Advertisement

5. About parameter
suppression relay)
The rush-current suppression relay usually operates under the conditions shown below, but if necessary, you can
add the ON/OFF status of the ST terminal (standby signal) of the inverter to the relay activation conditions, using
parameter
.
[
= 0 (default)]
The rush-current suppression relay operates with the time lag set with
the inverter has reached the specified voltage.
DC voltage
Rush-current
suppression relay
[
= 1 (interlocked with ST)]
The rush-current suppression relay operates along with the ST terminal with the time lag specified with
the voltage in the DC section of the inverter has reached the specified voltage.
DC voltage
ST terminal
Rush-current
suppression relay
(Mode of rush-current
ON
ON
ON
- 3E -
after the voltage in the DC section of
E6581228
after