INSTALLATION AND MAINTENANCE INSTRUCTIONS
SPLIT
L8 SPLIT/L12 SPLIT, HM 8-12 SPLIT, EHZK 90 SPLIT/WWS 300 SPLIT/WWS 500 SPLIT

Advertisement

Table of Contents
loading

Summary of Contents for Alpha-InnoTec L8 SPLIT

  • Page 1 MOS GB 1539-3 331457 SPLIT INSTALLATION AND MAINTENANCE INSTRUCTIONS SPLIT L8 SPLIT/L12 SPLIT, HM 8-12 SPLIT, EHZK 90 SPLIT/WWS 300 SPLIT/WWS 500 SPLIT...
  • Page 2 EHZK 90 SPLIT WWS 300 SPLIT WWS 500 SPLIT HM 8-12 SPLIT...
  • Page 3 L8 SPLIT L12 SPLIT...
  • Page 5: Table Of Contents

    Connecting the supply Readjusting the default settings Miniature circuit-breaker Temperature limiter Comfort setting cooling Connection between HM 8-12 SPLIT and L8 SPLIT/L12 General SPLIT Cooling operated from the outdoor sensor in operating Connection between HM 8-12 SPLIT and EHZK 90 SPLIT,...
  • Page 6: N] Supply Temp

    Outdoor unit Menu types Temperature sensor Menu management Sensor placement Menu tree Data for sensor in L8 SPLIT/L12 SPLIT Main menus Data for sensor in HM 8-12 SPLIT 1.0 [N] Hot water temp. 2.0 [N] Supply temp. Dimensions 3.0 [N] Supply temp. 2 Indoor unit 4.0 [N] Outdoor temp.
  • Page 7: For Home Owners

    SPLIT is a system for heating, cooling and producing hot water for small houses. The system consists of an outdoor module (L8 SPLIT/L12 SPLIT), which utilises the energy in the outdoor air and sends it to the indoor module (HM 8-12 SPLIT), which takes care of the regulation and heat distribution in the house.
  • Page 8 For Home Owners General This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or mental capabil- ities or lack of experience and knowledge if they have been given supervision or instruc- tion concerning use of the appliance in a safe way and understand the hazards in- volved.
  • Page 9: Information About The Installation Product Information

    4. The refrigerant (now in liquid state) is routed back to L8 SPLIT/L12 SPLIT and the process is repeated. Climate system Klimatsystem By reversing the process, thereby allowing the refrigerant Överströmnings- in L8 SPLIT/L12 SPLIT to retrieve the heat from the water Overflow valve ventil RFV SPLIT/ RG10/ RBE SPLIT...
  • Page 10: Front Panel, Indoor Module

    For Home Owners Front panel, indoor module rätt Front panel, indoor module Additional heat symbol Hot water symbol I II III I II I II III I II I II If the electrical addition is connected The heat pump charges hot water. ”I”...
  • Page 11: How To Use The Front Panel

    For Home Owners Front panel, indoor module How to use the front panel All the most common settings are made from the panel as well as control computer instructions such as comfort etc. that you require the heat pump system to fulfil. In order for the installation to be used optimally, certain basic settings must have been made (see page 9).
  • Page 12: Comfort Setting Heating General

    For Home Owners Comfort setting heating Comfort setting heating HM 8-12 SPLIT selects operating mode automatic General ■ (cooling can also be selected now) with regard to The indoor temperature depends on several factors. the outdoor temperature. This means that the oper- Sunlight and heat emissions from people and household ating mode switches between "Heating", "Cooling"...
  • Page 13: Default Setting

    For Home Owners Comfort setting heating Default setting Setting with diagrams The diagram is based on the dimensioned outdoor tem- The basic heating is set using menu 2.1.2 and with the I II III I II perature in the area and the dimensioned supply temper- “Offset, heating curve”...
  • Page 14: Readjusting The Default Settings

    For Home Owners Comfort setting heating Readjusting the default settings If the required room temperature is not obtained, readjust- ment may be necessary. Cold weather conditions When the room temperature is too low, the “Heating ■ curve” value is increased in menu 2.1.2 by one increment. When the room temperature is too high, the “Heating ■...
  • Page 15: Comfort Setting Cooling General

    For Home Owners Comfort setting cooling Comfort setting cooling General Controlling cooling mode using the room The condition in order for cooling to be activated is that sensor "On" is selected in menu 9.3.3 Cooling system. If RFV SPLIT is present, the condition for cooling is that the NOTE room temperature has exceeded the set room temperature (menu 6.3) by the set value in menu 8.2.5 and that the...
  • Page 16: Comfort Setting Hot Water

