Page 2
Every precaution has been taken in the preparation of this manual. Nevertheless, Procon Electronics assumes no responsibility, express or implied, for errors or omissions or any damages resulting from the use of the information contained in this publication. All trademarks belong to their respective owners. PROCON ELECTRONICS CANopen PC6RO...
1. Introduction The PC6RO module has 6 normally open/ normally closed relay outputs. These modules may be used when a higher drive capability is required, or when isolation between outputs are required. The module plugs into a special bus connector which fits inside the DIN rail. The power supply voltage and the CAN bus signals are connected via this bus connector.
Operating Temperature. -20°C to + 70°C Storage Temperature -40°C to + 85°C Connectors Logic Power and Comms. 5 way connector that clips onto DIN rail Inputs 6 x 3 Way screw connector on top and bottom PROCON ELECTRONICS CANopen PC6RO...
3. Physical Information 3.1 Physical Dimensions The PC6RO enclosure is shown below. The module clips directly onto an industry standard DIN rail. Field wiring is on the top and bottom of the module via 6 plug-in connectors. The module power and CAN communications wiring is on a separate connector which clips onto the DIN rail on the back of the housing.
Do not force the module onto the connector otherwise the module or connector may be damaged. Note: The modules are not designed for hot plug in. The power must be turned off before the modules are plugged into the base. PROCON ELECTRONICS CANopen PC6RO...
To eliminate the presence of reflections from the end of the cable, the cable must be terminated at both ends with a resistor across the line equal to its characteristic impedance. Both ends must be terminated since the direction of propagation is bi-directional. This termination is typically 120 ohms. PROCON ELECTRONICS CANopen PC6RO...
CAN port. The user is welcome to change the dip switches while the module is powered, however, a reset must be initiated afterward. The DIP switch can be toggled using a small flat blade screwdriver, or equivalent tool, as shown in the picture below. PROCON ELECTRONICS CANopen PC6RO...
Before the internal node id is selected, the user must first write the correct id value to the Module ID object in the manufacturer segment. The object address is 2001h. The node id can be configured from 1 to 127. PROCON ELECTRONICS CANopen PC6RO...
Before the internal baud rate is selected, the user must first write the correct baud rate value to the Module Baud Rate object in the manufacturer segment. The object address is 2002h. The following baud rates are supported. BAUD RATE OBJECT VALUE (2002h) kbits/s 1000 PROCON ELECTRONICS CANopen PC6RO...
CAN GND terminals on the modules together. This ensures that all of the modules are at the same potential. The ground wire must be earthed at one end only. CANL CANL network connection CANH CANH network connection PROCON ELECTRONICS CANopen PC6RO...
Indicates a CANopen error. Output Status: “OFF” when the output is off “ON” when the output is on. R = CANopen RUN state P = Power T = CANopen Error Output Status 1 - 6 Switch 1 Switch 8 PROCON ELECTRONICS CANopen PC6RO...
At least one of the error counters of the CAN controller has reached or exceeded the warning limit. Double flash Error Control Event A guard event (NMT- Slave or NMT- Master) or a Heartbeat event has occurred. Bus Off The CAN controller is bus-off. PROCON ELECTRONICS CANopen PC6RO...
The error register is a field of 8 bits, each for a certain error type. If an error occurs the bit has to be set. Meaning generic error communication error (overrun, error state) INDEX 1001 Name Error Register Object Code Variable Data Type UNSIGNED8 Access PDO Mapping Default Value 0x00 PROCON ELECTRONICS CANopen PC6RO...
Data Type UNSIGNED32 Sub-Index Description Number of Errors Access PDO Mapping Default Value 0x00000000 Sub-Index Description Standard Error Field Data Type UNSIGNED32 Access PDO Mapping Default Value 0x00000000 Sub-Index Description Standard Error Field Data Type UNSIGNED32 PROCON ELECTRONICS CANopen PC6RO...
Page 20
Standard Error Field Data Type UNSIGNED32 Access PDO Mapping Default Value 0x00000000 Sub-Index Description Standard Error Field Data Type UNSIGNED32 Access PDO Mapping Default Value 0x00000000 Sub-Index Description Standard Error Field Data Type UNSIGNED32 Access PDO Mapping PROCON ELECTRONICS CANopen PC6RO...
