Contents 1. General information ................4 2. Precautions ..................5 3. Warning notice ................... 6 4. What to do when there is a fire? ............7 5. Properties of the Genius H ..............8 ® 6. Mounting location and planning ............10 7. Installing the smoke detector ............13 8. Theft and removal protection (accessories) ........15 9. Operating and warning signals ............17 10. Functions of the test button .............. 19 11. Properties of the base .
1. General information In the event of a fire, deadly smoke can spread quickly throughout an entire flat and often goes unnoticed. The Genius H and Genius Hx smoke detec- ® ® tors warn early before these gases has deadly consequences. Thanks to the new smoke detector technology, false-alarm-proof smoke de- tection is achieved even when temperatures fluctuate. This is accomplished by the detector's capability to adapt automatically to normal changes in its environment and thus guarantees constant response sensitivity. The Genius Hx , with its special software algorithms, can even reliably ® detect fire smoke in kitchens, which was not possible with yesterday's detectors because of clouds of steam suddenly rising. The electronics in both smoke detectors is so finely tuned that a smoke detector typically has a service life of 10 years with one battery. Should you wish to have fire and smoke alarms relayed to the fire brigade, or if it is required, a fire alarm control panel compliant to DIN 14675 is available. Hekatron is not liable for expenses which may be incurred as a re- sult of alarming a service point such as a security service or the fire brigade. G 209178...
2. Precautions The purpose of smoke detectors is to warn you early about fire smoke and fires so that you can react quickly to danger with the appropriate measures. Smoke detectors cannot prevent or extinguish fires. These smoke detectors react early and reliably to smoldering fires as well as to open fires that develop smoke. The detector audibly outputs a loud alarm tone and visually a flashing red light when it detects smoke. Ensure that a sufficient number of smoke detectors are mounted. Only in this way is it possible to achieve comprehensive monitoring and maximum security (see page 10). It is not permitted to paint the smoke detector or cover the smoke inlet openings. To ensure trouble-free operation of the smoke detector, the smoke detector must be mounted correctly and maintenance and care instructions must be observed. Hekatron recommends DIN EN 14676 compliance for planning, mounting, commissioning and maintenance. Please read these mounting instructions completely before mounting and commissioning the smoke detector and keep them in a safe place.
3. Warning notice Mount the smoke detector only after all modifications, renovations and similar work have been completed. If smoke detectors are already installed before beginning work, they either have to be removed or covered. The removed smoke detectors must be protected from dust and similar substances during the work (e.g. store in plastic bags). Important: Once all work is completed, the smoke detectors must be remounted and the coverings removed. A smoke detector which is not mounted or is still covered will not function and is therefore useless. When smoke detectors are used in environments with high levels of dust and/or dirt, service life may be reduced due to faster soiling.
4. What to do when there is a fire 1 Save people ■ Alert those who live with you. ■ Immediately leave the room/building and close all doors behind you on the way out; this hinders the rapid spread of smoke and fire. ■ Stay close to the floor if smoke is dense. ■ Check whether all persons have vacated the room/ building. ■ If for any reason you are unable to leave the room/ building, close all doors, seal all gaps and openings, and try to gain someone's attention from the window. 2 Call the fire brigade ■ Call the fire brigade only after you are safe. 3 Extinguish fire ■ Fight the fire yourself only if it does not put you in danger.
5. Properties of the Genius H ® ■ Automatic operational readiness After the smoke detector is screwed into the base, it starts operating automatically. ■ Alarm memory If the smoke detector has an alarm, the LED visually indicates it until it is acknowledged. This means fast localisation. ■ Integrated real-time clock Suppression of status reports which do not influence the operation of the smoke detector from 10 pm to 6 am CET thanks to an integrated real- time clock. Your night time sleep is undisturbed. ■ Reduced light strength Automatic reduction of LED brightness from 10 pm to 6 pm CET by means of the integrated real-time clock. ■ Soiling compensation The detector adjusts its base signal according to the detector's level of soiling and achieves a longer service life than smoke detectors without compensation. In the event that the maximum soiling level is reached through adjustments, a fault is signaled.