    For Home Owners Comfort setting hot water Comfort setting hot water HEV 500 AMS10-8 The water heaters are coil models and are heated by circu- Domestic hot water volume, 40 °C (litre) Tappvarmvarmvattenvolym, 40 °C [l] lating water, which is heated by the heat pump. During “normal”...
  • Page 17 For Home Owners Comfort setting hot water NOTE ”Extra hot water” usually means that the electrical addition has been activated and therefore increases the electrical consumption. ”Extra hot water” can be activated in three different ways: 1. Periodic time based extra hot water Interval between increases is selected in menu 1.7.
  • Page 18: Maintenance

    For Home Owners Maintenance Maintenance HM 8-12 SPLIT and L8 SPLIT/L12 SPLIT require minimal VVS 300 SPLIT/VVS 500 SPLIT maintenance after commissioning. SPLIT contains many components and is why monitoring functions are integrated to help you. If something abnormal occurs, a message appears about malfunctions in the form of different ”alarm”...
  • Page 19: Emptying The Coil In The Water Heater

    During the cold months of the year, check to make sure that there isn't a build up of ice or frost under L8 SPLIT/L12 SPLIT. Strong wind combined with heavy snowfall can block the intake and exhaust air grilles.
  • Page 20: Dealing With Comfort Disruption

    For Home Owners Dealing with comfort disruption Dealing with comfort disruption Use the following list to find and remedy any heating or hot water problems. Symptom Cause Action Low hot water temperature or a lack of Circuit or main MCB tripped. Check and replace blown fuses.
  • Page 21: Operating Mode "Add. Heat Only

    For Home Owners Dealing with comfort disruption Operating mode "Add. heat only" In the event of malfunctions that cause a low indoor tem- perature, you can normally activate "Add. heat only" in HM 8-12 SPLIT, which means that heating only occurs with the immersion heater.
  • Page 22: Alarm Indications

    Check that the thermostats for the radiat- ors/under-floor systems are not closed. If cooling is in progress: Check that the air flow to L8 SPLIT/L12 SPLIT is not obstruc- ted. OU power failure / OU Com. error Outdoor unit not powered / Communica-...
  • Page 23: General Information For The Installer Transport And Storage

    General information for the installer Transport and storage EHZK 90 SPLIT, WWS 300 SPLIT, WWS 500 SPLIT Outdoor module L8 SPLIT/L12 SPLIT L8 SPLIT/L12 SPLIT should be transported and stored ver- tically. HUMMEL Patent If the heat pump is to be lifted using lifting straps without packaging, protect as illustrated.
  • Page 24: Assembly

    200 mm. L8 SPLIT/L12 SPLIT should Secure the wall bracket (enclosed) to a wall of a suitable ■...
  • Page 25: Manual Shunting

    HM 8-12 SPLIT, the water heater and L8 SPLIT/L12 SPLIT. See page 35. 4. Connect supply to HM 8-12 SPLIT. See page 33. 5. Follow the commissioning instructions on page 40.
  • Page 26: Pipe Installation General

    For the Installer Pipe installation Pipe installation General EHZK 90 SPLIT Pipe installation must be carried out in accordance with XL19 XL18 current norms and directives. HM 8-12 SPLIT can work at a temperature up to 65 C. For best savings, we recommend that the climate system be dimensioned for max 55 C.
  • Page 27: Pump Capacity Diagram

    For the Installer Pipe installation WWS 500 SPLIT Connecting HM 8-12 SPLIT to tank It is necessary to connect a water heater or a tank to HM 8-12 SPLIT. Pipe connections for the climate system are made at the bottom of HM 8-12 SPLIT. The tank EHZK 90 SPLIT, WWS 300 SPLIT, WWS 500 SPLIT ■...
  • Page 28: Connecting The Climate System

    INK KV-ANSL PROPPNING For the Installer Pipe installation BACKVENTIL WWS 500 SPLIT Connecting the hot water heater The water heater (WWS 300 SPLIT/WWS 500 SPLIT) must be supplied with the necessary set of valves. There must be a mixer valve if the temperature exceeds ■...
  • Page 29: Connection Of External Heat Source

