Mitsubishi Electric MS-09SN-C1 Service Manual page 26

Table of Contents

Advertisement

(4) The initial set temperature is decided by the initial room temperature.
Mode
COOL mode of
"I FEEL CONTROL"
DRY mode of
"I FEEL CONTROL"
1 When the system is restarted with the remote controller, the system operates with the previous set temperature regard-
less of the room temperature at restart.
The set temperature is calculated by the previous set temperature.
(5) TEMPERATURE buttons
In "I FEEL CONTROL" (
In addition, set temperature can be controlled by TOO WARM or TOO COOL buttons when you feel too cool or too
warm. Each time the TOO WARM or TOO COOL button is pressed, the indoor unit receives the signal and emits a
beep tone.
Fuzzy control
When the TOO COOL or TOO WARM button is pressed, the microprocessor changes the set temperature, considering
the room temperature, the frequency of pressing TOO COOL or TOO WARM button and the user's preference to heat
or cool. So this is called "Fuzzy control", and works only in "I FEEL CONTROL" mode.
In DRY mode of "I FEEL CONTROL", the set temperature doesn't change.
TOO
COOL
... To raise the set temperature 1~2 degrees(°C)
TOO
WARM
... To lower the set temperature 1~2 degrees(°C)
8-1-1. COOL mode of "I FEEL CONTROL"
1. Indoor fan speed control
Indoor fan operates continuously at the set speed by FAN SPEED CONTROL button regard-
less of thermostat's OFF-ON.
In Auto the fan speed is as follows.
MS-09/10/12/15/17/24SN-
Room temperature minus set temperature : 2 degrees or more·······························High
Room temperature minus set temperature : Between 1 and 2 degrees···················Med.
Room temperature minus set temperature : less than 1 degree·······························Low
MS-09/10/12/15SN-
, MS-18SN-
C2
Room temperature minus set temperature : 1.7 degrees or more·······························High
Room temperature minus set temperature : Between 1 and 1.7 degrees···················Med.
Room temperature minus set temperature : less than 1 degree··································Low
2. Coil frost prevention
Temperature control
When the indoor coil thermistor RT12 reads 4°C or below(MS-09/10SN) / -1°C or below(MS-12/15/17/18/24SN) for 5 min-
utes, the coil frost prevention mode starts.
The indoor fan operates at the set speed and the compressor stops for 5 minutes.
After that, if RT12 still reads below 4°C(MS-09/10SN) / or below -1°C(MS-12/15/17/18/24SN), this mode is prolonged until
the RT12 reads over 4°C(MS-09/10SN) / -1°C(MS-12/15/17/18/24SN).
Time control
When the three conditions as follows have been satisfied for 1 hour and 45 minutes, the compressor stops for 3 minutes.
The indoor fan operates at the set speed.
a. Compressor has been continuously operating.
b. Indoor fan speed is Low or Med..
c. Room temperature is below 26°C.
Initial room temperature
26: or more
25: to 26:
more than 13:, less than 25:
) mode, set temperature is decided by the microprocessor based on the room temperature.
C1
Initial temperature difference
C1
Initial temperature difference
Initial room temperature
minus 2:
Initial room temperature
minus 2:
Fan speed
Fan speed
26
Initial set temperature
24:
Difference between room
temperature and set tem-
perature during operation
2 deg. 4 deg.
1 deg. 1.7 deg.
Difference between room
temperature and set tem-
perature during operation
1 deg. 1.7 deg.
1
3 deg.