SILENT KNIGHT 5895XL Installation And Operation Manual
SILENT KNIGHT 5895XL Installation And Operation Manual

SILENT KNIGHT 5895XL Installation And Operation Manual

Intelligent power module for the 5820xl system
Table of Contents

Advertisement

MODEL
5895XL
Intelligent Power Module
for the 5820XL System
E C N : 1 1 - 0 3 1 7
Installation and
Document 151142-L8
J
Operations Manual
Rev:
151142-L8:J
15-0644

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 5895XL and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for SILENT KNIGHT 5895XL

  • Page 1 MODEL 5895XL Intelligent Power Module for the 5820XL System E C N : 1 1 - 0 3 1 7 Installation and Document 151142-L8 Operations Manual Rev: 151142-L8:J 15-0644...
  • Page 3: Table Of Contents

    ..................2-1 What’s in the Box? ........................2-1 Environmental Specifications ....................2-1 Preventing Water Damage .......................2-1 5895XL Board and Terminal Strip Description .................2-2 Earth Fault Resistance ......................2-4 Calculating Current Draw and Standby Battery ................2-5 2.6.1 Worksheet Requirements ....................2-5 Filling in the Current Draw Worksheet, Table 2-4 (Section 2.6.2) ........2-5 2.6.1.1 Maximum Battery Standby Load ................2-5...
  • Page 4 Model 5895XL Intelligent Power Module Installation and Operation Manual 3.5.4 Installing 2-Wire Smoke Detectors ...................3-10 Class B Installation .......................3-10 2-Wire Class A Smoke Detector Installation ..............3-11 3.5.5 Installing 4-Wire Smoke Detectors ...................3-12 Installing a Class B 4-Wire Smoke Detector ..............3-12 Installing 4-Wire Class A Smoke Detectors ..............3-13...
  • Page 5: Overview

    Note: The 5808 does not use 5815XL SLC expanders. The 5895XL has six Flexputs™ and two programmable relays. Outputs are rated 3.0 A (6.0 A total for each 5895XL). Relays are Form C rated at 2.5 A @ 24 VDC. Outputs and relays are fully programmable.
  • Page 6: Maximum Number Of Sbus Modules

    The chart below shows the maximum number of compatible modules that can be used in an IntelliKnight installation. Modules can be distributed among the main panel SBUS and each additional 5895XL SBUS in virtually any combination. Module or Device Maximum Number...
  • Page 7 Overview Figure 1-1 Example 5895XL Installation Overview 151142...
  • Page 8 Model 5895XL Intelligent Power Module Installation and Operation Manual Figure 1-2 Example 5895XL Installation Overview (Details Added) 151142...
  • Page 9: Agency Requirements

    Overview Agency Requirements The 5895XL has the same requirements as the main control panel. These requirements are listed in the IntelliKnight 5820XL Installation Manual (P/N 151209). About This Manual This manual covers installation of 5895XL hardware. Software configuration information is contained in the IntelliKnight 5820XL Installation Manual (P/N 151209).
  • Page 10: Before You Begin Installing

    Do not mount in areas with humidity-generating equipment (such as dryers, pro- duction machinery) When selecting a location to mount the 5895XL, the unit should be mounted where it will NOT be exposed to temperatures outside the range of 0°C-49°C (32°F-120°F) or humidity outside the range of 10%-93% at 30°C (86°F) non-condensing.
  • Page 11: 5895Xl Board And Terminal Strip Description

    Model 5895XL Intelligent Power Module Installation and Operation Manual 5895XL Board and Terminal Strip Description Figure 2-1 shows the 5895XL circuit board including location of terminals, the DIP switch for setting module ID, and the LED. Figure 2-1 The 5895XL Board Layout...
  • Page 12 24 VDC 2.5 A N.O. 5895XL communication with SBUS IN/ main panel or to controlling 5 VDC 100 mA 5895XL if daisy-chained 5895XL SBUS power (from MAIN 24 VDC 10 mA 5820XL) * Regulated/special application when used for releasing. 151142...
  • Page 13: Earth Fault Resistance

    Model 5895XL Intelligent Power Module Installation and Operation Manual Earth Fault Resistance Table 2-2 lists the earth fault resistance detection for each applicable terminal on the FACP. Table 2-2: Earth Fault Resistance Values by Terminal Terminal Label Low Biased High Biased...
  • Page 14: Calculating Current Draw And Standby Battery

    Filling in the Current Draw Worksheet, Table 2-4 (Section 2.6.2) 1. For the 5895XL, the worst case current draw is listed for the panel, addressable devices, and SLC expanders. Fill in the number of addressable devices and expanders that will be used in the system and compute the current draw require- ments for alarm and standby.
  • Page 15: Current Draw Worksheet

