Distributed busbar protection REB500
Product version: 8.2
Station communication
Table 37.
Station communication protocols
IEC 61850-8-1
IEC 61850-8-1 supports
IEC 60870-5-103
IEC 60870-5-103 supports
Address setting of station address
Sub address setting, common address of
ADSU
Hardware IED
Table 38.
Degree of protection of rack-mounted IED
Description
Front side
Rear side, connection terminals
Table 39.
Table 16. Degree of protection of the LHMI
Description
Front side
Table 40.
Dimensions of the IED – 6U ½ 19" Bay Unit / 6U ¾ 19"Central Unit
Description
Width
Height
Depth
40
- Edition 1 and Edition 2 of the standard, configurable in HMI
- Time synchronization via SNTP: typical accuracy ± 1 ms
- Two independent time servers are supported. Server 2 is used as
backup time
- Optical connection
- Differential current of each protection zone
- Monitoring information from REB500 central unit and bay unit
- Binary events (signals, trips and diagnostic)
- Trip reset command
- Single connection point to REB500 central unit
- Disturbance recorder access for bay unit and central unit via MMS
file transfer protocol
- Export of ICD - file, based on Substation Configuration Language
SCL
- GOOSE reception for use as BFP start signals
- Time synchronization: typical accuracy ±5 ms
- Optical connection 9600 or 19200 Bd
- Subset of binary events as specified in IEC
Private range: Support of all binary events
Generic mode: Support of all binary events
- Trip reset command
- Disturbance recording data (bay unit only)
0...254
0...255 (CAA)
CAA per bay unit freely selectable
Value
IP 40
IP 20
Value
IP40
Value Bay Unit
220 mm (8.66 inches)
265.9 mm (19.47 inches), 6U
224 mm (8.82 inches)
1MRK 505 352-BEN
Issued: 2016-03-01
Revision: -
Value Central Unit
330 mm (13 inches)
265.9 mm (19.47 inches), 6U
224 mm (8.82 inches)
ABB