Pressure switch

Advertisement

Please read all instructional literature carefully and thoroughly before starting. Refer to the final page for the list-
ing of Recommended Practices, Liabilities and Warranties.
GENERAL
BEFORE INSTALLING, CHECK THE SENSOR
MODEL SELECTED FOR COMPATIBILITY TO
THE PROCESS MEDIA IN CONTACT WITH THE
SENSOR AND WETTED PARTS.
J6 pressure switches are activated when a bellows or piston
sensor responds to a pressure change. This response
actuates a single snap-action switch, converting the
pressure signal into an electrical signal.
Set point may be varied by turning the internal adjustment
screw according to procedures outlined below.
Part I - Installation
MOUNTING
J6 pressure switches may be mounted and operated in
any position. They may be surface mounted via the two
mounting ears on either side of the enclosure, or mounted
directly to a rigid pipe by using the pressure connection.
LOCATE THE UNIT WHERE VIBRATION, SHOCK
AND AMBIENT TEMPERATURE CHANGES ARE
MINIMAL. SHOULD THE UNIT BE INSTALLED
WHERE CONDENSATION IS EXPECTED, VERTICAL
MOUNTING IS RECOMMENDED.
NEVER USE THE ENCLOSURE FOR LEVERAGE
TO
HAND
TIGHTEN
CONNECTION. ALWAYS USE A WRENCH TO
TIGHTEN THE PRESSURE CONNECTION TO THE
PIPE.
6 Series
Pressure Switch
Tools Needed
-Adjustable wrench
- Flatblade screwdriver
THE
PRESSURE
UNITED ELECTRIC
CONTROLS
Installation and Maintenance Instructions
On models supplied with an external manual reset button,
be sure to leave sufficient finger space over the reset button
for the operator to reset the switch.
WIRING
WIRE IN ACCORDANCE WITH LOCAL OR
NATIONAL CODES. BE SURE ALL LIVE SUPPLY
CIRCUITS
ARE
WIRING THE CONTROL. MAXIMUM WIRE SIZE #14
AWG.
Remove the four screws retaining the cover and cover
gasket. A 1/2" NPT conduit connection is provided on the
upper left hand side of the enclosure. The three switch
terminals are clearly labeled common, normally open and
normally closed.
If lead wires are supplied, color coding is as follows:
SPDT
Common
Violet
Normally Open
Blue
Normally Closed
Black
A threaded grounding boss, tapped #10-32, is provided in
the lower left corner of the enclosure. Keep the wires as
short as possible to prevent interference with the plunger,
manual reset button and, when provided, the adjustable
differential switch wheel.
IM6-02
DISCONNECTED
BEFORE