    Model 5895XL Intelligent Power Module Installation and Operation Manual 2.6.2 Current Draw Worksheet For *each 5895XL in the installation, use this worksheet to determine current requirements during alarm/battery standby operation. (Copy this page if additional space is required.) Table 2-4: Current Draw Calculations...
  • Page 16: Wiring Specifications

    1 amp limit, then the current draw must be distributed using 5895XL Power Expanders. Each 5895XL Power Expander provides an additional SBUS, with an additional 1 amp of SBUS current. Wiring distance calculations are done separately for each 5895XL, and separately for the panel itself.
  • Page 17 Model 5895XL Intelligent Power Module Installation and Operation Manual These cases are marked in the chart with an asterisk (*). Maximum length can never be more than 6,000 feet, regardless of gauge used. (The formula used to generate this chart is shown in the note below).
  • Page 18: Wiring Distance Calculation Example

    Wiring Distance calculation example: Suppose a system is configured with the following SBUS modules: 2 - Module 5860 Fire Annunciator 1 - 5895XL Intelligent Power Expander 1 - 5865 LED Fire Annunciator 1 - 5824 Parallel/Serial Interface The total worst case current is calculated as follows: 5860 Current Draw = 2 x .100 amps...
  • Page 19: Wire Routing

    Model 5895XL Intelligent Power Module Installation and Operation Manual 2.7.3 Wire Routing You must follow power-limited wiring techniques, which includes maintaining one-quarter inch spacing between power-limited and nonpower-limited circuits and separating high and low voltage circuits. 5895XL Board Figure 2-2 Wire Routing Example...
  • Page 20: Hardware Installation

    • Physical connection of any outputs (conventional relays, notification appliances, auxiliary power modules, and so on) that will be powered by this 5895XL. See Section 3.5.1 for notification appliance wiring information. Refer to the IntelliKnight 5820XL Installation Manual (P/N 151209), for software configuration information and other information about installing outputs.
  • Page 21: Battery Connection

    Model 5895XL Intelligent Power Module Installation and Operation Manual Battery Connection The 5895XL battery charge capacity is 7.0 to 33.0 AH. Use 12V batteries of the same AH rating. Determine the correct AH rating as per your current load calculation (see Section Table 2-4).
  • Page 22: Connecting The 5895Xl To The Facp

    2. Use on-board DIP switch to assign an ID#. (See Section 3.3.1) Figure 2-1 shows the location of the DIP switches on the 5895XL board. 3. Configure the 5895XL module by adding it to the system (through JumpStart or manually). You can also assign a name to the module. These procedures are described in the IntelliKnight 5820XL Installation Manuals (P/N 151209).
  • Page 23 Model 5895XL Intelligent Power Module Installation and Operation Manual See Figure 3-6 for SBUS Module Connections See Figure 3-6 for SBUS Module Connections Figure 3-4 Class A 5895XL Connection to FACP 151142...
  • Page 24: Setting The Device Id

    Hardware Installation 3.3.1 Setting the Device ID board to set the module ID#. Figure 2-1 shows the location of the DIP switch on the board. Figure 3-5 Possible Module Addresses 151142...
  • Page 25: Connecting Sbus Modules To The 5895Xl

    Model 5895XL Intelligent Power Module Installation and Operation Manual Connecting SBUS Modules to the 5895XL 1. Connect SBUS modules to the 5895XL as shown in Figure 3-6 or Figure 3-7. 2. All SBUS modules must have an ID. Use the DIP switches on the module board to assign an ID number (1-31) to the module.
  • Page 26: Flexputs™ I/O Circuits

    Flexputs I/O Circuits The six Flexput™ circuits are an innovative and versatile feature of the 5895XL panel. They can be used as: Class A or B notification circuits, Class A or B initiation circuits (either 2 or 4 wire detectors), or as auxiliary power (resettable, continuous, or door holder).
  • Page 27: Class B Notification Wiring

    Model 5895XL Intelligent Power Module Installation and Operation Manual spacing in accordance with NFPA 72. Table 3-1: Approved Releasing Solenoids Manufacturer Part Number Rating Current Freq Asco T8210A107 24 VDC 3A max 0 Hz 8210G207 24 VDC 3A max 0 Hz 3.5.2.1 Class B Notification Wiring...
  • Page 28: Class A Notification Wiring

    Hardware Installation 3.5.2.2 Class A Notification Wiring You must use an appliance from the list of compatible appliances in the Appendix A at the back of this manual. To install a Class A notification appliance circuit: 1. Wire the Class A notification appliances as shown in Figure 3-9. 2.
  • Page 29: Conventional Initiation Circuits

