Raychem H910 Installation Instructions Manual

Raychem H910 Installation Instructions Manual

Wintergard splice and tee kit with end seal

Advertisement

Quick Links

Approvals
Kit Contents:
Item
Qty
Description
A
2
Insulated bus wire crimps
B
1
Uninsulated braid crimps
C
3
Cable ties
D
6
Mastic strips
E
1
Heat-shrinkable cap
F
1
Heat-shrinkable tube (6" long, 1" dia.)
G
1
Black cloth tape (6" long)
H
1
Clamp tie
I
1
End seal
WARNING:
This component is an electrical device that must be
installed correctly to ensure proper operation and to
prevent shock or fire. Read these important warnings
and carefully follow all the installation instructions.
• To minimize the danger of fire from sustained
electrical arcing if the heating cable is damaged
or improperly installed, and to comply with the
requirements of Tyco Thermal Controls, agency
certifications, and national electrical codes, ground-
fault equipment protection must be used. Arcing may
not be stopped by conventional circuit breakers.
• Bus wires will short if they contact each other. Keep
bus wires separated.
H910
WinterGard

Installation Instructions

Description
The WinterGard
self-regulating heating cables to make splice, tee, and end seal con-
nections. The kit contains materials for one splice and one end seal, or
one tee connection and one end seal. This kit does not provide a power
connection; use an H900 or H908 power connection kit for a complete
installation.
Applications
Use the H910 kit with the following WinterGard heating cables:
H311, H611, H612, H621, and H622. All are designed for pipe
freeze protection in dry locations, but H612 and H622 cables are
designed for both wet and dry areas, as well as for roof and gutter
de-icing. The cable type is printed on the outer jacket of the cable.
Tools Required
• Diagonal Cutters
• Utility knife
• Crimp tools (Ideal 30-425 and T&B WT112M or WT2000)
• Hammer and nail (for gutter/downspout applications only)
Installation and Support
The minimum installation temperature for this kit is 0°F (–18°C).
See the WinterGard Application and Design Guide (H53585),
H900, or H908 installation instructions for design information.
For additional technical support call Tyco Thermal Controls at (800)
545-6258.
• Keep components and heating cable ends dry before
and during installation.
• The black heating cable core is conductive and can
short. It must be properly insulated and kept dry.
• Component approvals and performance are based on
the use of Tyco Thermal Controls-specified parts only.
Do not use substitute parts or vinyl electrical tape.
• Leave these instructions with end user for reference
and future use.
®
Splice and Tee Kit with End Seal
H910 Splice and Tee Kit is for use with WinterGard
®
• Needle nose pliers
• Heat gun or torch
E
G
F
H
A
B
C
D
E
I

Advertisement

loading

Summary of Contents for Raychem H910

  • Page 1: Installation Instructions

    Installation Instructions Description The WinterGard H910 Splice and Tee Kit is for use with WinterGard ® self-regulating heating cables to make splice, tee, and end seal con- nections. The kit contains materials for one splice and one end seal, or one tee connection and one end seal.
  • Page 2 H910 Installation Instructions Splice or Tee Connections The instructions are shown for a tee connection. Splice connections are done the same way, without the third heating cable section. Braid Inner jacket Core 12" • Allow 12" of extra heating cable as...
  • Page 3 H910 Installation Instructions • Score between bus wires at base jacket. • Bend core to break free at base jacket. • Peel core and any Repeat steps  through Do not cut remaining material 6 for other heating cable bus wires.
  • Page 4 H910 Installation Instructions • Twist the braid 1/4" pigtails together. • Slide uninsulated crimp over • Crimp the braid, using the • Cut off the extra braid. braid to within 1/4” of heating Ideal crimp tool. cable as shown. Black tape •...
  • Page 5 H910 Installation Instructions • Immediately after shrinking, pinch the end of the tube with needle- nose pliers until the end stays sealed; this normally takes 10 seconds. Ring of mastic and adhesive will appear CAUTION: To avoid burns allow heated sections to cool before touching.
  • Page 6 H910 Installation Instructions End Seal Installation Instructions for H612 and H622 Heating Cables Note: The end seal is designed to be installed only once. It cannot be removed from the heating cable once it is installed. Do not install it until instructed to do so in Step 3 •...
  • Page 7 — without notification to Buyer — to processing or materials that Fax: (650) 474-7711 do not affect compliance with any applicable specification. info@tycothermal.com www.tycothermal.com Tyco, Raychem and WinterGard are trademarks of Tyco Thermal Controls LLC or its affiliates.