Aerovent IM-200 Installation, Operation And Maintenance Instructions

Gas door air heater

Advertisement

General Installation, Operation and Maintenance Instructions For Aerovent Products

Installation

1. Install the door heater in position required.
Dimensions can vary to suit door opening. Heaters
can be mounted in horizontal, angular or vertical
position. Do not mount with control box upside
down or on the bottom. Weight of unit is approxi-
mately 375 lbs.
NOTE: Negative pressure in the building will have
an affect on unit's ability to maintain an air curtain
effect. This should be taken into account when locat-
ing the unit.
Typical Overhead Door
13'
13'
Angular Mounting Approx. 45°
Roll Top or Straight Lift Door
18" Min. Clearance
14'
Vertical Mounting Used With Roll Top Doors
2. Connect electrical power. If the unit does not have a
built-in disconnect switch, then an external discon-
nect should be provided by the installer. Be sure
power supply is the proper voltage. These units are
furnished for specified voltage.
Gas Door Air Heater
12'
45°
4'
5'
12'
3. Connect gas supply line using the regulator fur-
nished with the unit. Consult your gas company ser-
vice representative to determine the proper size for
the gas line. This varies according to the pressure
and length of the run. Required gas input can be
determined by the chart, Fig. 1.
Fig. 1
NATURAL. GAS
MODEL NO.
24S728
NDH*
3/4 HP
24S728
NDH*
2 HP
*PDH = Propane units
4. Mount operating station in a convenient location and
make connections to the terminal strip in the unit as
indicated in Fig. 2, or Fig. 3 for units supplied with
optional high-low fire feature.
Fig. 2. Operating Station
1
Lamp
2
R
Back of Lid
Connect H, 1, 2, and R to terminal
strip in unit control box.
Fig. 3. Operating Station with Optional Hi-Lo Fire
1
Lamp
2
Back of Lid
Connect H, 1, 2, R, 13 and 15 to
terminal strip in unit control box.
©1997 Aerovent
IM-200
June 1997
INPUT
NOMINAL
BTU
TEMP. RISE
325,000
73°F
440,000
99°F
580,000
131°F
440,000
66°F
580,000
85°F
680,000
102°F
790,000
118°F
870,000
130°F
990,000
148°F
H
1
2
R
1
H
Box
H
1
2
1
2
R
H
Box
GAS
PRESS.
1 oz.
2 oz.
3 oz.
2 oz.
3 oz.
4 oz.
5 oz.
6 oz.
7 oz.
13 15
R

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the IM-200 and is the answer not in the manual?

Questions and answers

Summary of Contents for Aerovent IM-200

  • Page 1 IM-200 June 1997 General Installation, Operation and Maintenance Instructions For Aerovent Products Gas Door Air Heater Installation 3. Connect gas supply line using the regulator fur- nished with the unit. Consult your gas company ser- 1. Install the door heater in position required.
  • Page 2 NO. 1 Door Switch Door in fully opened position with switch actuated Connect as shown when switch is held with door in open position. 49° Max. Door Track 15° Min. Free Position INSTALLATION NO. 2 Actuated Position IM-200...
  • Page 3: Troubleshooting

    (no carbon). If flame relay has power to it but flame cycle will not occur, reset For additional troubleshooting guidance, refer to flame relay (manual reset). If flames comes on RM7890A1015 bulletin. momentarily and goes out, check flame rod. There IM-200...
  • Page 4 Note: To avoid danger of over-firing, make certain that inlet pressure is at 1.0" w.c. above the outlet pressure. 3. Replace cover plate. A Twin City Fan Company 5959 Trenton Lane • Minneapolis, MN 55442-3238 Phone (612) 551-7500 • Fax (612) 551-7501 • www.aerovent.com...

Table of Contents