Repotec RP-UPH603T User Manual

On-line 6k-10kva
Hide thumbs Also See for RP-UPH603T:

Advertisement

Quick Links

USER'S MANUAL
On-Line 6K-10KVA
Uninterruptible Power Supply

Advertisement

loading

Summary of Contents for Repotec RP-UPH603T

  • Page 1 USER’S MANUAL On-Line 6K-10KVA Uninterruptible Power Supply...
  • Page 2: Table Of Contents

    CONTENTS 1. Safety Instructions ........…..2. Introduction ....……...………………...….….. 3. System Description .......……..……...…... 4. Connection and Installation ...……..……... 5. UPS Operation ........……..6. Trouble Shooting Guide .....……..…..… 7. Communication Port ....…………………... 8. Product Specification ......……....
  • Page 3: Safety Instructions

    1. Safety Instructions 1.1 Transport ★ Please transport the UPS system only in the original packaging (to protect against shock and impact). 1.2 Set-up ★ Condensation may occur if the UPS system is moved directly from a cold to a warm environment. The UPS system must be absolutely dry before being installed.
  • Page 4 1.4 Operation ★ Do not disconnect the mains cable on the UPS system or the building wiring socket outlet (shockproof socket outlet) during operations since this would cancel the protective earthing of the UPS system and of all connected loads. ★...
  • Page 5 ★ Only persons are adequately familiar with batteries and with the required precautionary measures may replace batteries and supervise operations. Unauthorised persons must be kept well away from the batteries. ★ Caution - risk of electric shock. The battery circuit is not isolated from the input voltage.
  • Page 6: Introduction

    2. Introduction This On-Line Series is an Uninterruptible Power Supply incorporating double-converter technology. It provides perfect protection specifically for Novell, Windows NT and UNIX servers. The double-converter principle eliminates all mains power disturbances. A rectifier converts the alternating current from the socket outlet to direct current.
  • Page 7: System Description

    3. System Description 3.1 Front panel description for LCD model 1. LCD Display: This indicates the UPS operation information, including UPS status, input/output voltage, input/output frequency, battery voltage, battery capacity left, output load, inside temperature, and the times of history events. 2.
  • Page 8 6. Warning LED (yellow): To indicate the UPS is in the status of overload, bypass and battery back-up. 7. Normal LED (green): To indicate the UPS is operating normally. 3.2 Front panel description for LED module 1. Line LED (green): To indicate the AC power is applied to the UPS input.
  • Page 9 4. Inverter LED (green): To indicate the UPS is powered through inverter. 5~9. Load & Battery Capacity LEDs: (a) No. 5 to 8 LED is green color and No. 9 (used as warning LED for overload or battery low) is yellow. (b) These LEDs show the load % of the UPS if the mains power is available (in normal operation).
  • Page 10: Connection And Installation

    Connection and Installation The system may be installed and wired only by qualified electricians in accordance with applicable safety regulations! 4.1 Unpacking and Inspection for 6K(L)/10K(L) 1. Unpack the packaging and check the package contents. The shipping package contains:  A UPS ...
  • Page 11 2. Installation (a) Installation and wiring must be performed in accordance with the local electric code and the following instructions by professional personnel. (b) For safety, please cut off the mains power switch before installation. The battery breaker also needs to be cut off if it is a long backup time model (“L”...
  • Page 12 (g) The protective earth ground wire refers to the wire connection between the equipment which consumes electric equipment and the ground wire. The wire diameter of protective earth ground wire should be at least as above mentioned for each model and green wire or green wire with yellow ribbon wire is used.
  • Page 13 (m) If it is necessary to connect the inductance load such as a monitor or a laser printer to the UPS, the start-up power should be used for calculating the capacity of the UPS, as its start-up power consumption is too big when it is started. Input Ground Output Ground Input Neutral...
  • Page 14 2. The connector of the external battery cable is used to plug into the external battery socket of the UPS. The other end of the external battery cable is made of three open wires with ring terminals to connect with the external battery pack(s). The procedure of installing battery bank should be complied with strictly.
  • Page 15 3. To complete the connection by plugging the connector of the external battery cable into the external battery socket of the UPS. Do not attempt to connect any loads to the UPS now. You should connect the input power wire to the right position first. And then set the breaker of the battery pack in the ON position.
  • Page 16 (c) Connect the output wires of each UPS to an output breaker panel. (d) Disconnect the Jumper on JP1 and JP2 of the terminal block first, and connect each output breaker to a main output breaker and then to the loads. *...
  • Page 17: Ups Operation

