If the input voltage configuration is changed, this label must be replaced to reflect the new configuration. Replacement labels are available from TestEquity at no charge. ! CAUTION: This chamber must be properly configured for either 208 V or 230 V nominal input.
! CAUTION: The Series F4 “Alarm” functions are NOT used in the chamber’s safety system and are NOT connected. TestEquity does NOT recommend using the Series F4 alarm function as the main protection device. The independent EZ-Zone Limit Controller functions as the main protection device.
Page 7
! WARNING: This chamber operates at extreme temperatures. Avoid contact with air, objects, and surfaces that are hot or cold to prevent severe burns or frostbite. Protective gloves are recommended. TestEquity 1007C Temperature Chamber Page 1-3...
Chapter 2 – Installation Uncrating Inspect the shipping container for any signs of visible damage. Notify the carrier and TestEquity immediately if there are signs of shipping damage. The pallet is designed with ramps so the chamber can be rolled off without the need for a forklift or pallet jack.
Therefore, it must empty into an open floor drain. Alternatively, the chamber drain can empty into a condensate pump. You can purchase a condensate pump from suppliers such as Grainger (www.grainger.com). Page 2-2 TestEquity 1007C Temperature Chamber...
If the input voltage configuration is changed, this label must be replaced to reflect the new configuration. Replacement labels are available from TestEquity at no charge. ! CAUTION: This chamber must be properly configured for either 208 V or 230 V nominal input.
Switch. Connect earth ground to the ground lug. Three Phase Single Phase Wire D to terminal B Wire D to terminal A Figure 2-2 – Power Distribution Block Terminals on the Electrical Sub Panel Page 2-4 TestEquity 1007C Temperature Chamber...
2. Connect the “Hot” input wires to terminals L1 and L2 on the Main Disconnect Switch. 3. Connect the Ground wire (NOT A NEUTRAL) to the Ground terminal. 4. Put the chamber side panel back on and close the lower door. TestEquity 1007C Temperature Chamber Page 2-5...
3. Enter the desired temperature set point (or program) on the Temperature Controller. 4. Load your test sample in the chamber. 5. Turn the CONDITIONING Switch ON. Alternatively, turn the CONDITIONING Switch to the EVENT 1 position and turn EVENT 1 on the F4 controller ON. TestEquity 1007C Temperature Chamber Page 3-1...
In this mode, the Modbus register for Digital Output 1 is 2000. ! CAUTION: Remember to set CONDITION to On in the profile event prompt all programmed steps when the chamber is to be operational. Page 3-2 TestEquity 1007C Temperature Chamber...
The Cool Light will illuminate when the Temperature Controller turns on the cooling valve to maintain the workspace temperature. The Cool Light will cycle on/off as the workspace temperature approaches and reaches the temperature set point. TestEquity 1007C Temperature Chamber Page 3-3...
Limit Controller’s temperature limits are exceeded. ! CAUTION: To prevent damage to your test sample and the chamber’s compressors, do not exceed the live load rating of the chamber. Live Load Capacity for Model 1007C Temp +23°C 0°C –40°C...
Make sure that all connectors, wiring, pc boards, and auxiliary components can withstand the temperature extremes that they will be subjected to. In some cases, these components may not be able to last after repeated tests and should be considered expendable. TestEquity 1007C Temperature Chamber Page 3-5...
The vent body can become hot or cold depending on the workspace condition. The vent assembly has a drip pan to catch any condensate that may occur. Page 3-6 TestEquity 1007C Temperature Chamber...
However, there will be times when entry into these menus is necessary. For example, you may need to gain access to Setup Page in order to change from °C to °F display, or to change the time or date. You must call TestEquity at 877-512-3457 or 805-480-0638 to obtain the password. TestEquity 1007C Temperature Chamber...
After making the change with the with the ▲ or ▼ key, you may back using the ◄ key out or proceed using the ► key to the end of the series. Page 4-2 TestEquity 1007C Temperature Chamber...
The % of throttle of the heat (positive number) or cool (negative number) output. Real-time clock date. Date Real-time clock time. Time TESTEQUITY 1007C Identifies the chamber model number. Go to Operations Access to Operations Page Access to Profiles Page Go to Profiles Access to Setup Page. Not displayed if running a profile.
Choose Event Output prompt. 85.0°C ▲ ► DigitalOut1______ █ Press the ◄ key once to return back to the Main Page. Power1 50% ▼ You will see a 1 in the DigitalOut line if Event1 is Page 4-4 TestEquity 1007C Temperature Chamber...
• Event outputs 1 through 7 to turn ON or OFF (For controlling the power to remote devices.) • Rate (in degrees per minute) • Temperature Set Point • PID set (One of five sets of PID tuning parameters. Normally, just leave at PID Set 1.) • **Guaranteed Soak TestEquity 1007C Temperature Chamber Page 4-5...