Page 21
Data Type UNSIGNED32 Access PDO Mapping Default Value 0x00000000 Sub-Index Description Standard Error Field Data Type UNSIGNED32 Access PDO Mapping Default Value 0x00000000 Sub-Index Description Standard Error Field Data Type UNSIGNED32 Access PDO Mapping Default Value 0x00000000 PROCON ELECTRONICS CANopen PC6RO...
UNSIGNED32 Access PDO Mapping Default Value 0x00000080 7.2.5 Object 1008h: Manufacturer Device Name Contains the device name. INDEX 1008 Name Manufacturer Device Name Object Code Variable Data Type VISIBLE_STRING Access CONST PDO Mapping Default Value PC6RO PROCON ELECTRONICS CANopen PC6RO...
CONST PDO Mapping Default Value V01.00 7.2.7 Object 100Ah: Manufacturer Software Version Contains the device software version. INDEX 100A Name Manufacturer Software Version Object Code Variable Data Type VISIBLE_STRING Access CONST PDO Mapping Default Value V01.00 PROCON ELECTRONICS CANopen PC6RO...
The life time factor multiplied with the guard time gives the life time for the device. It is 0, if not used. INDEX 100D Name Life Time Factor Object Code Variable Data Type UNSIGNED8 Access PDO Mapping Default Value 0x00000000 PROCON ELECTRONICS CANopen PC6RO...
Error Mode 6 Output Lines 6206h Fault State 6 Output Lines 6207h INDEX 1010 Name Store Parameter Field Object Code Array Data Type UNSIGNED32 Sub-Index Description Number of Entries Access PDO Mapping Default Value Sub-Index Description Save all Parameters PROCON ELECTRONICS CANopen PC6RO...
Default Value 0x00000000 7.2.11 Object 1011h: Restore Default Parameters This entry supports restoring of default parameters. With a read access the device provides information about its capabilities to restore these values. Several parameter groups are distinguished. PROCON ELECTRONICS CANopen PC6RO...
Page 27
Number of Entries Access PDO Mapping Default Value Sub-Index Description Restore all Default Parameters Data Type UNSIGNED32 Access PDO Mapping Default Value 0x00000000 Sub-Index Restore Communication Default Description Parameters Data Type UNSIGNED32 Access PDO Mapping Default Value 0x00000000 PROCON ELECTRONICS CANopen PC6RO...
UNSIGNED32 Access PDO Mapping Default Value 0x00000000 7.2.12 Object 1014h: COB-ID EMCY COB-ID used for emergency message (Emergency Producer). INDEX 1014 Name COB-ID EMCY Object Code Variable Data Type UNSIGNED32 Access PDO Mapping Default Value 0x00000080 PROCON ELECTRONICS CANopen PC6RO...
The lower 16 bits contain the heartbeat time INDEX 1016 Name Heartbeat Consumer Entries Object Code Array Data Type UNSIGNED32 Sub-Index Description Number of Entries Access PDO Mapping Default Value 0x02 Sub-Index Description Consumer Heartbeat Time 1 Data Type UNSIGNED32 PROCON ELECTRONICS CANopen PC6RO...
The producer heartbeat time defines the cycle time of the heartbeat. If the time is 0 it is not used. The time has to be a multiple of 1 msec INDEX 1017 Name Producer Heartbeat Time Object Code Variable Data Type UNSIGNED16 Access PDO Mapping Default Value 0x00000000 PROCON ELECTRONICS CANopen PC6RO...
IDENTITY Sub-Index Description number of entries Access PDO Mapping Default Value Sub-Index Description Vendor Id Data Type UNSIGNED32 Access PDO Mapping Default Value 0x000003AD Sub-Index Description Product Code Data Type UNSIGNED32 Access PDO Mapping Default Value PROCON ELECTRONICS CANopen PC6RO...
Page 32
Sub-Index Description Revision number Data Type UNSIGNED32 Access PDO Mapping Default Value Sub-Index Description Serial number Data Type UNSIGNED32 Access PDO Mapping Default Value PROCON ELECTRONICS CANopen PC6RO...
3 .. 127 reserved INDEX 1029 Name Error Behaviour Object Code Array Data Type UNSIGNED8 Sub-Index Description Number of Entries Access PDO Mapping Default Value Sub-Index Description Communication Error Data Type UNSIGNED8 Access PDO Mapping Default Value PROCON ELECTRONICS CANopen PC6RO...