    3.5.3.1 Class B Inputs You can connect conventional Class B switches, such as waterflow switches and pull stations, directly to the I/O circuits of the 5895XL panel. To install a Class B switch: 1. Wire the Class B switch as shown in Figure 3-10.
  • Page 30: Installing 2-Wire Smoke Detectors

    3.5.4 Installing 2-Wire Smoke Detectors Any compatible U.L. listed two-wire smoke detector can be used with the 5895XL panel (see Appendix A for list of compatible smoke detectors). Figure 3-12 and Figure 3-13 illustrate how to connect a UL listed 2-wire detector to the control panel.
  • Page 31: Class B Installation

    Model 5895XL Intelligent Power Module Installation and Operation Manual Class B Installation To install a Class B two-wire smoke detector, wire as shown in Figure 3-12. Note: I/O circuit 5 used as an example. Any I/O circuit UL Listed EOL could be used.
  • Page 32: Installing 4-Wire Smoke Detectors

    3.5.5 Installing 4-Wire Smoke Detectors Any compatible U.L. listed four-wire smoke detector can be used with the 5895XL panel (see Appendix A for list of compatible smoke detectors). Figure 3-12 and Figure 3-13 illustrate how to connect a UL listed four-wire detector to the control panel.
  • Page 33: Installing 4-Wire Class A Smoke Detectors

    Model 5895XL Intelligent Power Module Installation and Operation Manual Installing 4-Wire Class A Smoke Detectors Figure 3-15 illustrates how to install 4-wire Class A detectors. Conventions used for wiring 4-wire Class A loops: 1. Up to two Class A 4-wire loops can be connected to the control panel at once.
  • Page 34: Door Holder Power

    30 seconds, then re-applied. Conventional Relay Installation 5895XL relay circuits are installed in exactly the same way as 5820XL main panel relay circuits. For ease of installation, the 5895XL output terminals use the same numbering scheme as 5820XL terminals.
  • Page 35 For proper operation, you must use polarized devices with a Model 7628 4.7k ohm EOL resistor on each loop. All supervised notification appliances used with the 5895XL must be polarized. Note: Not all devices can use the Sync feature, be sure to check Table A-1 to ensure the device you have chosen will work with this feature.
  • Page 36 Model 5895XL Intelligent Power Module Installation and Operation Manual Table A-1: Compatible Notification Appliances Manufacturer Model Audio Visual Type Vibrating Bell Vibrating Bell Single Stroke Bell 2700 -M. -R, -T, -Y, -Z Strobe 2701 Series Strobe 2705 Series Strobe 2820...
  • Page 37: Appendix A Compatible Devices

    Compatible Devices Table A-1: Compatible Notification Appliances Manufacturer Model Audio Visual Type 5378 8-Tone Horn/Strobe 5383 8-Tone Horn/Strobe with Sync Strobe 5386 8-Tone Horn/Strobe with Sync Strobe 5387 8-Tone Horn/Strobe with Sync Strobe 5388 8-Tone Horn/Strobe with Sync Strobe 5508 Single Gang Sync Strobe 5509 Strobe...
  • Page 38 Model 5895XL Intelligent Power Module Installation and Operation Manual Table A-1: Compatible Notification Appliances Manufacturer Model Audio Visual Type BLVCH Vibrating Chime H12/24-FC Horn H12/24W-FC Horn H12/24K-FC Horn HC12/24-FC Horn HC12/24W-FC Horn HC12/24K-FC Horn P2415-FC Horn/Strobe P2415W-FC Horn/Strobe P2415K-FC Horn/Strobe...
  • Page 39 Compatible Devices Table A-1: Compatible Notification Appliances Manufacturer Model Audio Visual Type HG124 Horn HS24-15 Horn/Strobe HS24-30 Horn/Strobe HS24-60 Horn/Strobe HS24-75 Horn/Strobe HS24-110 Horn/Strobe HS24-1575 Horn/Strobe GCC24 Multi Candella Horn/Strobe Ceiling Mount GCCR24 Multi Candella Horn/Strobe Ceiling Mount GCS24 Multi Candella Strobe Ceiling Mount GCSR24 Multi Candella Strobe Ceiling Mount GECR-24...
  • Page 40 Model 5895XL Intelligent Power Module Installation and Operation Manual Table A-1: Compatible Notification Appliances Manufacturer Model Audio Visual Type Chime Chime CHSR 2-Wire Chime/Strobe CHSW 2-Wire Chime/Strobe Horn Horn Horn Horn WHT Wall 4x4 Horn Red Wall 4x4 HGRL Horn Red Wall 2x4...
  • Page 41 Compatible Devices Table A-1: Compatible Notification Appliances Manufacturer Model Audio Visual Type P2WH-P 2-Wire Horn/Strobe High Candela PC2WH 2-Wire Horn/Strobe High Candela PC2WH-P 2-Wire Horn/Strobe High Candela P2RK 2-Wire Horn/Strobe PC2RK 2-Wire Horn/Strobe P2RHK 2-Wire Horn/Strobe High Candela PC2RHK 2-Wire Horn/Strobe High Candela 4-Wire Horn/Strobe PC4R 4-Wire Horn/Strobe...
  • Page 42 Model 5895XL Intelligent Power Module Installation and Operation Manual Table A-1: Compatible Notification Appliances Manufacturer Model Audio Visual Type SCWH-P Strobe High Candela Strobe SCRK Strobe SRHK Strobe High Candela SCRHK Strobe High Candela SRL, SRL-P, SRL-SP* Strobe Red Wall 4x4...
  • Page 43 Compatible Devices Table A-1: Compatible Notification Appliances Manufacturer Model Audio Visual Type ASWP-24MCWH Horn/Strobe ASWP-24MCCH Horn/Strobe CH-70 Chime CH-90 Chime CH70-241575W Chime/Strobe CH70-24MCW Chime/Strobe CH70-24MCWH Chime/Strobe CH90-24MCC Chime/Strobe CH90-24MCCH Chime/Strobe HS-24 Horn HS4-241575W Horn/Strobe HS4-24MCW Horn/Strobe HS4-24MCWH Horn/Strobe HS4-24MCC Horn/Strobe MIZ-24S Mini Horn Strobe MT-121575W...
  • Page 44 Model 5895XL Intelligent Power Module Installation and Operation Manual Table A-1: Compatible Notification Appliances Manufacturer Model Audio Visual Type ZNS-24MCCH Horn/Strobe RSS-121575W Strobe RSS-241575W Strobe RSS-24MCC Strobe RSS-24MCCR Strobe RSS-24MCCH Strobe RSS-24MCCHR Strobe RSS-24MCW Strobe RSS-24MCWH Strobe RSSP-121575W Strobe RSSP-241575W...
  • Page 45: Two-Wire Smoke Detectors