    L8 SPLIT/L12 SPLIT and HM 8-12 SPLIT. Installation must be carried out in accordance with current norms and directives. L8 SPLIT/L12 SPLIT limitations Maximum pipe length, L8 SPLIT and L12 SPLIT (L): 30m. ■ Maximum height difference (H): ±7m. ■...
  • Page 30 Pipe connection Perform pipe installation with the service valves (QM35, ■ QM36) closed. ■ L8 SPLIT Remove the side panel on L8 SPLIT/L12 SPLIT during in- stallation to facilitate access. XL13 XL18 XL14 XL19 Ensure that water or dirt does not enter the pipes.
  • Page 31 Pipe installation Flare connections Pressure test and leak test Expansion: Both HM 8-12 SPLIT and L8 SPLIT/L12 SPLIT are pressure tested and leak tested at the factory, but the pipe connec- tions between the products must be checked after install- ation.
  • Page 32 For the Installer Pipe installation Insulating refrigerant pipes Insulate refrigerant pipes (both gas and liquid pipes) for ■ heat insulation and to prevent condensation. Use insulation that can withstand at least 120 °C. Poorly ■ insulated pipes can cause insulation related problems and unnecessary cable wear.
  • Page 33: Dockings

    Dockings General SPLIT can be connected in several different ways, some of which are shown on the following pages. Installation requirements L8 SPLIT L12 SPLIT Max pressure, climate system 0.25 MPa (2.5 Bar) Highest recommended supply/return temperature at dimensioned outdoor 55/45 °C...
  • Page 34 Erf. säker- safety devices hetsutr. HM 8-12 HBS 16 SPLIT BT 1 External additional Extern tillsats heat L8 SPLIT /L12 HEV 300/HEV 500 AMS 10-12 WWS 300 SPLIT/WWS 500 SPLIT SPLIT Klimatsystem Climate system Överströmnings- Overflow valve ventil RFV SPLIT/...
  • Page 35 For the Installer Pipe installation Climate system Radiator system Under floor heating systems Fan convector system Radiator Golvvärme Fläktkonvektor Extra Extra Extra Extra Extra Extra system system system system system system volume volume volume volym volym volym Överströmningsventil Överströmningsventil Överströmningsventil Overflow valve Overflow valve Overflow valve...
  • Page 36 For the Installer Pipe installation External additional heat Solar panels Wood boiler with accumulator Solfångare Vedpanna med ackumulator Solar panels Wood-fired Accumulator GP31 Accumulator boiler GP32 Extern styrning External control External control Extern styrning Gas boiler Oil/pellet boiler Exhaust air heat pump Gaspanna Olje-/pelletspanna Frånluftsvärmepump...
  • Page 37: Electrical Installation General

    Cables must be routed so that they are not damaged by ■ metal edges or trapped by panels. L8 SPLIT/L12 SPLIT is equipped with a single phase ■ compressor. This means that phase L3 is loaded with up to 15 A during compressor operation.
  • Page 38 Type Scale length of tion conductor (mm) FD1-BT30 UB1,2,3 Cable gland Terminal block, incoming mains supply Terminal block, L8 SPLIT/L12 X101 SPLIT Terminal block, communica- X100 tion, L8 SPLIT/L12 SPLIT Terminal block, external addi- tion Terminal block, external im- mersion heater and temperat-...
  • Page 39: Connecting The Supply

    (X1) in HM 8-12 SPLIT via cable gland (UB1). The NOTE cable must be dimensioned according to the applicable norms. L8 SPLIT/L12 SPLIT must be earthed before the wiring between the units is connected. HM 8-12 SPLIT can be connected with either 400 V 3NAC or 230 V 1AC.
  • Page 40: Wws 300 Split, Wws 500 Split

    For the Installer Electrical installation L12 SPLIT Connection between HM 8-12 SPLIT and EHZK 90 SPLIT, WWS 300 SPLIT, WWS 500 SPLIT The cable between the units must be connected between terminal block for outgoing electricity (X4) in HM 8-12 SPLIT and terminal block X100 in EHZK 90 SPLIT, WWS 300 SPLIT, WWS 500 SPLIT.
  • Page 41: Setting Max Power, Electrical Addition

    For the Installer Electrical installation Setting max power, electrical addition Connecting the outside sensor Setting the different maximum immersion heater outputs Install the outdoor temperature sensor (BT1) in the shade is performed using the knob (R25) on the load monitor on a wall facing north or north-west, so it is unaffected by board (AA22).
  • Page 42: Connection Of Centralised Load Control/Tariff

    When switch (SF1) is in the " 0" or “ ” position the relay X1:5 and X1:7. is in the alarm position. Tariff B, the compressor in L8 SPLIT/L12 SPLIT has to be Docking specific connection disconnected. Connect a potential-free contact function to terminal block X1:6 and X1:7.
  • Page 43 For the Installer Electrical installation External additional heat HM 8-12 SPLIT can control an external addition. Sensor BT19 must be moved to sensor output BT24 between the docking connections XL8 and XL9 on the tank (does not apply to solar power or wood fired docking). See section Component positions on page 78.
  • Page 44: Start-Up And Inspection Preparations

    Outdoor temperature NOTE Setting system flow cooling Do not start L8 SPLIT/L12 SPLIT at outdoor air temper- atures of -20 C or less. A temperature difference of dt=7 K is recommended in most cases. To achieve this, the following setting can be selected: 1.
  • Page 45: Checking External Addition With Internal Immersion Heater Blocked

    For the Installer Start-up and inspection Checking external addition with internal immer- Secondary adjustment sion heater blocked Air is initially released from the hot water and venting may be necessary. If gurgling sounds can be heard from HM 1. Select "Ext. 1 step" in menu 9.2.8. 8-12 SPLIT or from the climate system, the entire system 2.
  • Page 46: Checklist: Checks Before Commissioning

    Miscellaneous Start-up and inspection Checklist: Checks before commissioning Hot water Notes Checked Non-return valve Safety valve Mixing valve Shut off valves Heating Notes Checked System volume Expansion vessel Safety valve Internal addition External additional heat Cooling Notes Checked Pipe system, condensation insulation Reversing valve (QN12) cooling/heating Refrigerant system Notes...
  • Page 47: Miscellaneous Control

    Miscellaneous Control Control Display Changing parameters Changing a parameter (value): ■ Operating symbols Value of the current parameter Access the required menu. ■ Press the enter button, the numerical value starts to ■ flash. I II III I II Increase or decrease using the Plus/Minus buttons. ■...
  • Page 48: Menu Tree

    Miscellaneous Control Menu tree 1.0 [N] Hot water temp. 1.1 [N] Max HW/Period time 1.2 [N] Start temperature HW 1.3 [N] Stop temperature HW 1.4 [U] Stop temperature XHW 1.5 [U] Heat pump stop XHW 1.6 [U] Max heat p. time XHW 1.7 [U] Interval XHW 1.8 [U] Next XHW action 1.9 [U] HW run time...
  • Page 49 Miscellaneous Control 2.0 [N] Supply temp. 2.1.0 [N] Heating settings 2.1.1 [N] Offset heating/Total 2.1.2 [N] Heating curve 2.1.3.0 [U] Own heating curve 2.1.3.1 [U] Supply temp.at +20 2.1.3.2 [U] Supply temp.at -20 2.1.3.3 [U] Buckling temperature 2.1.3.4 [U] Supply t. at buckl. 2.1.3.5 [U] Return 2.1.4 [U] Min supply heating 2.1.5 [U] Circ-pump speed heat...
  • Page 50 Miscellaneous Control 3.0 [N] Supply temp. 2 4.0 [N] Outdoor temp. 3.1 [N] Offset heating/Tot 2 4.1 [N] Outdoor avg. temp. 3.2 [N] Heating curve 2 4.2 [U] Outdoor filter time 3.3 [U] Min supply temp. 2 4.3 [U] Outdoor avg. 1min. 3.4 [U] Max supply temp.
  • Page 51 Miscellaneous Control 5.0 [N] Heat pump 6.0 [N] Room temperature* 5.1 [N] Number of starts 6.1 [U] Room compensation 5.2 [N] Run time compressor 6.2 [U] Heating system 5.3 [U] Time to start 6.3 [N] Room temp. setpoint 5.4 [U] Outdoor temp. Tho-A 6.4 [U] Room temp avg.
  • Page 52 Miscellaneous Control 7.0 [N] Clock 8.0 [N] Other adjustments 7.1 [N] Date 8.1.0 [N] Display settings 8.1.1 [N] Menu type 7.2 [N] Time 8.1.2 [N] Language 7.3.0 [U] Temp set back 7.3.1 [U] Set back time 8.1.3 [N] Display contrast 7.3.2 [U] Set back temp +/- 8.1.4 [N] Light intensity 7.3.3 [U] Heating system...
  • Page 53 Miscellaneous Control 9.0 [S] Service menus 9.1.0 [S] Heat pump settings 9.1.1 [S] DM start heating 9.1.2 [S] DM start cooling 9.1.3 [S] Stop temp. heat low 9.1.4 [S] Stop temp. heat high 9.1.5 [S] Stop temp. cool low 9.1.6 [S] Stop temp. cool high 9.1.7 [S] Time bet.
  • Page 54 Miscellaneous Control 9.0 [S] Service menus 9.3.10.2 [S] Period time 1 9.3.10.3 [S] Temp. period 1 9.3.10.4 [S] Period time 2 9.3.10.5 [S] Temp. period 2 9.3.10.6 [S] Return 9.3.11 [S] Supply pump exer. 9.3.12 [S] Supply diff HP 9.3.13 [S] Diff HP add. heat 9.3.14 [S] Block HW/Heating 9.3.15 [S] Heat drop at alarm 9.3.16 [S] Type of HW sensor...
  • Page 55 Miscellaneous Control 9.0 [S] Service menus 9.8.x.8 [S] Outdoor temp Tho-A 9.8.x.9 [S] Supply/Return temp 9.8.x.10 [S] Condensor out 9.8.x.11 [S] Hot water temp. 9.8.x.12 [S] CompFreq act/set 9.8.x.13 [S] Heat Ex Tho-R1 9.8.x.14 [S] Heat Ex Tho-R2 9.8.x.15 [S] Suction temp. Tho-S 9.8.x.16 [S] Hot gas Tho-D 9.8.x.17 [S] Liquid line temp.
  • Page 56: Main Menus