Number of Entries Access PDO Mapping Default Value Sub-Index Description COB-ID Client -> Server Data Type UNSIGNED32 Access PDO Mapping Default Value 0x00000600 Sub-Index Description COB-ID Server -> Client Data Type UNSIGNED32 Access PDO Mapping Default Value 0x00000580 PROCON ELECTRONICS CANopen PC6RO...
Sub-Index Description Number of Entries Access PDO Mapping Default Value 0x03 Sub-Index Description COB-ID Data Type UNSIGNED32 Access PDO Mapping Default Value 0x00000200 Sub-Index Description Transmission Type Data Type UNSIGNED8 Access PDO Mapping Default Value 0xFF PROCON ELECTRONICS CANopen PC6RO...
Receive PDO Mapping Name Parameter 1 Object Code Record Data Type PDO_MAPPING Sub-Index Description Number of Entries Access PDO Mapping Default Value 0x08 Sub-Index Description Mapping Entry 1 Data Type UNSIGNED32 Access PDO Mapping Default Value 0x62000108 PROCON ELECTRONICS CANopen PC6RO...
Page 37
Default Value 0x00050008 Sub-Index Description Mapping Entry 4 Data Type UNSIGNED32 Access PDO Mapping Default Value 0x00050008 Sub-Index Description Mapping Entry 5 Data Type UNSIGNED32 Access PDO Mapping Default Value 0x00050008 Sub-Index Description Mapping Entry 6 PROCON ELECTRONICS CANopen PC6RO...
Page 38
Data Type UNSIGNED32 Access PDO Mapping Default Value 0x00050008 Sub-Index Description Mapping Entry 7 Data Type UNSIGNED32 Access PDO Mapping Default Value 0x00050008 Sub-Index Description Mapping Entry 8 Data Type UNSIGNED32 Access PDO Mapping Default Value 0x00050008 PROCON ELECTRONICS CANopen PC6RO...
Object Code Variable Data Type UNSIGNED8 Access PDO Mapping Default Value 0x7F 7.3.2 Object 2002h: Module Baud Rate INDEX 2002 Name Module Baud Rate Object Code Variable Data Type UNSIGNED8 Access PDO Mapping Default Value 0x04 PROCON ELECTRONICS CANopen PC6RO...
6200 Name Write State 6 Output Lines Object Code Array Data Type UNSIGNED8 Sub-Index Description Number of Elements Access PDO Mapping Default Value Sub-Index Description digital Outputs 1-6 Data Type UNSIGNED8 Access PDO Mapping Default Value PROCON ELECTRONICS CANopen PC6RO...
Polarity 6 Output Lines Object Code Array Data Type UNSIGNED8 Sub-Index Description Number of Elements Access PDO Mapping Default Value Sub-Index Description Polarity for digital Outputs 1-6 Data Type UNSIGNED8 Access PDO Mapping Default Value 0x00 PROCON ELECTRONICS CANopen PC6RO...
Error Mode 6 Output Lines Object Code Array Data Type UNSIGNED8 Sub-Index Description Number of Elements Access PDO Mapping Default Value Sub-Index Fault Mode for digital Outputs 1- Description Data Type UNSIGNED8 Access PDO Mapping Default Value 0x3F PROCON ELECTRONICS CANopen PC6RO...
Fault State 6 Output Lines Object Code Array Data Type UNSIGNED8 Sub-Index Description Number of Elements Access PDO Mapping Default Value Sub-Index Fault State for digital Outputs 1- Description Data Type UNSIGNED8 Access PDO Mapping Default Value 0x00 PROCON ELECTRONICS CANopen PC6RO...
Access PDO Mapping Default Value Sub-Index Description digital Output 1 Data Type BOOLEAN Access PDO Mapping Default Value Sub-Index Description digital Output 2 Data Type BOOLEAN Access PDO Mapping Default Value Sub-Index Description digital Output 3 PROCON ELECTRONICS CANopen PC6RO...
Page 46
Output 4 Data Type BOOLEAN Access PDO Mapping Default Value Sub-Index Description digital Output 5 Data Type BOOLEAN Access PDO Mapping Default Value Sub-Index Description digital Output 6 Data Type BOOLEAN Access PDO Mapping Default Value PROCON ELECTRONICS CANopen PC6RO...
The IO Modules are only allowed to be installed wit out voltage app lied and by qualified personnel. General safety regulations and nationally applicable accident prevention guidelines must be observed. Electrical installation must be carried out according to the relevant guidelines (e.g. line cross section, fuse, protective ground connection). PROCON ELECTRONICS CANopen PC6RO...