Product version: 8.2
Type Tests according to standards
Table 21.
Electromagnetic compatibility tests
Description
100 kHz and 1 MHz burst disturbance
test
Common mode
Differential mode
Electrostatic discharge test
Contact discharge
Air discharge
Radio frequency interference tests
Conducted, common mode
Radiated, amplitude-modulated
Fast transient disturbance tests
Communication ports
Other ports
Surge immunity test
Communication ports
Auxiliary power supply
Other ports
Power frequency (50 Hz) magnetic field
3 s
Continuous
Power frequency immunity test
Common mode
Differential mode
34
Type test value
2.5 kV
2.5 kV
8 kV
15 kV
10 V (emf), f=150 kHz...80 MHz
20 V/m (rms), f=80...1000 MHz and
f=1.4...2.7 GHz
4 kV
4 kV
2 kV line-to-earth
4 kV line-to-earth, 2 kV line-to-line
2 kV line-to-earth, 1 kV line-to-line
1000 A/m
100 A/m
300 V rms
150 V rms
1MRK 505 352-BEN
Issued: 2016-03-01
Revision: -
Reference
IEC 60255-26
IEC 61000-4-18, level 3
ANSI C37.90.1-2002
IEC 60255-26
IEC 61000-4-2, level 4
ANSI C37.90.3-2001
IEC 60255-26
IEC 61000-4-6 , level 3
IEC 60255-26
IEC 61000-4-3, level 3
ANSI C37.90.2-2004
IEC 60255-26
IEC 61000-4-4, level 4
ANSI C37.90.1-2002
IEC 60255-26
IEC 61000-4-5,
level 3
level 4/3
level 3/2
IEC 60255-22-5
IEC 61000-4-8, level 5
IEC 60255-26
IEC 61000-4-16