Mitsubishi A1S64TCTT-S1 User Manual page 3

Advertisement

3. Name of Each Part
A
1S64TCTT-S1
RUN
OUT
OUT
CH1
CH3
1)
ALM
ALM
OUT
OUT
CH2
CH4
ALM
ALM
L1
1
2
L2
L3
3
4
L4
+
-
5
NC
6
NC
7
+
8
C
+
H
9
C
2
-
10
H
2)
-
1
11
12
C
13
J
14
15
NC
16
+
17
C
+
18
H
C
-
3
H
19
4
20
-
A1S64TCTT-S1 LED
A
1S64TCTT-S1
RUN
OUT
OUT
CH1
CH3
ALM
ALM
OUT
OUT
CH2
CH4
ALM
ALM
Number
Name
1)
LED
RUN
A1S64TC operation status display
ON: Normal operation
Flashing (2 sec. ON, 2 sec. OFF)
: When write data error occurs
Flashing (1 sec. ON, 1 sec. OFF): Hardware error
OFF: 5V power OFF
OUT
Transistor output status display
ON: Transistor output ON
OFF: Transistor output OFF
ALM
Alert alarm status display
ON
: The alert alarm is turned ON.
Flashing: The measured temperature range is
OFF
BR.W
Heater disconnection detection status display
ON: The heater disconnection is detected.
OFF: The heater disconnection has not been
detected.
2)
Cool contact
temperature
Shipped pre-installed to the terminal block.
compensation
resistor
3)
Disconnection
Connector to the current sensor
detection
connector
A
1S64TCTTBW-S1
RUN
OUT
OUT
1)
CH1
ALM
ALM
CH3
BR.W
BR.W
OUT
OUT
CH2
ALM
ALM
CH4
BR.W
BR.W
L1
1
2
L2
L3
3
4
L4
+
-
5
NC
6
NC
7
+
8
C
+
H
9
C
2
-
10
H
2)
-
1
11
12
C
13
J
14
15
NC
16
+
17
C
{
18
H
C
|
-
3
H
19
4
20
-
3)
A1S64TCTTBW-S1 LED
A
1S64TCTTBW-S1
RUN
OUT
OUT
CH1
ALM
ALM
BR.W
BR.W
OUT
OUT
CH2
ALM
ALM
BR.W
BR.W
Description
LAB error occurred.
exceeded.
The thermocouple is not connected.
The thermocouple cable is not connected.
: The alert alarm is OFF.
Wire breakage detection connector
installation screw
BW1(For CH1)
BW2(For CH2)
Cable fixing screws
BW3(For CH3)
BW4(For CH4)
4. Loading and Installation
Precautions when handling the A1S64TC and installation enviroment
are explained.
For details of implementing and setting up this unit, please refer to the
User's Manual for the PC CPU used.
4.1
Handling Instructions
1) The module case is made of plastic. Be sure not to drop it or
subject it to strong vibration.
2) Do not remove the module printed circuit boards from the case.
It may cause trouble.
3) When connecting the wiring, do not allow wire cuttings or other
foreign matter to enter from the top of the module. Remove any
foreign matter from the module.
4) Tighten the module installation screws within the following
tightening torque range.
Module installation screw (M4 screw)
Terminal block terminal screw (M3.5 screw)
Terminal block installation screw
(M4 screw)
Wire breakage detection connector installation
screw *(M2.6 screws)
Cable fixing screw *(M2 screws)
*: Use only for A1S64TCTTBW-S1.
4.2 Installations Enviroment
Never install the AnS series PC in the following environments:
1) Locations where the ambient temperature is outside the range of 0
to 55 .
2) Locations where the ambient humidity is outside the range of 10 to
CH3
90%RH.
3) Locations where dew condensation takes place due to sudden
temperature changes.
CH4
4) Locations where there are corrosive and/or combustible gasses.
5) Locations where there is a high level of conductive power (such as
dust and iron filings, oil mist, salt, and organic solvents).
6) Locations exposed to the direct rays of the sun.
7) Locations where strong power and magnetic fields are generated.
8) Locations where vibration and shock are directly transmitted to the
main module.
5. Wiring
The precaution when wiring and the module connection example are
shown below.
5.1 Precaution when wiring
In order to have the best result from the A1S64TC functions and to
make the system highly reliable, an external cabling with low noise
effects are necessary.
The external wiring precautions are shown below:
1) Use separate cables for the alternating current and A1S64TC
external input signals to avoid A/C surges and induction effects.
2) Do not bunch the cables with the main circuit, high-voltage cable or
load cables from other than PC, or install them close to each other.
Install the cables far apart from high-frequency circuits, such as the
high-voltage cable and inverter load main circuit, as much as
possible.
This increases the noises, surges, and induction.
3) Perform a one-point grounding for the shielded line and shields of
the seal and cable at the PC. However, there may be cases when
grounding should be performed externally depending on the noise
condition.
Screw position
Tightening torque range
78 to 118N•cm
59 to 88N•cm
78 to 118N•cm
15 to 30N•cm
11 to 14N•cm

Advertisement

loading

This manual is also suitable for: