sinercom PANTHER 1KR User Manual

Panther series high frequency online ups 1kva – 10kva 1 phase in - 1 phase out

Advertisement

Quick Links

PANTHER SERIES
HIGH FREQUENCY
1kVA – 10kVA
1 Phase In - 1 Phase Out
 
 
 
Headquarter: Via G. Cappalonga 9/A‐ 00043 Ciampino (Rm) (Italy) 
Factory: Via Cascina Secchi 247/4b ‐ 24040 Isso (BG) 
ONLINE UPS
Sinercom srl 
tel. +39.06.79800323 fax +39.06.79814644   
tel. +39.0363.938231 fax +39.0363.998235 

USER MANUAL

 

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the PANTHER 1KR and is the answer not in the manual?

Questions and answers

Summary of Contents for sinercom PANTHER 1KR

  • Page 1: User Manual

      PANTHER SERIES HIGH FREQUENCY ONLINE UPS 1kVA – 10kVA 1 Phase In - 1 Phase Out       Sinercom srl  Headquarter: Via G. Cappalonga 9/A‐ 00043 Ciampino (Rm) (Italy)  tel. +39.06.79800323 fax +39.06.79814644    Factory: Via Cascina Secchi 247/4b ‐ 24040 Isso (BG)  tel. +39.0363.938231 fax +39.0363.998235  USER MANUAL...
  • Page 2       Thank you for purchasing product. Observe the warnings on the machine and manual strictly and properly keep the manual. Do not operate the UPS before read safety notes and operation instructions.  ...
  • Page 3: Table Of Contents

          TABLE CONTENTS 1、  Introduction........................2  1.1 Description of Commonly Used Symbols................2  1.2 Safety Instructions.......................2  2、  Product Description......................4  2.1 System Type and Configuration..................4  2.2The Appearance of the UPS....................5  2.3 Operating Principle ......................8  3、  Installation........................10  3.1 Unpacking Inspection .......................10  3.2 Installation Notes ......................10  3.3 Cable Connection......................11 ...
  • Page 4: Introduction

          1、 Introduction 1.1 Description of Commonly Used Symbols Some or all of the following symbols may be used in this manual and may appear in your application process. Therefore, all users should read the form carefully and thoroughly. Symbol &...
  • Page 5       6. Do not open or mutilate the battery or batteries, released electrolyte is highly poisonous and harmful to the skin and eyes. 7. Do not short the positive and negative of battery electrode. Otherwise, it may cause electric shock or fire.
  • Page 6: Product Description

    1kVA --1 0kVA UPS. Table 2-1 UPS types and configurations Type Model Remark 1kVA PANTHER 1KR With a 1A internal charger and 3 batteries 2kVA PANTHER 2KR With a 1A internal charger and 6 batteries Standard...
  • Page 7: The Appearance Of The Ups

            2.2The Appearance of the UPS   (1) Front view     Figure 2-1 PANTHER 2U     Figure 2-2 PANTHER 3U (2) Rear view     Figure 2-3 The rear panel of PANTHER 1KR(XL) 5   ...
  • Page 8         Figure 2-4 The rear panel of PANTHER 2KR     Figure 2-4 The rear panel of PANTHER 2KR-XL   Figure 2-6 The rear panel of PANTHER 3KR   Figure 2-5 The rear panel of PANTHER 3KR-XL  ...
  • Page 9         Figure 2-7 The rear panel of PANTHER 6KR   Figure 2-8 The rear panel of HP9115CRT 10K 7   ...
  • Page 10: Operating Principle

          Figure 2-9 The front external view 2.3 Operating Principle  1-3kVA  Figure 2-10 The UPS operating principle 8   ...
  • Page 11 LED indicators will indicate the fault type, and the fault information will be reported through the communication ports. 6. Charger: Standard model: 1A charging current for PANTHER 1KR ~3KR; charging curre nt 2A for PANTHER 6KR~10KR; Long backup model: 7A charging current for PANTHER 1KR-XL ;...
  • Page 12: Installation

          3、 Installation 3.1 Unpacking Inspection 1. Open the packing box of UPS and take it out, visually examine the unit for transit damage. 2. Check against the accessory lists that the accessories of the UPS are present. (Refer to Table 3-1).
  • Page 13: Cable Connection

