states
Function indicator
ON
green LED
A
red LED
B
red LED
Key coding switch
For setting the limit value from 0...99% of the configured signal range in steps of 1%.
At two-position-control ∆s the limit value A represents the switching value and the limit value B the switching back value.
Configuration switches
The configuration of the input signal range as well as the relay functions is made per dip switches inside the housing.
Dangerous voltage
Ensure a safe switching off the supply voltage when opening the housing
For configuration release the upper housing part at top and bottom side behind the terminals by using a screwdriver and pull
it out of the housing. Drop-in pin's avoid a complete pulling out. Following the respective dip switches can be set according to
the desired functions to ON or OFF.
Relay functions switcher block SB1
Switch 1, 2, 5, 6 (SB1)
Switch 3, 7 (SB1)
Switch 4 (SB1)
Input signal range GWA – 250
Switch 1 (SB2)
Input signal range GWAP – 250
Switch 2, 3 (SB2)
Switch 1, 2, 3 (SB3)
Limit value channel A
2-digit
key coding switch
Limit value channel B
2-digit
key coding switch
ready status, power supply voltage on
output relay A switched on
output relay B switched on
Safety function
switching state S1
ON
OFF
switching state S5
ON
OFF
switching delay
switch
3
7
operation function
switch
switching state ON
two-position-control ∆s
4
switcher block SB2
measuring range – only at GWA – 250
switch
switching state ON
1
input signal 4...20mA
switcher block SB2 / SB3
measuring range signal zero value – only at GWAP – 250
switching state S2
ON
OFF
OFF
measuring range signal range – only at GWAP – 250
switching state S1
switching state S2
ON
ON
OFF
OFF
switching state S2
OFF
ON
switching state S6
OFF
ON
switching state ON
channel B – 4 seconds
channel A – 4 seconds
switching state S3
ON
ON
OFF
switching state S3
ON
ON
OFF
ON
OFF
ON
OFF
OFF
GWA – 250
Configuration switch
inside the housing
safety function
channel B – minimum safety
channel B – maximum safety
safety function
channel A – minimum safety
channel A – maximum safety
switching state OFF
channel B – 0,4 seconds
channel A – 0,4 seconds
switching state OFF
double limit value switch function
switching state OFF
input signal 0...10V / 0...20mA
signal zero value
zero value – 50°C
zero value
0°C
zero value + 50°C
signal range
30 Kelvin
50 Kelvin
100 Kelvin
600 Kelvin
page 7 of 8