INSTALLATION INSTRUCTIONS
REVISION: #0002 ECO# 1558
Note:
The details shown below illustrate standard countertop configurations. When projections beyond either
side of the wall exceed 6" additional support must be supplied beneath the countertop by others.
1 5/8"
SUPPORT ANGLES SUPPLIED
ONLY WHEN THIS DIMENSION
EXCEEDS 6"
NO CLIP ANGLES
SUPPLIED THIS SIDE
Before permanently installing the countertop into the opening it is advisable to check it for proper fit.
Unpack the countertop from the shipping crate and lay it on a clean flat surface. Be careful to properly
support countertops in the center when lifting to prevent cracking especially if they are long and narrow.
Measure the opening size and check this dimension against the drawings provided and the actual size of
1 1/2 HOUR FIRE RATED LAMINATED
COUNTERTOP INSTALLATION
4'-0" MAX.
4" STD.
PUBLIC SIDE
STANDARD UNIT CONFIGURATION
PUBLIC SIDE
FOR UNITS THAT EXTEND LESS
THAN 6" TO FLUSH WITH THE WALL
ON THE PUBLIC SIDE.
6" MIN.
SUPPORT ANGLES
ALWAYS SUPPLIED
THIS SIDE OF
COUNTERTOP
APPLY RTV FLAME
RETARDANT SILICONE
COIL SIDE
SEALANT TO THIS SURFACE
PRIOR TO INSTALLING
COUNTERTOP
4'-0" MAX.
6" MIN.
APPLY RTV FLAME
RETARDANT SILICONE
SEALANT TO THIS SURFACE
PRIOR TO INSTALLING
COUNTERTOP
COIL SIDE
ES 10-234
BY: JD
DATE: 10/23/2012

Advertisement

loading
Need help?

Need help?

Do you have a question about the ES 10-234 and is the answer not in the manual?

Questions and answers

Summary of Contents for Cornell ES 10-234

  • Page 1 INSTALLATION INSTRUCTIONS ES 10-234 1 1/2 HOUR FIRE RATED LAMINATED COUNTERTOP INSTALLATION REVISION: #0002 ECO# 1558 BY: JD DATE: 10/23/2012 Note: The details shown below illustrate standard countertop configurations. When projections beyond either side of the wall exceed 6” additional support must be supplied beneath the countertop by others.
  • Page 2 INSTALLATION INSTRUCTIONS ES 10-234 1 1/2 HOUR FIRE RATED LAMINATED COUNTERTOP INSTALLATION REVISION: #0002 ECO# 1558 BY: JD DATE: 10/23/2012 the countertop. The standard countertop is built to allow a 1/8” clearance dimension between the edges of the countertop at all points where it contacts the wall. The portion of the countertop projecting through the wall opening should be 1/4”...
  • Page 3 INSTALLATION INSTRUCTIONS ES 10-234 1 1/2 HOUR FIRE RATED LAMINATED COUNTERTOP INSTALLATION REVISION: #0002 ECO# 1558 BY: JD DATE: 10/23/2012 TWO-PIECE LAMINATED COUNTERTOP INSTALLATION Please read these instructions carefully before attempting countertop installation! 1. Lay countertop sections face side down, on the floor in front of the coil side of the opening. Use cardboard, foam or some other material to protect the face of the countertop from being scratched.
  • Page 4: Installation Instructions

    INSTALLATION INSTRUCTIONS ES 10-234 1 1/2 HOUR FIRE RATED LAMINATED COUNTERTOP INSTALLATION REVISION: #0002 ECO# 1558 BY: JD DATE: 10/23/2012...
  • Page 5 Cornell’s UL classified laminated countertop assemblies may be field over-laminated in order to provide a seamless surface between a Cornell UL classified countertop and non fire rated countertops that will be installed adjacent to these units. The classified countertop assembly provided by Cornell shall not be modified in any way other than preparation of the existing surfaces in the field that are required to be over-laminated.