Page 1
MODEL 5895XL Intelligent Power Module for the 5820XL System E C N : 1 1 - 0 3 1 7 Installation and Document 151142-L8 Operations Manual Rev: 151142-L8:J 15-0644...
..................2-1 What’s in the Box? ........................2-1 Environmental Specifications ....................2-1 Preventing Water Damage .......................2-1 5895XL Board and Terminal Strip Description .................2-2 Earth Fault Resistance ......................2-4 Calculating Current Draw and Standby Battery ................2-5 2.6.1 Worksheet Requirements ....................2-5 Filling in the Current Draw Worksheet, Table 2-4 (Section 2.6.2) ........2-5 2.6.1.1 Maximum Battery Standby Load ................2-5...
Page 4
Model 5895XL Intelligent Power Module Installation and Operation Manual 3.5.4 Installing 2-Wire Smoke Detectors ...................3-10 Class B Installation .......................3-10 2-Wire Class A Smoke Detector Installation ..............3-11 3.5.5 Installing 4-Wire Smoke Detectors ...................3-12 Installing a Class B 4-Wire Smoke Detector ..............3-12 Installing 4-Wire Class A Smoke Detectors ..............3-13...
Note: The 5808 does not use 5815XL SLC expanders. The 5895XL has six Flexputs™ and two programmable relays. Outputs are rated 3.0 A (6.0 A total for each 5895XL). Relays are Form C rated at 2.5 A @ 24 VDC. Outputs and relays are fully programmable.
The chart below shows the maximum number of compatible modules that can be used in an IntelliKnight installation. Modules can be distributed among the main panel SBUS and each additional 5895XL SBUS in virtually any combination. Module or Device Maximum Number...
Page 7
Overview Figure 1-1 Example 5895XL Installation Overview 151142...
Page 8
Model 5895XL Intelligent Power Module Installation and Operation Manual Figure 1-2 Example 5895XL Installation Overview (Details Added) 151142...
Overview Agency Requirements The 5895XL has the same requirements as the main control panel. These requirements are listed in the IntelliKnight 5820XL Installation Manual (P/N 151209). About This Manual This manual covers installation of 5895XL hardware. Software configuration information is contained in the IntelliKnight 5820XL Installation Manual (P/N 151209).
Do not mount in areas with humidity-generating equipment (such as dryers, pro- duction machinery) When selecting a location to mount the 5895XL, the unit should be mounted where it will NOT be exposed to temperatures outside the range of 0°C-49°C (32°F-120°F) or humidity outside the range of 10%-93% at 30°C (86°F) non-condensing.
Model 5895XL Intelligent Power Module Installation and Operation Manual 5895XL Board and Terminal Strip Description Figure 2-1 shows the 5895XL circuit board including location of terminals, the DIP switch for setting module ID, and the LED. Figure 2-1 The 5895XL Board Layout...
Page 12
24 VDC 2.5 A N.O. 5895XL communication with SBUS IN/ main panel or to controlling 5 VDC 100 mA 5895XL if daisy-chained 5895XL SBUS power (from MAIN 24 VDC 10 mA 5820XL) * Regulated/special application when used for releasing. 151142...
Model 5895XL Intelligent Power Module Installation and Operation Manual Earth Fault Resistance Table 2-2 lists the earth fault resistance detection for each applicable terminal on the FACP. Table 2-2: Earth Fault Resistance Values by Terminal Terminal Label Low Biased High Biased...
Filling in the Current Draw Worksheet, Table 2-4 (Section 2.6.2) 1. For the 5895XL, the worst case current draw is listed for the panel, addressable devices, and SLC expanders. Fill in the number of addressable devices and expanders that will be used in the system and compute the current draw require- ments for alarm and standby.
Model 5895XL Intelligent Power Module Installation and Operation Manual 2.6.2 Current Draw Worksheet For *each 5895XL in the installation, use this worksheet to determine current requirements during alarm/battery standby operation. (Copy this page if additional space is required.) Table 2-4: Current Draw Calculations...
1 amp limit, then the current draw must be distributed using 5895XL Power Expanders. Each 5895XL Power Expander provides an additional SBUS, with an additional 1 amp of SBUS current. Wiring distance calculations are done separately for each 5895XL, and separately for the panel itself.
Page 17
Model 5895XL Intelligent Power Module Installation and Operation Manual These cases are marked in the chart with an asterisk (*). Maximum length can never be more than 6,000 feet, regardless of gauge used. (The formula used to generate this chart is shown in the note below).
Wiring Distance calculation example: Suppose a system is configured with the following SBUS modules: 2 - Module 5860 Fire Annunciator 1 - 5895XL Intelligent Power Expander 1 - 5865 LED Fire Annunciator 1 - 5824 Parallel/Serial Interface The total worst case current is calculated as follows: 5860 Current Draw = 2 x .100 amps...
Model 5895XL Intelligent Power Module Installation and Operation Manual 2.7.3 Wire Routing You must follow power-limited wiring techniques, which includes maintaining one-quarter inch spacing between power-limited and nonpower-limited circuits and separating high and low voltage circuits. 5895XL Board Figure 2-2 Wire Routing Example...
