Specifications - S-Tech STCH-1000 Owner's Manual

Table of Contents

Advertisement

2.

SPECIFICATIONS

METHANE ALARM LEVEL
POWER SOURCE
OPERATING TEMPERATURE
ALARM SOUND LEVEL
MINIMUM ALARM TIME
DETECTION FREQUENCY
RELAY RATED INDUCTIVE LOAD
RELAY MAX. SWITCHING POWER
3. RECOMMENDED LOCATIONS OF DETECTORS:
• Install at least one natural (methane) gas detector on every floor level (see Figure
1).
• Install the detector close to every place that gas operated appliances are installed
(see Figure 1).
• Since natural (methane) gas is lighter than air (1:0.56), the greatest concentration
of gas will be immediately under the ceiling. Mount detectors on the wall with the
top edge of the detector at a minimum of 6" (15cm) and a maximum of 12" (30.5
cm) below the ceiling, and at least 2 feet (60.1 cm) from any corner (see Figure 2).
• If the ceiling is sloped or higher than 8.5 feet (2.6 m), please ask your local Gas
Company for advice about proper installation.
BEDROOM
+
GAS
DRYER
DINNING
LIVING ROOM
+
Detector placement
for minimum protection.
BEDROOM
+
+
BEDROOM
+
HEATER
+
GAS OVEN
KITCHEN
BEDROOM
+
BEDROOM
- 3 -
Additional detector
location for added protection.
10 – 25% L.E.L.
120VAC, 60Hz, 5 WATTS (FOR MODELS
STCH-1000,
1000HW, STCH-1000HWR)
12VDC, 5 WATTS (FOR MODEL PSM-
011)
32° F (0° C) TO 104° F (40° C)
85 dB AT 10 FEET
5 MINUTES
SAMPLING EVERY SECOND
0.2A at 125VAC; 1A at 30VDC
25VA, 30W
FIGURE 1
Ceiling
BEDROOM
STCH-1000LC,
STCH-
6 IN
Dead Air
Space
6 IN
Never Here
12 IN
Acceptable Here
Side Wall
FIGURE 2