Input configuration

CP 14
OFF = Temperature setback is disabled
ON = Temperature setback is enabled
CP 15
Set point limit at full setback
CP 16
Lower temperature limit:
Outside temperature with maximum setback
The set point will be equal to the minimum set point limit
CP 17
Upper temperature limit:
Outside temperature at begin of setback.
CP 18
Number of seconds taken into account to calculate the
averaging input signal.
Low value = fast response
High value = slow response
Temperature setback (TSET)
Shift the humidity set point towards a defined TSET set point CP15 depending on the outdoor temperature.
Temperature setback becomes active when the outside temperature drops below the activation limit of temperature
setback CP17. The full temperature setback is reached when the temperature reaches the full limit CP16. The actual
set point will in this case be equal to the TSET set point.
Temperature setback may be enabled with CP14.
Setpoint
Temperature setback
W
CP15
CP16
Averaging function of input signal:
The averaging function is used to prevent unwanted fluctuation of sensor signals. The controller measures every
second the signal inputs. The input signal is built over a number of measured values. Select how many values should
be used to calculate the averaging signal. Control speed will slow down when a large number of samples are used for
an averaging signal. This should be taken into account when defining the control parameters.
Doc: 70-00-0142, V1.4, 20160912
Subject to alteration
T [°C, F]
CP17
© Vector Controls GmbH, Switzerland
www.vectorcontrols.com
Humidistat TCY-BH
ON, OFF
OFF
0...100%
20%
-40...60°C
-30°C (-22°F)
-40...160°F
-40...60°C
0°C (32°F)
40...160°F
0...100
10