Reference Scaling

ABB Drives and DCU Profiles

The following table describes
Reference
REF1
REF2
Note! The setting of parameter 1104
the scaling of references.
When parameter 1103
COMM
Reference
REF1
Embedded Fieldbus
Reference
Range
Type
-32767
Speed or
...
frequency
+32767
-32767
Speed or
...
frequency
+32767
Torque
PID
Reference
1
REF
*
1, the reference is scaled as follows:
AI
Value
Setting
+
1
COMM
AI
COMM
scaling for the ABB Drives profile.
REFERENCE
ABB Drives and DCU Profiles
Scaling
-20000 = -(par. 1105)
0 = 0
+20000 = (par. 1105)
(20000 corresponds to 100%)
-10000 = -(par. 1108)
0 = 0
+10000 = (par. 1108)
(10000 corresponds to 100%)
-10000 = -(par. 1108)
0 = 0
+10000 = (par. 1108)
(10000 corresponds to 100%)
-10000 = -(par. 1108)
0 = 0
+10000 = (par. 1108)
(10000 corresponds to 100%)
1
and 1107
REF
MIN
or 1106
2
SELECT
REF
ABB Drives and DCU Profiles
AI Reference Scaling
(%) +(
(%) - 0.5*
1
AI
REF
MAX
(100 + 0.5 * (Par. 1105)%
100%
(100 - 0.5 * (par. 1105))%
0%
ACH550-UH User's Manual
Remarks
Final reference limited by
1104/1105. Actual motor
speed limited by 2001/2002
(speed) or 2007/2008
(frequency).
Final reference limited by
1107/1108. Actual motor
speed limited by 2001/2002
(speed) or 2007/2008
(frequency).
Final reference limited by
2015/2017 (torque1) or 2016/
2018 (torque2).
Final reference limited by
4012/4013 (PID set1) or
4112/4113 (PID set2).