Intelli-Vent Specifications; Gas Pressure Requirements - A.O. Smith INTELLI-VENT Troubleshooting Manual

Table of Contents

Advertisement

INTELLI-VENT TROUBLESHOOTING GUIDE
INTELLI-VENT™ SPECIFICATIONS
INTELLI-VENT™ CONTROL SPECIFICATIONS
Body
Electrical Ratings
Max Inlet Gas Pressure
Temperature Range
High Temp Cut Off - ECO
OPERATING SEQUENCE
Pre-Purge Time
Ignitor Warm-up Time
Trial for Ignition Period
Inter-Purge Time
Post-Purge Time
Ignition Retries
Ignition Recycles

GAS PRESSURE REQUIREMENTS

NATURAL GAS
Supply gas
Manifold gas
PROPANE GAS
Supply gas
Manifold gas
†. Manifold gas pressure is non adjustable. Always verify correct main burner orifice
before replacing a control for failing to maintain correct manifold pressure.
Technical Training Department
½ inch NPT inlet.
½ inch inverted flare outlet. (RH thread natural, LH thread propane)
120 VAC, 60 Hz, 1Ø, 5-7 FLA.
Ignitor load: 2 amps maximum.
Blower/inducer motors: 3 amps full load - 4 amps locked rotor.
½ PSI maximum (14.0" W.C.)
70 - 160°F Residential.
120 - 180°F Commercial.
195°F Residential - single use (control must be replaced)
195°F Commercial - resettable (reset temp 120°F)
5 seconds.
20 seconds.
4 seconds.
5 seconds.
5 seconds.
2 retries; 3 trials before lockout.
2 recycles, 3 losses of flame before lockout.
4.5 to 5.0" W.C. minimum -14.0" W.C. maximum
Always check control/water heater label
3.5 to 4.0" W.C.
Always check control/water heater label
11.0" W.C. minimum 14.0" W.C. maximum
10.0" W.C.
5 of 24
Ashland City, Tennessee © 2005