6.0

Mounting Location

Hydrogen is colorless and odorless; the lightest of all gases and thus rises. The hydrogen
sensor, therefore, should be installed at the highest, draft-free location in the battery
compartment, cabinet, or room where hydrogen gas would accumulate.
The Alarm Box can be mounted at eye level or wherever is convenient for the user.
The size of the area one sensor will protect depends upon the battery compartment or room.
The detector measures hydrogen gas concentration in the air immediately surrounding the
sensor. Hydrogen gas may accumulate in several areas of the battery compartment or room
therefore; individual detectors should be installed in each of these areas.
Mounting and Power Options:
Alarm Wiring
SBS-H2 Users Manual
Pre-March 2016 Version
Wall Mountable
Integrated back mounting plate allows
user to easily mount directly to any wall
using qty.2 3/16" screws (not included).
Wiring
Power and Alarm Wires can be ran
through the sides of the unit
Input Power
Junction Box Mountable
Mounts to a standard, 4 11/16" x 4 11/16"
2-gang junction box (SBS Part# H2-JB).
Hardwire
Run AC or DC power and alarm wires through
back of the unit, into the gang box and out
through conduit.