Page 9
■ Soiling prognosis Based on the level of soiling up to the present, the smoke detector calculates how long it can still be operated if the rate of soiling remains the same. ■ Active service prognosis A function test automatically generates the soiling prognosis. If the prog- nosis is greater than 15 months, the test is confirmed as positive. ■ Muting The smoke detector can be muted for 10 minutes by pressing the test button when there is an alarm. ■ Time-delayed deactivation Automatic, time-delayed deactivation after unscrewing the smoke detec- tor from its base gives you enough time (5 minutes) to test the smoke detector out of its base.
6. Mounting location and planning The minimum configuration consists of mounting at least one smoke detec- tor in each bedroom, children's room and in the hallways. For the optimal configuration mount at least one smoke detector in all rooms, hallways and entrance areas. Mount the smoke detectors so that smoke from a fire can reach the detector unimpeded to ensure early detection. Minimum configuration Optimal configuration Notice: Please note that living rooms are often used for sleeping.
Page 11
The smoke detector monitors a 60 m² area in a room with a maximum height of 6 m. It must be mounted on the ceiling and centred in the room as much as possible. According to DIN 14676, the detector must be at least 0.5 m from other fittings on the ceiling and from the walls. These fittings also include switched power supplies, such as energy-saving lights, transmitters and similar. If the detector is mounted in a ceiling peak, the following applies concerning the ceiling angle: ■ for a ceiling angle of up to 20°, the detector must be suspended 0.2 m - 0.5 m from the ceiling peak. The detector may be offset to the side and mounted directly on the ceiling or roof. ■ for a ceiling angle greater than 20°, suspended horizontally 0.2 m - 0.5 m from the ceiling peak. Smoke detectors are not intended for outdoor use.
Page 12
6.1 Arrangement of smoke detectors in entrance areas, hallways and in rooms with unusual shapes In entrance areas and hallways with a maximum width of 3 m, the distance between two smoke detectors may be up to 15 m. The distance to the front side of an entrance area may not be greater than 7.5 m. straight-line entrance area or hallway right-angle entrance area or hallway in large entrance areas and hallways in corner areas...
7. Installing the smoke detector Use the supplied fastening materials when mounting the smoke detector. If other screws are used, they must not protrude more than 5.0 mm into the base. We recommend using an oval head screw DIN ISO 7049, Phillips-head screw H, form C, 3.5 x 25 mm. The mounting surface must be flat.
Page 14
One-hole mounting Two-hole mounting 1 Mark the place for the hole on the ceiling 1 Mark the place for the holes on the ceiling and drill the hole. and drill the holes. 2 Insert the dowel into the hole. 2 Insert the dowels into the holes. 3 Remove the protective foil from the adhe- 3 Hold the base onto the ceiling. sive pad. 4 Lightly screw the base onto the ceiling, 4 Screw the base onto the ceiling. press the base to the ceiling and then tighten the screw. 5 Place the detector onto the base (the test button of the smoke detector has to be aligned over the oblong hole in the base). 6 Turn the detector clockwise until the base goes into the smoke detector and snaps into place (rotation of about 45°). Once the detector is fastened in the base, it begins operation automatically and carries out a function test.
8. Theft and removal protection (accessories) To secure the smoke detector against removal by unauthorised persons, removal protection in the form of a seal can be fastened to the detector and base. The seal is fastened to the detector in the housing wall opening. Break out the predetermined breaking point in the base and turn the smoke detector in the base. Predeter- Insert the seal in the opening.
Page 16
After the seal is inserted, the opening must be completely closed. To remove the seal, rotate it 90° using a screwdriver. This shears off the head of the seal and you can then rotate the detector out of the base normally.
9. Operating and warning signals 9.1 Fire alarm Horn Cause What to do Alternating, loud Flashes every Smoke has been Leave the building horn second detected Double flash Alarm memory Search the area for possible every 48 sec. of this smoke de- fire sources. Reset the alarm tector detected memory by pressing the test a fire button. 9.2 Signalling during the day (6 am to 10 pm CET) Horn Cause What to do Flashes every Normal opera- ---- 48 sec.
Page 18
9.3 Signaling at night (10 pm to 6 am CET) Horn Cause What to do Flashes dimly Normal opera- ---- every 48 sec. tion Once every 48 sec. Flashes every Fault Replace smoke detector with 8 sec. a new one. Acknowledge by pressing the test button. 9.4 Signaling after acknowledgement Horn Cause What to do Off for 24 hours Flashes every Weak battery Smoke detector is still after pressing the 48 sec. operational, but it should be test button replaced by a new one within 30 days at the latest (battery replacement not possible).
