Appendix A - Signal Sources - ABB SM1000 User Manual

Videographic recorder
Hide thumbs Also See for SM1000:
Table of Contents

Advertisement

Videographic Recorder
SM1000
Appendix A – Signal Sources
Source Name
Analog Sources
Analog I/P A1
to
Analog I/P B6
Comms AIN 1 to 24
Stats 1.1 max
to
Stats 2.6 max
Stats 1.1 min
to
Stats 2.6 min
Stats 1.1 avg
to
Stats 2.6 avg
Error States
AIN A1 fail
to
AIN B6 fail
Comms AIN 1 fail
to
Comms AIN 24 fail
Stats 1.1 fail
to
Stats 2.6 fail
Archive media not present
Too many files on archive media
Archive 100% full
Archive 80% full
Archive media present
Archive on-line
Digital Input States
Digital I/P A1
to
Digital I/P D6
BCD digital I/P D0
to
BCD digital I/P D31
Table A.1 Signal Sources
104
Description
Analog input values (from Analog input module). Available only if an analog input module is fitted in the
relevant position.
Analog input values. Received via the Modbus/Modbus TCP serial communications link – see Appendix B,
page 106.
Maximum Statistics Input Value. Value since the totalizer on a given channel last wrapped or reset. Available
only on analog channels and if the relevant totalizer is enabled in the Configuration level.
Minimum Statistics Input Value. Value since the totalizer on a given channel last wrapped or reset. Available
only on analog channels and only if the relevant totalizer is enabled in the Configuration level.
Average Statistics Input Value. Value since the totalizer on a given channel last wrapped or reset. Available
only on analog channels and only if the relevant totalizer is enabled in the Configuration level.
Analog Input Failure. Active when the signal detected at the analog input is outside the 'Fault Detect Level'
specified in Section 4.6.2.
Totalizer Input Value Failure. Activated when the totalizer fails, cleared when the totalizer wraps or is reset.
Available only for analog channels if the relevant totalizer is enabled in the Configuration level.
Active when the removable archive media is not present.
Active when there are approximately 300 files on the removable archive media.
Active when the removable archive media is 100% full.
Active when the removable archive media is 80% full.
Active when the removable archive media is present.
Active when archiving is in progress.
Digital Input States. From optional hybrid I/O boards fitted at module positions C or D or from analog input
modules fitted at module positions A or B if input 'Type' is set to 'Volt free digital input' – see Section 4.6.2,
page 74. Available only if the module is fitted.
BCD (Binary Coded Decimal) Digital Input States. Digital states derived from digital inputs D1 to D6.
Available only if optional hybrid I/O board is fitted in module position D.
Appendix A – Signal Sources
IM/SM1000 Issue 11