Page 26
Define the End by choosing Hold, Control Off, All Off or Idle end state. NOTE: TestEquity recommends having the end step type to be Hold or Idle. TestEquity does NOT recommend using an end step type of Control Off or All Off. This does not turn off the chamber fan.
► Idle Save your settings. Save profile data • Press ◄ to exit the Profiles Page. or restore values? • After exiting the Profiles Page, choose ▲ to save ▼ Restore ▲ Save profile data. TestEquity 1007C Temperature Chamber Page 4-7...
• TestEquity recommends having the end step type to be Hold or Idle. • TestEquity does NOT recommend using an end step type of All Off or Control Off. This does not turn off the chamber fan. The chamber temperature can reach +55°C just from heat generated by the fan, and even higher if your test sample is energized.
Page 29
While running a profile, the Main Page on the lower display will keep you informed about the progress of the profile. Use the ▲or ▼ key to scroll through the list of running profile parameters. You cannot manually change any operating condition while the profile is running. TestEquity 1007C Temperature Chamber Page 4-9...
• Press ▲or ▼ to scroll through your choice. ▲ Edit Profile • Press ► to select your choice. ► Delete Profile █ • The controller will prompt you to select the profile Re-Name Profile you want to delete or re-name. Page 4-10 TestEquity 1007C Temperature Chamber...
• A Jump Step that jumps to an End Step cannot be deleted. • An End Step cannot be deleted. • Inserting a new ramp step usually requires inserting an associated soak step. • Deleting a ramp step usually requires deleting the associated soak step. TestEquity 1007C Temperature Chamber Page 4-11...
Chapter 4 – Temperature Controller Profile Examples The following are examples of two typical profiles Note that Digit Out 1 is named CONDITION. Page 4-12 TestEquity 1007C Temperature Chamber...
The solid state relays are rated for 24 to 240 VAC, 3.0 Amps. However, TestEquity recommends derating the maximum current to 2.5 Amps. The solid state relay mounting board is UL recognized/CSA certified for 120 VAC max. with the board-mounted fuses;...
The Operations Page provides access to menus for control tuning (PID) and controller alarms. TestEquity has configured the security to require a password for access to all parameters in the Operations Page. You must call TestEquity at 877-512-3457 or 805-480-0638 to obtain the password.
Chapter 4 – Temperature Controller Factory Page The Factory Page provides access to menus for controller diagnostics and calibration. TestEquity has configured the security to require a password for access to the Setup Page. However, there will be times when entry into these menus is necessary. For example, you may need to gain access to Factory Page in order to perform a calibration, or to change the security password.
Not all features or functions are applicable. Only the capabilities of a model PM6L1AJ-AAAABAA are applicable. ! CAUTION: The EZ-Zone Limit Controller has been properly configured by TestEquity to match the chamber’s system requirements. Improper modifications to these setup values can result in unreliable and unsafe operation. Do not attempt to modify the setup values, unless you thoroughly understand what you are doing.
Then, you must press the RESET or EZ Key to resume normal operation. Silencing the Audible Alarm Turning off the MASTER switch on the chamber front panel lets you temporarily turn off the Audible Alarm, even though the High or Low Limit condition may still exist. Page 5-2 TestEquity 1007C Temperature Chamber...
3. Locate the terminal strip on the electrical subpanel. Connections to the safety contacts are at terminals A1 and A2 on the terminal strip. Terminal Strip A1 A2 Figure 5-2 – Location of Safety Contact Connections on the Electrical Sub Panel TestEquity 1007C Temperature Chamber Page 5-3...
Connect the power cord from the Dry Air system to the DRY AIR POWER socket on the rear panel. This plug must be twisted clockwise to lock it. The Dry Air system requires 8 cfm of compressed air at 100 psig (175 psig max). TestEquity 1007C Temperature Chamber Page 6-1...
A suggested starting setting is 4 SCFM. Relief Vent Excess pressure in the chamber workspace is vented through a pressure-relief check-valve, which is located on the top of the chamber. There is no need to vent this externally. Page 6-2 TestEquity 1007C Temperature Chamber...
50 Hz rating of 200 V. This transformer is available from TestEquity for a reasonable cost and is easy to install in the field. Note that the cooling performance will be reduced by 17% at 50 Hz. Please call TestEquity for details on reconfiguring for 50 Hz operation.
Page 44
“How to inspect the refrigeration machinery compartment” and “How to check the refrigerant charge” before placing the chamber back into service to make sure that no damage has occurred. Page 7-2 TestEquity 1007C Temperature Chamber...
Page 45
Can/Should I put a filter in front of the condenser air inlet? No, TestEquity does not recommend this. Just follow the maintenance procedures and clean the condenser fins periodically.
Chapter 8 – Specifications Chapter 8 – Specifications Model 1007C Chamber Specifications Temperature Range –73°C to +175°C Control Tolerance ±0.5°C (±0.2°C Typical) (Measured at the control sensor after stabilization) Uniformity ±0.5°C (Variations throughout the chamber after stabilization) Live Load Capacity @ +23°C...