• Physical connection of any outputs (conventional relays, notification appliances, auxiliary power modules, and so on) that will be powered by this 5895XL. See Section 3.5.1 for notification appliance wiring information. Refer to the IntelliKnight 5820XL Installation Manual (P/N 151209), for software configuration information and other information about installing outputs.
Model 5895XL Intelligent Power Module Installation and Operation Manual Battery Connection The 5895XL battery charge capacity is 7.0 to 33.0 AH. Use 12V batteries of the same AH rating. Determine the correct AH rating as per your current load calculation (see Section Table 2-4).
2. Use on-board DIP switch to assign an ID#. (See Section 3.3.1) Figure 2-1 shows the location of the DIP switches on the 5895XL board. 3. Configure the 5895XL module by adding it to the system (through JumpStart or manually). You can also assign a name to the module. These procedures are described in the IntelliKnight 5820XL Installation Manuals (P/N 151209).
Page 23
Model 5895XL Intelligent Power Module Installation and Operation Manual See Figure 3-6 for SBUS Module Connections See Figure 3-6 for SBUS Module Connections Figure 3-4 Class A 5895XL Connection to FACP 151142...
Hardware Installation 3.3.1 Setting the Device ID board to set the module ID#. Figure 2-1 shows the location of the DIP switch on the board. Figure 3-5 Possible Module Addresses 151142...
Model 5895XL Intelligent Power Module Installation and Operation Manual Connecting SBUS Modules to the 5895XL 1. Connect SBUS modules to the 5895XL as shown in Figure 3-6 or Figure 3-7. 2. All SBUS modules must have an ID. Use the DIP switches on the module board to assign an ID number (1-31) to the module.
Flexputs I/O Circuits The six Flexput™ circuits are an innovative and versatile feature of the 5895XL panel. They can be used as: Class A or B notification circuits, Class A or B initiation circuits (either 2 or 4 wire detectors), or as auxiliary power (resettable, continuous, or door holder).
Model 5895XL Intelligent Power Module Installation and Operation Manual spacing in accordance with NFPA 72. Table 3-1: Approved Releasing Solenoids Manufacturer Part Number Rating Current Freq Asco T8210A107 24 VDC 3A max 0 Hz 8210G207 24 VDC 3A max 0 Hz 3.5.2.1 Class B Notification Wiring...
Hardware Installation 3.5.2.2 Class A Notification Wiring You must use an appliance from the list of compatible appliances in the Appendix A at the back of this manual. To install a Class A notification appliance circuit: 1. Wire the Class A notification appliances as shown in Figure 3-9. 2.
3.5.3.1 Class B Inputs You can connect conventional Class B switches, such as waterflow switches and pull stations, directly to the I/O circuits of the 5895XL panel. To install a Class B switch: 1. Wire the Class B switch as shown in Figure 3-10.
3.5.4 Installing 2-Wire Smoke Detectors Any compatible U.L. listed two-wire smoke detector can be used with the 5895XL panel (see Appendix A for list of compatible smoke detectors). Figure 3-12 and Figure 3-13 illustrate how to connect a UL listed 2-wire detector to the control panel.
Model 5895XL Intelligent Power Module Installation and Operation Manual Class B Installation To install a Class B two-wire smoke detector, wire as shown in Figure 3-12. Note: I/O circuit 5 used as an example. Any I/O circuit UL Listed EOL could be used.
3.5.5 Installing 4-Wire Smoke Detectors Any compatible U.L. listed four-wire smoke detector can be used with the 5895XL panel (see Appendix A for list of compatible smoke detectors). Figure 3-12 and Figure 3-13 illustrate how to connect a UL listed four-wire detector to the control panel.
Model 5895XL Intelligent Power Module Installation and Operation Manual Installing 4-Wire Class A Smoke Detectors Figure 3-15 illustrates how to install 4-wire Class A detectors. Conventions used for wiring 4-wire Class A loops: 1. Up to two Class A 4-wire loops can be connected to the control panel at once.
30 seconds, then re-applied. Conventional Relay Installation 5895XL relay circuits are installed in exactly the same way as 5820XL main panel relay circuits. For ease of installation, the 5895XL output terminals use the same numbering scheme as 5820XL terminals.
Page 35
For proper operation, you must use polarized devices with a Model 7628 4.7k ohm EOL resistor on each loop. All supervised notification appliances used with the 5895XL must be polarized. Note: Not all devices can use the Sync feature, be sure to check Table A-1 to ensure the device you have chosen will work with this feature.
Page 36
Model 5895XL Intelligent Power Module Installation and Operation Manual Table A-1: Compatible Notification Appliances Manufacturer Model Audio Visual Type Vibrating Bell Vibrating Bell Single Stroke Bell 2700 -M. -R, -T, -Y, -Z Strobe 2701 Series Strobe 2705 Series Strobe 2820...