    If the UPS is connected via the power cable, please use a proper socket with protection against electric current, and pay attention to the capacity of the socket: over 10A for PANTHER 1KR( XL)~2KR(X,L)over 16A for PANTHER PANTHER 3KR(XL) over 32A for PANTHER 6KR( XL) and over 50A for PANTHER 10KR(XL), The wiring configuration is shown in the following diagram.
  • Page 14       Figure 3-2 Connection method of output for PANTHER 1KR(XL)~3KR(XL)  Apart from using the socket for output, PANTHER 3KR(XL) has the terminal block available for output as well when the output current over 10A recommended. The wring configuration is shown in the following diagram.
  • Page 15        The input and output of PANTHER 6KR(XL)/PANTHER 10KR(XL) all available to use terminal block, The wiring configuration is shown in the following diagram. 1) Remove the cover of the terminal block; ² 2) PANTHER 6KR(XL)use AWG10 (5.3mm ) wires for wiring configuration;...
  • Page 16: Operation Procedure Of External Battery For Long Backup Time Ups

    Therefore, the following steps must be strictly complied with. 1. First connect in series the batteries of the pack to ensure proper battery voltage that PANTHER 1KR-XL for 36VDC,PANTHER 2KR-XLf or 72VDC , PANTHER 3KR-XL for 96VDC; PANTHER 6KR-XL/10KR-XL for 192VDC.
  • Page 17: Connecting Communication Cable

          3.3.3 Connecting Communication Cable 1. Computer interface      computer interface: The type of signals, serial command (RS232), is provided by the UPS to communicate with a host computer. User can use WinPower software to monitor the UPS through the port. 2.
  • Page 18 AS400 and SNMP and CMC cards. If you have any question about the above communication ports, please contact customer service center. 3. Surge-protection connection--only for PANTHER 1KR(XL)~3KR(XL) a — Output: Connects the equipment to be protected. b — Input: Connects the telephone line or network.
  • Page 19       corresponding stitches and shield, as the UPS parallel cable. The length of the parallel cable is appropriate to be less than 3m. 2) Strictly follow the stand-alone wiring requirements to perform the input wiring of each UPS 3)Connect the output wires of each UPS to an output breaker panel 4)Each UPS need a independent battery pack 5)Please refer to the wiring diagram in the next page, and opt suitable breaker.
  • Page 20             18   ...
  • Page 21        Operation and maintenance  1)To perform the general operation, follow the stand-alone operating requirement. 2)Startup: The units transfer to INV mode simultaneously as the y start up sequentially in Line mode. 3) Shutdown: the units shut down sequentially in INV mode. When the last one completes the shutdown action, e ach unit will shut down the inverter simultaneously an d transfer to Bypass mode.
  • Page 22: Operation

          4、 Operation 4.1 Introduction of Display Panel   1. ON/OFF button: The ON/OFF button provides the following functions: 1) Turn on UPS system: By pressing the ON/OFF button more than 1 second, the UPS system is turned on. 2) Turn off UPS system: By pressing this button more than 1 second turns off the UPS system whenever the UPS run under the normal mode/battery mode.
  • Page 23       Display Information or data LED indicator When the fault occurs, this light bright City light Inverter lamp When the machine in the inverter status, this light bright Trouble light When the fault occurs, this light bright Input information Display input voltage Display voltage range 0-999 VAC Display input voltage...
  • Page 24: Operation Mode

          Load information Display load power WATT or VA value of the ratio Battery status information Display the battery voltage capacity of the ratio Fault/warning Display buzzer, warning, mains, batteries, charging state identification Output voltage, frequency and bypass choose information Choose UPS output voltage, choose 200VAC anyone 208VAC,220VAC,230VAC under No output mode or bypass mode.
  • Page 25       1. Mains mode LCD are shown in the following figure: 2. If output overloaded, the load level indicators will be turned on and alarm will beep twice every second. You should get rid of some unnecessary loads one by one to decrease the loads connected to the UPS less than 100% capacity of the UPS.
  • Page 26: Bypass Mode

