Front View - M-system R7F4HML3-D-DAC32B Instruction Manual

Npn/pnp discrete input & pnp transistor output module, 16 points each (mechatrolink- iii use)
Hide thumbs Also See for R7F4HML3-D-DAC32B:
Table of Contents

Advertisement

FRONT VIEW

Station Address Setting Rotary SW
MECHATROLINK-III Connector
Power Supply Connector
■ STATUS INDICATOR LED
ID
COLOR FUNCTION
PWR
Green
Turns on when the internal power is sup-
plied normally.
ERR
Red
Turns on at MECHATROLINK-III com-
munication error
CON
Green
Turns on at MECHATROLINK-III con-
nection is established
LNK1
Green
Turns on at MECHATROLINK-III LNK1
is established
LNK2
Green
Turns on at MECHATROLINK-III LNK2
is established
■ STATION ADDRESS
Station Address is selected between 03H and EFH in hexa-
decimal.
The SA1 switch determines the MSD, while the SA2 switch
does the LSD of the address.
(Factory setting: 03H)
SA1
LNK1
LNK2
×10
Station Address Setting (LSD)
Station Address Setting (MSD)
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: + 81 ( 6 ) 6659-8201 Fax: + 81 ( 6 ) 6659-8510 E-mail: info@m-system.co.jp
Operating Mode Setting DIP SW (SW1)
Status Indicator LED
SA2
×1
PWR
CON
LNK2
ERR
LNK1
1 2 3 4
ON
I / O Connector
■ OPERATING MODE
• Read Rate (SW1-1, 1-2, 1-3)
SW1-1
SW1-2
OFF
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
OFF
OFF
ON
ON
ON
• Output at Loss of Communication (SW1-4)
SW1-4
Output at loss of communication
OFF
Reset the output (turned off)
ON
Hold the output (*)
(maintains the last data received normally)
(*) Factory setting
■ DISCRETE I / O STATUS INDICATOR LED
LED green indicators shows the signal status.
ON: LED ON
OFF: LED OFF
R7F4HML3-D-DAC32B
Discrete Input Status Indicator LED
SW1-3
Read rate
OFF
≤10 msec. (*)
OFF
≤1 msec.
OFF
≤5 msec.
OFF
≤20 msec.
ON
≤50 msec.
ON
≤70 msec.
ON
≤100 msec.
ON
≤200 msec.
EM-8002-B Rev.2 P. 2 / 12