Summary of Contents for Monicon Instruments AVR-15
Page 1
Monicon International Co., Ltd AVR-15 AVR-15 User Manual Site:http://www.monicon.com.tw E - m a i l :s a l e s @ m o n i c o n . c o m . t w...
Page 2
2. Wiring: : : : The range of sensing the phase voltage in the AVR-15 is AC 110 /220V. The input voltage for AVR-15 is 100 ~ 240VAC, 50/60Hz. Please follow the instructions and wiring diagram for the AVR-15 to prevent any malfunctions.
Page 3
Monicon International Co., Ltd AVR-15 3.3 Genset Voltage Fine Tune(Volt): : : : After Genset has successfully started and in rated speed, slowly turn Volt clockwise to the rated voltage. (If EXT.VR is connected with a potentiometer, please adjust the potentiometer to the center position) 3.4 Genset Stabilization Adjustment(Stable):...
Page 4
Monicon International Co., Ltd AVR-15 used to excite the magnetism. Please make sure the generator has been completely shut down before proceed to step 3. 4.3 . Please shut down the generator before perform the following steps 4.3.1 Disconnect AVR terminals (F+) and (F-), then use 3-12V DC (e.g. battery) as power source and connect the positive terminal to a current limiting resistor 5~50Ω/30W, then connect to the positive terminal of the Genset and...
Page 5
Monicon International Co., Ltd AVR-15 Low Frequency Protection Low Frequency Protection: Genset 60 Hz: Lower than 55Hz, AVR ceases Low Frequency Protection Low Frequency Protection output (Default setting) Genset 50 Hz: Lower than 45Hz, AVR ceases output (Default setting) EMI Protection:...