Compatible Devices Table A-1: Compatible Notification Appliances Manufacturer Model Audio Visual Type 5378 8-Tone Horn/Strobe 5383 8-Tone Horn/Strobe with Sync Strobe 5386 8-Tone Horn/Strobe with Sync Strobe 5387 8-Tone Horn/Strobe with Sync Strobe 5388 8-Tone Horn/Strobe with Sync Strobe 5508 Single Gang Sync Strobe 5509 Strobe...
Page 38
Model 5895XL Intelligent Power Module Installation and Operation Manual Table A-1: Compatible Notification Appliances Manufacturer Model Audio Visual Type BLVCH Vibrating Chime H12/24-FC Horn H12/24W-FC Horn H12/24K-FC Horn HC12/24-FC Horn HC12/24W-FC Horn HC12/24K-FC Horn P2415-FC Horn/Strobe P2415W-FC Horn/Strobe P2415K-FC Horn/Strobe...
Page 39
Compatible Devices Table A-1: Compatible Notification Appliances Manufacturer Model Audio Visual Type HG124 Horn HS24-15 Horn/Strobe HS24-30 Horn/Strobe HS24-60 Horn/Strobe HS24-75 Horn/Strobe HS24-110 Horn/Strobe HS24-1575 Horn/Strobe GCC24 Multi Candella Horn/Strobe Ceiling Mount GCCR24 Multi Candella Horn/Strobe Ceiling Mount GCS24 Multi Candella Strobe Ceiling Mount GCSR24 Multi Candella Strobe Ceiling Mount GECR-24...
Page 40
Model 5895XL Intelligent Power Module Installation and Operation Manual Table A-1: Compatible Notification Appliances Manufacturer Model Audio Visual Type Chime Chime CHSR 2-Wire Chime/Strobe CHSW 2-Wire Chime/Strobe Horn Horn Horn Horn WHT Wall 4x4 Horn Red Wall 4x4 HGRL Horn Red Wall 2x4...
Page 41
Compatible Devices Table A-1: Compatible Notification Appliances Manufacturer Model Audio Visual Type P2WH-P 2-Wire Horn/Strobe High Candela PC2WH 2-Wire Horn/Strobe High Candela PC2WH-P 2-Wire Horn/Strobe High Candela P2RK 2-Wire Horn/Strobe PC2RK 2-Wire Horn/Strobe P2RHK 2-Wire Horn/Strobe High Candela PC2RHK 2-Wire Horn/Strobe High Candela 4-Wire Horn/Strobe PC4R 4-Wire Horn/Strobe...
Page 42
Model 5895XL Intelligent Power Module Installation and Operation Manual Table A-1: Compatible Notification Appliances Manufacturer Model Audio Visual Type SCWH-P Strobe High Candela Strobe SCRK Strobe SRHK Strobe High Candela SCRHK Strobe High Candela SRL, SRL-P, SRL-SP* Strobe Red Wall 4x4...
Control unit Smoke Reset Time must be programmed for a number greater than or equal to the maximum reset time of the smoke detector. Table A-2 lists two-wire smoke detectors that are compatible with the 5895XL panel. The table is 151142...
Page 46
Model 5895XL Intelligent Power Module Installation and Operation Manual organized by manufacturer. The columns show the number of detectors per loop that can be used. Table A-2: Compatible Two-Wire Smoke Detectors Model Name or Number Compatibility ID Manufacturer (Base model name or number in...
Page 47
Compatible Devices Table A-2: Compatible Two-Wire Smoke Detectors Model Name or Number Compatibility ID Manufacturer (Base model name or number in # per Loop Head Base parentheses.) PSD 7156 (FE01A) (P56FE1) P56FE1 FE01A 30 / loop PSD 7156 (FE51A) (P56FE1) P56FE1 FE51A 30 / loop...
Page 48
Model 5895XL Intelligent Power Module Installation and Operation Manual Table A-2: Compatible Two-Wire Smoke Detectors Model Name or Number Compatibility ID Manufacturer (Base model name or number in # per Loop Head Base parentheses.) 1100T 30 / loop 1100TB 30 / loop...
2040-24 Power Supervision Unit Hochiki SIH-24F HS-224D or SHB-224 Base SLK-24F HS-224D Base SLK-23FH HS-224D Base System Sensor 1851B 2851/2851BTH DH200ADCD A.3.1 Door Holder Device The following UL listed door holder can be used with the 5895XL: ESL DHS-1224 151142 A-15...
UPS ground. • Return the Silent Knight product circuit board only. Products that are returned in cabinets will be charged an additional $50 to cover the extra shipping and handling costs over board only returns. Do not return batteries to Honeywell has the authority to determine if a product is repairable.
• Repairs and returns should be sent to: Honeywell Fire Systems Attn: Repair Department / RA Number_______________________ 12 Clintonville Road Northford, CT 06472 USA Manufacturer Warranties and Limitation of Liability Manufacturer Warranties. Subject to the limitations set forth herein, Manufacturer warrants that the Products manufactured by it in its Northford, Connecticut facility and sold by it to its authorized Distributors shall be free, under normal use and service, from defects in material and workmanship for a period of thirty six months (36) months from the date of manufacture (effective Jan.