• Check the low-stage refrigeration charge. • Check the high-stage refrigeration charge. • Verify the chamber performance. Every 6 Months • Inspect the electrical compartment. • Clean the condenser. Every 12 Months • Verify the calibration. TestEquity 1007C Temperature Chamber Page 9-1...
• If you (the cleaner) are in doubt about the compatibility of the cleaning or decontamination agents with the door seal, the interior, or other parts of the equipment, you (the cleaner) should contact TestEquity or an authorized TestEquity agent. How to listen for abnormal noise or vibration.
4. If you see bubbles or it appears partially full, then this indicates that there is probably a leak. 5. When the Temperature Controller is cycling (Cool Light cycles on/off), the sightglass may appear 1/2 to 2/3 full. This is normal. TestEquity 1007C Temperature Chamber Page 9-3...
These tests assume that the Temperature Controller’s setup and tuning values have not been changed from the values as shipped from TestEquity. Also, the Limit Controller high limit must be set to over +85°C (+88°C would be fine), and the low limit set to –75°C.
Page 53
18. Set the Temperature Controller Set Point to +23°C. The chamber should begin to heat up. The compressors should turn off within approximately 1 minute. 19. This concludes the chamber performance verification tests. 20. Let the chamber heat up to +23°C before turning the Master Switch OFF. TestEquity 1007C Temperature Chamber Page 9-5...
How to verify the calibration. TestEquity recommends verifying the calibration before attempting to actually perform a calibration. The state-of-the-art instrumentation used in TestEquity chambers is of the highest quality and seldom goes out of calibration. If you try to calibrate the instrumentation before determining that calibration is necessary, you may make it worse if done incorrectly.
The Low-Stage uses refrigerant R-508B. High pressure liquid refrigerant is fed from the condenser circuit of the cascade condenser, through the filter-drier and liquid-line solenoid valve to the capillary tube/strainer assembly. The capillary tubes feed the finned evaporator coil, which TestEquity 1007C Temperature Chamber Page 9-7...
Page 56
The low-stage compressor turns on 30 seconds after the high-stage turns on through Timing Module TM1. This reduces the system’s starting current, while allowing the cascade condenser to get cool before the low-stage turns on. Page 9-8 TestEquity 1007C Temperature Chamber...
Moisture or debris in the refrigeration system. DPS2 trips. (pressure switch on the rear left side) Trips when the cool light cycles Hot gas bypass regulator may to OFF. be defective or set too low. TestEquity 1007C Temperature Chamber Page 9-9...
Page 58
Chamber has been off for R-404A crankcase heater several hours or more, and is defective (open). connected to source of power and main disconnect switch is on during that time. Page 9-10 TestEquity 1007C Temperature Chamber...
These are NOT do-it-yourself instructions! R-404A High-Stage Charge TestEquity does NOT recommend charging the system by relying on a clear sight glass only. Although a clear sight glass generally means the system is fully charged, it can be misleading.
Chapter 9 – Maintenance Recommended Spare Parts Replacement parts are available from TestEquity. Parts are generally in-stock and ready for immediate shipment. Next-day delivery is always available. If you cannot risk being out of service for even one day, then you should purchase critical spare parts in advance. Although most parts are standard and available from a variety of local distributors, some parts are either harder to find or custom.
“Full Defaults”, you must reconfigure all System and Operation Parameters as documented in the TestEquity manual, NOT the “Series F4 User’s Manual”. TestEquity has configured the Temperature Controller with the parameters as documented on the following pages. TestEquity 1007C Temperature Chamber...
NOTE: The alarm outputs of the Power-Out Action Continue Temperature Controller are NOT connected Communications Menu to the chamber’s safety system. TestEquity Analog Input Menu Main Page\Go to Setup\ does NOT recommend using the Communications Main Page\Go to Setup\Analog Input1 Temperature Controller’s alarm function as...
The Series F4 Controller has several levels of security to prevent unauthorized users from changing critical configuration parameters. Only the Set Point and Profile menus have “Full Access”. TestEquity has configured all other menus to “Password”, and have protected them with a password.
Improper modifications to these setup values can result in erratic performance and unreliable operation. Do not attempt to modify the setup values, unless you thoroughly understand what you are doing. If there is any doubt, please call TestEquity before proceeding. Setup Menu Prompt...
If the repair or replacement is performed in the FIRST YEAR from the date of invoice, TestEquity will also pay for the labor associated with the repair at the Purchaser's site, subject to TestEquity’s prior approval. During the SECOND and THIRD YEAR of the warranty period, Purchaser will be responsible for the installation and cost of installation of replacement or repaired parts.
Need help?
Do you have a question about the 1007C and is the answer not in the manual?
Questions and answers