10. Functions of the test button The test button initiates and acknowledges the various functions of the smoke detector. By lightly pressing the button, you can ... ■ start the functional test in normal operation ■ acknowledge a fault ■ acknowledge/mute an alarm ■ clear the alarm memory. Test 11. Properties of the base When the smoke detector is screwed into the base, it begins operation au- tomatically and carries out a self-test. When the smoke detector is removed from the base, it switches off after 5 minutes. If the Genius H is removed ® from the base during an alarm, the alarm is muted (see also Properties of the Genius H - Muting). ®...
12. Maintenance and care To guarantee the functional reliability of the detector, maintenance is required at least once a year in compliance with DIN EN 14676. Proceed as follows. If needed, remove dust from the detector with a soft cloth. If needed, remove soiling with a moist cloth. Do not use cleaning agents. Press the test button and compare the results with the following: Horn Cause What to do Test signal* 3 x with Smoke detector test No action required. (3 x horn tone) horn positive Every Service prognosis < 15 Replace smoke detector 48 sec. months, detector still as soon as possible. functional Every Weak battery See table 9.4 48 sec. Detector defective Replace smoke detector immediately. * According to standard 14604, audible signalling is sufficient.
13. Note about disposal Consumers are legally responsible for returning all electrical and electronic devices to official collection points. This is an important contribution to environmental protection! Disposing of such devices as household waste is pro- hibited. Securiton has covered the cost for disposal by paying the SWICO-ARF fee for you. The smoke detector is produced in accordance with strict criteria of the quality and environmental management system in compliance with DIN ISO 9001. It fulfills the statutory RoHS requirements and does not contain any prohibited materials. The battery is permanently built into the detector and cannot be replaced.
14. Technical data VdS approval DIN EN 14604 / G number 209178 EU certificate of conformity 0786-CPD-20856 Audible alarm Sound pressure over 85 dB (3 m) Audible alarm perception Frequency optimisation for human hearing Area of application According to DIN 14676 Operation Via test button Automatic operating levels Fault suppression at night from Automatic with real-time clock 10 pm to 6 am CET Fault suppression during day For 24 hours by pressing the test button Reduced light strength of the LED at night from Automatic with real-time clock 10 pm to 6 am CET Voltage supply for detector 1 x lithium battery, 3.6 V, permanently built in * Battery capacity 2.2 Ah Detector battery service life Typically 10 years Automatic self-monitoring Active soiling tracking Alarm memory...
Page 23
Active soiling prognosis Yes, signalling when test button pressed Theft protection With seal (accessory) Optical removal detection With seal (accessory) Storage temperature -10°C to +60°C Ambient operating temperature 0°C to 55°C Humidity ambient condition at ≤ +40°C, 10 to 70% rel. hum. (continuous, without condensation) Protection type IP 40 Colour Pure white, similar to RAL 9010 Material PC ABS Height / diameter dimensions 48 mm x 104 mm Weight approx. 143 g 1-hole mounting / 2-hole mounting Yes/Yes RoHS/WEEE compliant Environmentally compliant disposal Disposal regulated through EAR For reasons of safety, uninterrupted voltage supply is necessary for the smoke detector. Technical and colour subject to change without out notice. No liability for errors or printing mistakes!
15. Genius H and Genius Hx "Real Alarm Guarantee" ® ® and 10-year device guarantee Hekatron (a Swiss Securitas Group company) is a leading German manu- facturer of smoke detectors and guarantees that based on the high product quality of the new smoke detector generation of Genius H and Genius Hx ® ® no false alarms will occur during normal use. The Genius guarantee conditions apply. The Genius guarantee conditions are found at www.hekatron.de. Reference document: 7002589 MA Genius H - Edition 11.02.10 ® 16. Guarantee handling For guarantee handling it is imperative that a return delivery note and a fault log are requested from Hekatron via the supplier. The fault log is also available for downloading on our website at www.heka- tron.de under "Smoke detectors".
17. Ordering information Designation Order number Genius H Hekatron smoke detector in neutral packaging 239 151 Seal set Genius H/Hx VE32 gr Seal set 31-4100003-01-01...