    Control unit Smoke Reset Time must be programmed for a number greater than or equal to the maximum reset time of the smoke detector. Table A-2 lists two-wire smoke detectors that are compatible with the 5895XL panel. The table is 151142...
  • Page 46 Model 5895XL Intelligent Power Module Installation and Operation Manual organized by manufacturer. The columns show the number of detectors per loop that can be used. Table A-2: Compatible Two-Wire Smoke Detectors Model Name or Number Compatibility ID Manufacturer (Base model name or number in...
  • Page 47 Compatible Devices Table A-2: Compatible Two-Wire Smoke Detectors Model Name or Number Compatibility ID Manufacturer (Base model name or number in # per Loop Head Base parentheses.) PSD 7156 (FE01A) (P56FE1) P56FE1 FE01A 30 / loop PSD 7156 (FE51A) (P56FE1) P56FE1 FE51A 30 / loop...
  • Page 48 Model 5895XL Intelligent Power Module Installation and Operation Manual Table A-2: Compatible Two-Wire Smoke Detectors Model Name or Number Compatibility ID Manufacturer (Base model name or number in # per Loop Head Base parentheses.) 1100T 30 / loop 1100TB 30 / loop...
  • Page 49: Four-Wire Smoke Detectors

    2040-24 Power Supervision Unit Hochiki SIH-24F HS-224D or SHB-224 Base SLK-24F HS-224D Base SLK-23FH HS-224D Base System Sensor 1851B 2851/2851BTH DH200ADCD A.3.1 Door Holder Device The following UL listed door holder can be used with the 5895XL: ESL DHS-1224 151142 A-15...
  • Page 50: Silent Knight Fire Product Warranty And Return Policy

    UPS ground. • Return the Silent Knight product circuit board only. Products that are returned in cabinets will be charged an additional $50 to cover the extra shipping and handling costs over board only returns. Do not return batteries to Honeywell has the authority to determine if a product is repairable.
  • Page 51: Manufacturer Warranties And Limitation Of Liability

    • Repairs and returns should be sent to: Honeywell Fire Systems Attn: Repair Department / RA Number_______________________ 12 Clintonville Road Northford, CT 06472 USA Manufacturer Warranties and Limitation of Liability Manufacturer Warranties. Subject to the limitations set forth herein, Manufacturer warrants that the Products manufactured by it in its Northford, Connecticut facility and sold by it to its authorized Distributors shall be free, under normal use and service, from defects in material and workmanship for a period of thirty six months (36) months from the date of manufacture (effective Jan.
  • Page 54 Silent Knight 12 Clintonville Road Northford, CT 06472-1610 203-484-7161 Fax: 203-484-7118 www.silentknight.com...

Table of Contents