VALEN X-CEL 6-12V INSTRUCTION AND OPERATIONS MANUAL TABLE OF CONTENTS SECTION CONTENT PAGE SECTION CONTENT PAGE GENERAL INFORMATION OPERATION Battery Characteristics Initial Charge Float Voltage SAFETY INFORMATION 6.2.1 Float Voltage Requirements General Information 6.2.2 Float Temp. Compensation Sulphuric Acid Maximum Charge Current...
Page 3
Compared to a flooded battery of equal capacity, a VALEN X-CEL Battery releases a gas volume of SECTION 2 - SAFETY INFORMATION 1% or less than the flooded battery. Due to this 2.1 General Information...
For example, the VALEN 4.1 General X-CEL is designed for a 10 year float service life at 20°C. If Do not store batteries outside, exposed to the elements. the battery were to be continuously operated at 28°C, the Store indoors in a cool, dry location.
5.4.1 Existing Racks in the string. If the batteries are installed in a cabinet, it When VALEN X-CEL Batteries are to be installed on should be designed to allow unobstructed air circulation existing racks, ensure the racks are: and prevent temperature build-up.
5.5.3 Connector Installation batteries becomes necessary. Batteries must be properly The VALEN X-CEL Batteries are supplied with hardware to paralleled in order to get the best system performance attach the copper interconnects or cables. Install the and longest battery life.
The initial or equalise charge voltage for the 6.2.1 Float Voltage Requirement VALEN X-CEL Batteries is 2.35V/cell at 20°C. Calculate the The recommended float voltage for the VALEN X-CEL initial charge voltage for your installation based on either Batteries is 2.25VPC at 20°C ±...
Since VALN would be needed. These conditions would include: X-CEL Batteries are of low maintenance design, there is Temperature variation in the string greater than 3°C no addition of water or specific gravity checks needed for low float voltage the life of the battery.
VALEN X-CEL 6-12V INSTRUCTION AND OPERATIONS MANUAL Keep the above records in a safe place for review by Measure the battery temperature in the middle of the maintenance personnel. Remember, these records are side (preferably) or the end wall of the container.
VALEN X-CEL 6-12V INSTRUCTION AND OPERATIONS MANUAL 9.3 Discharge Test Notes 1. VALEN X-CEL Batteries are shipped at 95% capacity. Full capacity will be achieved after a few cycles. 2. String voltage should be measured at the battery terminals, not at the load connections.
VALEN X-CEL 6-12V INSTRUCTION AND OPERATIONS MANUAL SECTION 10 – BATTERY REPORT VALEN X-CEL BATTERY REPORT Installed by: Representative: Operating Company: Date: Time: Battery Information Type of Battery: No. of Cells/String: String Float Voltage: Installation Date: No. of Strings/Battery: Battery Charge Current:...
Page 12
VALEN X-CEL 6-12V INSTRUCTION AND OPERATIONS MANUAL VALEN X-CEL BATTERY MAINTENANCE REGISTER Date Maintenance Description 1300 734 253 sales@regalelectro.com.au THANK YOU FOR MAKING IT A www.regalelectro.com.au...
Need help?
Do you have a question about the X-CEL and is the answer not in the manual?
Questions and answers