Mounting The Device On A Din Rail - Siemens RUGGEDCOM RX1400 Installation Manual

Hide thumbs Also See for RUGGEDCOM RX1400:
Table of Contents

Advertisement

RUGGEDCOM RX1400
Installation Guide
• When installing the device in a closed or multi-device rack, be aware the operating ambient
temperature of the rack may be higher than the ambient temperature of the room. Make sure the
rack is installed in a suitable environment that can withstand the maximum ambient temperature
generated by the rack.
• Make sure each device in the rack is separated by at least one rack-unit of space, or 44 mm (1.75
in), to promote convectional airflow. Forced airflow is not required. However, any increase in airflow
will result in a reduction of ambient temperature and improve the long-term reliability of all equipment
mounted in the rack space.
• Do not exceed the maximum number of devices or weight restrictions specified by the rack
manufacturer.
• Do not overload the supply circuit. Refer to the over-current protection and power supply ratings
specified by the rack manufacturer.
• Make sure the rack and all devices have a proper ground-to-Earth connection. Pay particular
attention to power supply connections other than direct connections to the branch circuit (e.g. power
strips).
To secure the device to a standard 48 cm (19 in) rack, do the following:
1.
Make sure the rack mount adapters are installed.
Figure 2: Rack Mount Adapters
1. Rack Mount Adapter
2.
Insert the assembly into the rack.
3.
Secure the adapters to the rack using the supplied hardware.
Section 2.2.2

Mounting the Device on a DIN Rail

For DIN rail installations, the RX1400 can be equipped with panel/DIN rail adapters pre-installed on each side of
the chassis. The adapters allow the device to be slid onto a standard 35 mm (1.4 in) DIN rail.
To mount the device to a DIN rail, do the following:
1.
Align the adapters with the DIN rails and slide the device into place.
Mounting the Device on a DIN Rail
1
2. RX1400
2
1
Chapter 2
Installing the Device