    Miscellaneous Control Main menus Menu 9.0 [S] Service menus This menu and its sub-menus are only shown on the display Menu 1.0 [N] Hot water temp. screen when access has been selected in menu 8.1.1. The current hot water temperature in the hot water Values can be read and various settings can be made from heater is shown here.
  • Page 57: 1.0 [N] Hot Water Temp

    The desired temperature during extra hot water is set here. These setting initially apply when "On" is selected in menu Setting range: 40 – 65 °C 1.11.2. Factory setting: 65 °C L8 SPLIT L12 SPLIT Menu 1.5 [U] Heat pump stop XHW Setting range 20 – 81 Hz 25 –...
  • Page 58 Miscellaneous Control Menu 2.1.1 [N] Offset heating/Total Menu 2.1.4 [U] Min supply heating The selected heating curve offset is shown here. The set minimum level for the supply temperature to the climate system is shown here. The total offset of the heat curve is also shown here. It in- cludes schedule, outer compensation and any room con- The calculated flow temperature never drops below the trol.
  • Page 59: N] Supply Temp. 2

    Miscellaneous Control Menu 2.2.4 [N] Min supply cooling 3.0 [N] Supply temp. 2 The set minimum level for the supply temperature to the Menu 3.1 [N] Offset heating/Tot 2 climate system during cooling is shown here. The selected heating curve offset 2 is selected here. The calculated flow temperature never drops below the The total offset of heat curve 2 is also shown here.
  • Page 60: N] Outdoor Temp

    Menu 3.6.1 [U] Supply temp.at +20 Menu 5.3 [U] Time to start The supply temperature at an outdoor air temperature of Time until the compressor start in the L8 SPLIT/L12 SPLIT +20 °C is selected here. is shown in this menu.
  • Page 61: 6.0 [N] Room Temperature

    Menu 7.3.2 [U] Set back temp +/- Shows the total number of incorrect communications with Changes to the heat curve with a day change, e.g. the L8 SPLIT/L12 SPLIT since start-up. night reduction is set here. Setting range: -10 – 10 Menu 5.15.3 [S] Reset com.
  • Page 62: 8.0 [N] Other Adjustments

    Miscellaneous Control Menu 7.5.3 [U] Heating system Menu 8.1.1 [N] Menu type The climate system that the vacation set back is to affect The menu type is chosen here. is selected here. If shunt group 2 is present the menu can Normal, covers the normal user's needs.
  • Page 63: 9.0 [S] Service Menus

    9.0 [S] Service menus Setting range: 1.0 – 10.0 Menu 9.1.0 [S] Heat pump settings Default value: 1.0 Settings for L8 SPLIT/L12 SPLIT are made in the sub-menus Menu 8.2.6 [N] Return to this menu. Return to menu 8.2.0. Menu 9.1.1 [S] DM start heating Menu 8.3.0 [U] Current limiter...
  • Page 64 Menu 9.1.10 [S] OU current heat act/max Select the type of addition to be used. The phase current to L8 SPLIT/L12 SPLIT and the highest permitted current that can be set during heating are Setting range: Internal power 1, Ext. 1 step, Ext. Lin 3, shown here.
  • Page 65 Miscellaneous Control Menu 9.3.3 [S] Cooling system Menu 9.3.8 [S] Factory setting Select "On" if cooling system is installed (accessory re- Here you can select to restore factory settings in HM 8-12 quired). SPLIT. Setting range: Off, On When returning to the factory settings the language switches to English.
  • Page 66 Miscellaneous Control Menu 9.3.10.6 [S] Return Menu 9.3.16 [S] Type of HW sensor Return to menu 9.3.10.0. Here you can select whether to use hot water sensors that manage higher temperatures (above90 °C) or not. Menu 9.3.11 [S] Supply pump exer. Standard: Standard setting Pump operation can be deactivated here.
  • Page 67 Menu 9.5.14 [S] Run status regulator is way off the set point. Max difference between Shows the current operating status of L8 SPLIT/L12 SPLIT flow line front and calculated flow line. The display can show: Off, Hot water, Heating, Cooling, Setting range: 2.0 –...
  • Page 68: Alarm List