    5. UPS Operation 5.1 Check prior to start up 1. Ensure the UPS is in a suitable positioning. 2. Check input cord is secured. 3. Make sure the load is disconnected or in the “OFF” position. 4. Check if input voltage meets the UPS rating required. 5.2 Start-up procedure for LCD model Please follow the instructions below for UPS operation.
  • Page 18 5.3 LCD display menu Use Up/Down key to select menu-displays of the LCD described below. This screen will refresh once the system power is enabled. Rated Spec Status Voltage Frequency...
  • Page 19 Battery Status Output Power Temperature History Record...
  • Page 20 Output and bypass setting Just connect the AC power (don't need to turn on the UPS) and the LCD will light up with the welcome slogan (initial) screen. Then press the Down-key to find the screen and then press Enter-key for setting. Once finished, please disconnect the AC power and then reconnect power again to refresh the setting.
  • Page 21 Output Voltage & Frequency Adjust A. In this screen, press Enter-key to enter the following steps for output voltage and frequency adjustment. B. The cursor (→) will pop up to indicate the output voltage and frequency newly selected. C. Use Up or Down-key to adjust the output voltage (220V, 230V, and 240V ).
  • Page 22 5.4 Start-up procedure for LED model Please follow the instructions below for UPS operation. 1. Once the AC source is connected, Line LED shall light up immediately to indicate ready to switch on the inverter. In case this LED blinks, it means the main AC source is out of tolerance. 2.
  • Page 23 5. 5 Parallel machine maintenance This UPS system has parallel machine function, if you want to add single machine to parallel system, please follow operational process of joining new machine; if because of cutting down load or attainting UPS, and you must remove UPS, please follow operational processes of removing parallel machine.
  • Page 24 (h) Take apart the board of parallel ports when UPS has turned to bypass mode, insert the other end of combine line into parallel card’s slot and screw down its pin; and then lock up the board of parallel ports over again (i) Close line input switch of all UPS (including new UPS) in the parallel system;...
  • Page 25 (c) Turn off other UPS which are running, take apart the maintain cover of every UPS and turn all UPS maintain switch from “UPS” to “BPS” until all running UPS turn to BPS mode. Then turn off every UPS own input switch. (d) After removing single UPS, if leaving UPS system is changed to single running, please connect the short line between JP1 and JP2 of this UPS output port.
  • Page 26 5.6 Backup time for the standard model The backup time of the long backup time model is dependent on the external battery pack capacity and the load level as well as other factors. The backup time of standard model may vary from different models and load level.
  • Page 27 5.7 Battery Maintenance  The battery used for this models are regulated sealed lead-acid maintenance free battery. Please charge the UPS regularly in order to maximize the expected life of the battery. When being connected to the utility power, whether the UPS is turned on or not, the UPS keeps charging the batteries and also offers the protective function of overcharging and over-discharging.
  • Page 28 5.8 Notes for Battery Disposal and Battery Replacement  Before disposing of batteries, remove conductive jewelry such as necklace, wrist watches and rings.  If it is necessary to replace any connection cables, please purchase the original materials from the authorized distributors or service centers, so as to avoid overheat or spark resulting in fire due to insufficient capacity.
  • Page 29: Trouble Shooting Guide

    7. Trouble Shooting Guide 6.1 For LCD Model The following guideline may be helpful for basic problem solving. LED and LCD status ACTION Charger may break down. Please replace charger board. AC utility power is normal. UPS is running normally, but battery capacity is low (referring to Battery Status Menu).
  • Page 30 LED and LCD status ACTION Please reduce the critical load to POWER(%)<100%. AC utility power is normal but UPS is overloaded. Warning LED lits up and buzzer beeps per second. Please reduce the critical load to POWER(%)<100%. AC utility power is normal but UPS is overloaded up to 125%.
  • Page 31 LED and LCD status ACTION Please reduce the critical load to POWER(%)<100%. AC utility power is normal, but the load is supplied by AC utility power via bypass. Output power is more than 150% (referring to the Output Power Menu). Warning LED lits up and buzzer beeps continuously.
  • Page 32 LED and LCD status ACTION UPS will shut down automatically. Please save data soon. AC utility fails. The load is supplied by UPS in backup mode and battery power is approaching low level. Buzzer alarm beeps every second. UPS will restart up when AC utility power is restored.
  • Page 33 6.2 For LED Model The following guideline may be helpful for basic problem solving. UPS STATUS ACTION AC utility power is normal. UPS is Charger may broke down. running normally, but battery capacity is Please replace charger low. Buzzer beeps once every second board.
  • Page 34 UPS STATUS ACTION If AC utility power fails, reduce the less critical load in order to extend backup AC utility power fails .The load is supplied by battery power. Buzzer time. If it is not abnormal alarm sounds every 4 seconds. power failure, please check the rated input or connected line.
  • Page 35: Communication Port

    8. Communication Port 7.1 RS232 Interface The following is the pin assignment and description of DB-9 connector. Pin # Description Output Input Input 7.2 AS400 Interface (Option) Except for the communication protocol as mentioned above, this series UPS has AS400 card (an optional accessory) for AS400 communication protocol.
  • Page 36 DB-9 Interface of AS400 communication protocol...
  • Page 37: Product Specification

    9. Product Specification 8.1 General Specification 10KL Model 10KVA/7KW Power Rating 6KVA/4.2KW 6KVA/4.2KW 10KVA/7KW 50/60 Frequency (Hz) 50/60 50/60 50/60 176~276 V 176~276 V 176~276 V 176~276 V Input 50A max. 31A max. 31A max. 50A max 240V 240V 240V 240V Battery 40A max...
  • Page 38 8.3 Operating Environment Operation Temperature 0°C-40°C Humidity 0- 95% non-condensing Altitude < 1000 M Note: if the UPS is installed or used in a place where the altitude is above than 1000m, the output power must be derated in use, please refer to the following: Altitude (M) 1000 1500...
  • Page 39 Appendix 1-Outline Description and Back Panel Back view of 6K Back view of 6KL...
  • Page 40 Back view of 10K Back view of 10KL...