The filter control system RM-216 C when connected to the mains poses an electrical hazard. Device
failure, serious or even fatal injuries may occur as a result of improper installation of the connected
equipment. Consequently, follow in particular the points set out below in addition to the general safety
regulations for equipment in industrial electrical installations:
-
Installation of the device may be carried out only by qualified experts, in accordance with the
provisions of IEC 364, DIN VDE 0105 for electrical equipment.
-
All applicable laws, conditions, orders and regulations governing the setting up of electrical equipment
must be observed with respect to the installation site.
-
Setting of equipment with degree of protection IP00 without covers, may only be performed by
authorized expert staff, when disconnected, and whilst observing the local safety and accident
prevention regulations.
The RM-216 C may only be operated in the permitted operating area.
Switch off the mains supply before replacing the filter control or any components connected to
it. Otherwise the equipment may be damaged.

2 Equipment specification

The RM-216 C is used to control 24 V DC solenoid valves on filtering separators with compressed air
pulse cleaning. After connecting the supply voltage, the filter control system functions fully automatically
without further activation. With ∆p mode switched on, the current differential pressure of the filter system
is displayed on the text display. The cleaning is carried out depending on the differential pressure. The
filter can be monitored via a ∆p alarm switch point (∆p alarm).
The full scale output for the measured differential pressure can be set by the parameter 15 "dP range".
The anlog output signal is automatically adjusted to the set full scale output.