    Miscellaneous Control Menu 9.8.x.1 [S] Time Menu 9.8.x.3 [S] Run status Menu 9.8.x.2 [S] Alarm type Menu 9.8.x.4 [S] Run status last See section Alarm list on page 65 for further alarm inform- Menu 9.8.x.5 [S] Run status time ation. Menu 9.8.x.6 [S] Run time compressor Alarm num- Cause...
  • Page 69: Alarm List Acknowledging Alarms

    - High temperature in the tank - Tripped circuit fuse (L2 HM 8-12 SPLIT alarm The following alarms block L8 SPLIT/L12 SPLIT. Addition runs at min permitted supply temperature. Alarm Alarm text on the dis- Description May be due to...
  • Page 70: L8 Split/L12 Split Alarm

    - Open-circuit or short-circuit on sensor input - Sensor does not work (see "Temperature sensor" section) L8 SPLIT/L12 SPLIT alarm The following alarms block L8 SPLIT/L12 SPLIT. Addition runs at min permitted supply temperature. Alarm Alarm text on the dis- Description...
  • Page 71 - Sensor does not work (see "Temperature sensor" section) - Defective control board in L8 SPLIT/L12 SPLIT Sensor fault Tho-D Sensor fault, hot gas in L8 SPLIT/L12 SPLIT (Tho- - Open-circuit or short-circuit on sensor input - Sensor does not work (see "Temperature sensor" section)
  • Page 72: Hot Water Alarm

    SPLIT/L12 SPLIT - Defective control board in L8 SPLIT/L12 SPLIT - Compressor fault Hot water alarm The following alarms block hot water production via L8 SPLIT/L12 SPLIT. The addition is blocked completely. Alarm Alarm text on the dis- Description May be due to play High HW temp.
  • Page 73: Outdoor Sensor Alarm

    Miscellaneous Alarm list Alarm Alarm text on the dis- Description May be due to play Sensor fault VBF2 Sensor fault, supply, system 2. - Open-circuit or short-circuit on sensor input - Sensor does not work (see "Temperature sensor" section) Outdoor sensor alarm The following alarms set so that the system runs at minimum permitted supply temperature.
  • Page 74: Electrical Circuit Diagram Hm 8-12 Split

    Miscellaneous Electrical circuit diagram Electrical circuit diagram HM 8-12 SPLIT SPLIT...
  • Page 75 Miscellaneous Electrical circuit diagram SPLIT...
  • Page 76 Miscellaneous Electrical circuit diagram SPLIT...
  • Page 77 Miscellaneous Electrical circuit diagram SPLIT...
  • Page 78 Miscellaneous Electrical circuit diagram SPLIT...
  • Page 79 Miscellaneous Electrical circuit diagram SPLIT...
  • Page 80: L8 Split

    Miscellaneous Electrical circuit diagram L8 SPLIT POWER SOURCE 230V 50Hz TO INDOOR UNIT F(20A) T2 T1 Y/GN F6 (5A) FM01 (4A) CNO2 (WH) 6 5 4 3 2 1 4 3 2 1 7 6 5 4 1 CNO1 CNW2...
  • Page 81 Fan motor Intelligent power module L/L1 Induction coil LED1 Indicator lamp (green for L8 SPLIT, red for L12 SPLIT) LED2 Indicator lamp (red for L8 SPLIT, green for L12 SPLIT) Low pressure transmitter Expansion valve for cooling Expansion valve for heating...
  • Page 82: Component Positions

    Miscellaneous Component positions Component positions HM 8-12 SPLIT Component image BT12 AA23 FD1-QA41 AA22-X1 AA22-R26 AA22-R25 AA22-R24 AA22 AA21 AA22-X4 BT15 QN11 QM40 QM31 QM30 XL14 QM20 XL13 XL18 XL19 SPLIT...
  • Page 83 Miscellaneous Component positions Component list Sensor, thermostats Pressure sensor, high pressure Pipe connections Temperature sensor, outdoor Climate system supply Temperature sensor, heating medium, flow Climate system return Temperature sensor, heating medium, return XL13 Liquid line refrigerant BT12 Temperature sensor, condenser, supply XL14 Gas line refrigerant BT15...
  • Page 84: Ehzk 90 Split, Wws 300 Split, Wws 500 Split