          4.2.2 Bypass mode 1. When the ups is running in battery mode, the alarm will beep every 4 seconds. If the/ “Function” button is pressed for more than 2 seconds the alarm will not beep(silence function).Press the Function! button more than 2 seconds again to resume the alarm function.
  • Page 27: Battery Mode

          4.2.3 Battery mode When operating in bypass mode set up through WinPower software, the display on the front panel is show in the following diagram. The utility power indicator and the bypass indicator are turn on. The load/battery capacity indicator will be turned on in accordance with the load capacity connected.
  • Page 28       1. Turning on the UPS The operation of turning on the UPS contains: turning on with utility power and turning on without utility power. 1) Turning on with utility power: Connect the mains input to the UPS, press and hold the ON/OFF button for 1 second until the buzzer beeps.
  • Page 29: Conducting Battery Self-Diagnosis

          2) Completely power down the UPS from Battery mode Press the ON/OFF! button persistently for more than 1 second to power off the UPS. When being powered off, the UPS will start self-diagnosis and all the load/battery capacity indicators will be turn on and off one after another.
  • Page 30: Error Code And Warning Code

          4.3.3 Error code and Warning code --for PANTHER 1KR(XL)~3KR(XL) Error code  Description  Warming code  Description  1  Communication error  11  EPO state  2  Short circuit  12  Battery overvoltage  3  Over load  13  Fan alarm  4  Thermal  14  Charging error  5  UPS voltage  15  Overload  6  Inverter fault     ...
  • Page 31: Maintenance

            5. Maintenance 5.1 Battery Maintenance The battery is key component of the UPS. The battery life depends on the ambient temperature, charge and discharge times. High ambient temperature and deep discharge will shorten the battery life. 1.
  • Page 32: Checking Ups Function

          5.2 Checking UPS function Every time when conducting field maintenance, please check the regular function of the UPS, including: 1. Check the operation status of the UPS If the main voltage is within the specifications, the UPS should operate in normal mode; if the main voltage is abnormal, the UPS should operate in battery mode.
  • Page 33: Troubleshooting

    6、Troubleshooting In the event of an UPS fault, shoot the trouble according to Table 6-1. If the fault still persists, please contact the customer service center. Table 6-1 UPS troubleshooting    PANTHER 1KR(XL)~3KR(XL)   Problem Possible cause solution Ensure that the UPS is not overloaded and the ventilation opening is not blocked and ambient temperature is not too high.
  • Page 34        PANTHER 6KR(XL)~10KR(XL)   Problem Possible cause Solution Make sure the UPS is not overloaded; the air vents are not blocked and the ambient The Fault code is “08”, The UPS transfers to fault temperature is not too high. Wait for 10 and the buzzer beeps mode due to internal minutes for the UPS to cool down before...
  • Page 35: Specifications

          7、Specifications 7.1Electrical 2KR- 3KR- 10KR Model (PANTHERSeries) 1KR-XL 10KR 3kVA/2400 6kVA/4800 10kVA Rating 1kVA/800W 2kVA 1600W J/000W Input system Single phase & earth ground Rated voltage 220VAC Voltage range 115VAC〜300VAC 120VAC〜275VAC Frequency 50/60Hz Power factor Input Voltage range of 80VAC 〜285VAC 187VAC 〜253VAC bypass...
  • Page 36: Environmental

          7.2 Environmental Item   Normal range   Ambient temperature   0℃~40℃  ~90%(No condensation)   Environment humidity   Altitude   Lower than 1000m: no derating Over 1000m :1% derating for every 100m rise Storage temperature   ‐15℃~45℃    7.3 EMC Item  ...
  • Page 37: Warranty

    Damage or loss resulted from force majeure or external causes;  Disassembly or modifications to the unit with no authorization;  Disobeying provisions of operating/using the unit;  Battery over discharged or man-made damage. Headquarter: Via G. Cappalonga 9/A‐ 00043 Ciampino (Rm) (Italy)  tel. +39.06.79800323 fax +39.06.79814644    Factory: Via Cascina Secchi 247/4b ‐ 24040 Isso (BG)  tel. +39.0363.938231 fax +39.0363.998235  www.sinercom.it 35   ...

Table of Contents