    Miscellaneous Component positions EHZK 90 SPLIT, WWS 300 SPLIT, WWS 500 SPLIT Component image QM20 BT19 XL18 FD1-BT30 X100 BT19 X101 X101 X100 BT24 BT24 XL19 WWS 500 SPLIT XL18 X101 XL18 XL19 XL19 BT19 WWS 300 SPLIT X100 FD1-BT30 EHZK 90 SPLIT SPLIT...
  • Page 85 Miscellaneous Component positions List of components Pipe connections Connection, Cold water Connection, Hot water Connection, Docking, in heating medium Connection, Docking, out heating medium XL18 Connection, Circulation XL19 Connection, Circulation Valves etc. Safety valve, heating medium Drain valve, heating medium QM20 Venting valve Electrical components...
  • Page 86: Outdoor Unit

    Miscellaneous Component positions Outdoor unit Component image, L8 SPLIT PWB1 PWB2 PWB3 63H1 FM01 EEV-H EEV-C QM35 QM36 Component image, L12 SPLIT PWB3 PWB1 PWB2 63H1 FM01 EEV-C QM35 QM36 EEV-H SPLIT...
  • Page 87 Miscellaneous Component positions List of components 63H1 High pressure pressostat Low pressure transmitter FM01 4-way valve Compressor PWB1 Control board PWB2 Inverter board PWB3 Filter board QM35 Service valve, liquid side QM36 Service valve, gas side EEV-H Expansion valve, heating EEV-C Expansion valve, cooling Terminal block, incoming supply and communication...
  • Page 88: Temperature Sensor Sensor Placement

    Temperature sensor, hot gas Tho-R1 Temperature sensor, heat exchanger out Sensors Tho-R2 Temperature sensor, heat exchanger, in Remote EB1 Tho-S Temperature sensor, suction gas Tho-A Data for sensor in L8 SPLIT/L12 SPLIT Tho-S Tho-D Tho-D BT19 Tho- (kΩ) BT30 Tho-R2 EHZK 90 SPLIT...
  • Page 89: Data For Sensor In Hm 8-12 Split

    Miscellaneous Temperature sensor Data for sensor in HM 8-12 SPLIT Temperature (°C) Resistance (k ) Voltage (V) 102.35 4.78 73.51 4.70 53.44 4.60 39.29 4.47 29.20 4.31 21.93 4.12 16.62 3.90 12.71 3.65 9.81 3.38 7.62 3.09 5.97 2.80 4.71 2.50 3.75 2.22...
  • Page 90: Indoor Unit

    Miscellaneous Dimensions Dimensions Indoor unit Under Right Front SPLIT...
  • Page 91 Miscellaneous Dimensions Hot water tank EHZK 90 SPLIT Right Front Above SPLIT...
  • Page 92 Miscellaneous Dimensions Water heater WWS 300 SPLIT 505050 Under Front Left Adjustable Above SPLIT...
  • Page 93 Miscellaneous Dimensions Water heater WWS 500 SPLIT Left Ø670 Front Ø760 Above SPLIT...
  • Page 94: Outdoor Unit

    Miscellaneous Dimensions Outdoor unit L8 SPLIT Anslutningsplint Terminal block Öppning för rör Opening for pipe and och kablage wiring Vätskeledning Liquid pipe Gasledning Gas pipe Front 188.5 Right Dräneringshål Drainage hole (Ø20 x 3) Above SPLIT...
  • Page 95 Miscellaneous Dimensions L12 SPLIT Opening for pipe and wiring Opening for pipe and wiring Drainage hole Drain hole ( Ø20 x 3) Under Liquid pipe Liquid pipe Gas pipe Gas pipe Cable gland Cable gland Cable gland Cable gland Left Opening for pipe and Opening for pipe and wiring...
  • Page 96: Technical Specifications

    0.61 l/s Circulation pump, flow at 20 kPa external pressure drop 0.49 l/s Min/max system flow, heating operation L8 SPLIT: 0.12 /0.38 l/s L12 SPLIT: 0.15 /0.57 l/s Min/max system flow, cooling operation L8 SPLIT: 0.15 /0.38 l/s L12 SPLIT: 0.20 /0.57 l/s Min flow, climate system, at 100% circulation pump speed (defrost flow) L8 SPLIT: 0.19 l/s...
  • Page 97: Technical Specifications

    Miscellaneous Technical specifications Outdoor module L8 SPLIT L12 SPLIT Compressor Twin Rotary Speed, heating 20–81 Hz (rps) 25–85 Hz (rps) Speed, cooling 20–86 Hz (rps) 20–80 Hz (rps) Max fan flow (heating, nominal) 3000 m 4380 m Fan rating 86 W...
  • Page 98: Performance, Hm 8-12 Split And L8 Split

    Electrical connections 230 V 1AC 50 Hz or 400 V 3NAC 50 Hz Part no. 150 796 01 150 805 01 150 806 01 Performance, HM 8-12 SPLIT and L8 SPLIT Heating Outd. temp: / Supply Nominal temp. 7/35 °C (floor) 1.75/0.50/3.50...
  • Page 99: Sound Pressure Levels

    Miscellaneous Technical specifications Sound pressure levels L8 SPLIT/L12 SPLIT is usually placed next to a house wall, which gives a directed sound distribution that should be considered. Accordingly, you should always attempt to find a placement on the side that faces the least sound sensitive neighbouring area.
  • Page 100: Standard Test, En14511

    8. Set the circulation pump speed in menu 2.1.5 to obtain limit position. 10 kPa external available pressure. 5. Set the current degree minute value in menu 2.6 to -200. Standard test, L8 SPLIT Air temperature (°C) Flow temperature (°C) Heat capacity (kW) Output in (kW) 4.66...
  • Page 101: Energy Labelling

    Miscellaneous Energy labelling Energy labelling Information sheet Supplier Alpha-InnoTec Model L8 SPLIT L12 SPLIT Model hot water heater HM 8-12 SPLIT + WWS 300 SPLIT HM 8-12 SPLIT + WWS 300 SPLIT Temperature application °C 35 / 55 35 / 55...
  • Page 102: Technical Documentation

    Miscellaneous Energy labelling Technical documentation Model L8 SPLIT Model hot water heater HM 8-12 SPLIT + WWS 300 SPLIT Type of heat pump Air-water Exhaust-water Brine-water Water-water Low-temperature heat pump Integrated immersion heater for additional heat Heat pump combination heater...
  • Page 103 Miscellaneous Energy labelling Model L12 SPLIT Model hot water heater HM 8-12 SPLIT + WWS 300 SPLIT Type of heat pump Air-water Exhaust-water Brine-water Water-water Low-temperature heat pump Integrated immersion heater for additional heat Heat pump combination heater Climate Average Cold Warm Temperature application...
  • Page 104: Accessories

    Part no. 150 791 01 WTPSK 100 SPLIT Heating/cooling Part no. 150 792 01 BKS SPLIT KWS 2 For L8 SPLIT/L12 SPLIT Condensation water pipe, dif- ferent lengths. Part no. 150 788 01 KWS 2/1 SPLIT, 1 m Part no. 150 812 01 KWS 2/3 SPLIT, 3 m Part no.
  • Page 105: Safety Precautions Caution

    Miscellaneous Safety precautions Safety precautions Caution Switch off the compressor before disconnecting the pipe from the pump. The installation must be carried out by a qualified installer. If the pipe is disconnected whilst the compressor is running and the If you install the system yourself, serious problems may occur, for ex- service valve is open, air is mixed into the process circuit.
  • Page 106: Especially For Units Intended For R410A

    Miscellaneous Safety precautions - Locations where substances that can affect the air conditioning unit, If the unit weights more than 20 kg, it must be carried by two people. for example, sulphide gas, chlorine, acid or alkaline substances can Do not carry by the plastic strap, always use the carry handle when occur.
  • Page 107: Index

    Item register Item register Accessories, 100 Readjustment, 41 Alarm, 18 Refrigerant pipe, 25 Alarm list, 65 Alarm outputs, 38 Safety precautions, 101 Assembly, 20 Serial number, 3 Sound pressure levels, 95 Centralised load, 38 Supplied components, 19 Checklist, 42 System flow, 40 Commissioning, 40 Component locations, 78 Tariff control, 38...
  • Page 108: Ec Declaration Of Conformity

    EC Declaration of Conformity in accordance with the EC Low Voltage Directive 2006/95/EC, Annex III The undersigned confirms that the following designated device(s) as designed and marketed by us fulfill the standardized EC directives, the EC safety standards and the product-specific EC standards. In the event of modification of the device(s) without our approval, this declaration shall become invalid.
  • Page 112 WS name: -Gemensamt WS version: a80 (working edition) Publish date: 2015-09-10 12:34 331457 For technical support, please contact your authorised installer or the manufacturer's local service partner. Contact details for your local service partner can be found at www.alpha-innotec.com. ait-deutschland GmbH Industriestrasse 3 D-95359 Kasendorf E-mail: info@alpha-innotec.com...