RECEIVING INFORMATION Shipping damage MUST be reported to the carrier IMMEDIATELY. Examine exterior. Remove cover and examine compressor and piping for signs of damage. General Information Installation shall be completed by qualifi ed agency. Retain this manual and warranty for future reference. Installer review this manual to verify unit has been installed correctly.
IMPORTANT SAFETY INFORMATION All fi eld wiring shall conform to requirements of authority Safety Information having jurisdiction or in absence of such requirements: • Installation by qualifi ed personnel. • United States - National Electrical Code, ANSI/NFPA 70 • Turn off electrical supply before servicing unit. •...
5 kW of supplemental heat. microprocessor monitors condensate pump safety switch and displays error code when fault occurs. (Only with Can be matched with EMI’s: optional condensate pump). • Single-zone condensing units — S1HV 09-24. • CEC (California Energy Commission) compliant.
Page 7
GENERAL PRODUCT INFORMATION Installation Considerations NOTICE • Determine best location for mounting unit for room air If excessive noise or vibration from unit mounted to circulation. masonry block wall, verify unit is plumb and level. If • Locate outdoor and indoor units as close together as noise or vibration persists, contact distributor.
UNIT MOUNTING Unit Mounting Instructions NOTICE Optimal unit location: • Locate unit in area with unrestricted air fl ow to the Do not install unit in location where curtains or space. drapes obstruct supply air grille. This may cause air •...
Page 9
UNIT MOUNTING Unit Mounting Instructions Figure 4 Ceiling Mounting WARNING Electrical shock hazard. Replace all panels after installation or servicing. Panels must remain on unit at all time while powered and in operation. Failure to do so could result in death or serious injury. Ceiling Mounting Threaded rods may be inserted through mounting holes to suspend unit from ceiling supports.
CONDENSATE PIPING UNHV is supplied with two ½" I.D. fl exible PVC hoses for Figure 6 Condensate Piping connection to copper or plastic condensate drain pipe work. • Each drain line is labeled and plugged at the factory. • Unplug appropriate line and connect to condensate drain.
REFRIGERANT PIPING Piping Preparation Figure 7 Refrigerant Connections • Avoid piping on wet and rainy days. • Use only clean, refrigeration-grade copper tubing. Suction line Liquid line Liquid line • Use tubing benders to guard against kinking. • Verify no burrs remain on fi ttings. •...
Page 12
REFRIGERANT PIPING Line Sizing Figure 8 Clean ends of tubing Size lines per Table 12, Page 39 . Match suction line size with condenser service valve connection. • When matching UNHV18 or 24 with 18,000 or 24,000-Btuh condenser, use 5/8" suction line, with reducer installed at indoor connection.
REFRIGERANT PROCESSING Refrigerant Processing Attach manifold set, vacuum pump, & Micron Gauge. See Figure 10. Evacuate line to 500 microns or less to insure all moisture has been removed and there are no leaks. See Figure 11. Evacuate B. Pressurize with 100psi N2 or Nitrogen C.
ELECTRICAL WIRING Site Preparation For Wiring Figure 14 Electrical Connections Electrical wiring must be in accordance with all electrical codes. In absence of such requirements to the National Electrical Code (NEC). WARNING Electrical shock hazard. Turn OFF electrical power supply before making electrical connections. Failure to do so could result in death or serious injury.
Page 16
ELECTRICAL WIRING High Voltage Electrical Wiring Figure 15 Remove Control Box Cover Screws Remove control box cover screws to access high To Access High Voltage Wiring voltage wiring compartment. See Figure 15 and Compartment Figure 16 Remove control box Refer to wiring diagram to connect power wire to Black cover screws L1 and Red L2 at power connector location.
Page 17
ELECTRICAL WIRING Units With Or Without Heat Figure 18 Unit-Mounted Controls — Cooling Only All low voltage interconnect wiring must be at least 18 AWG. Cooling Only Connection • Cooling only units utilize four (4) low voltage interconnecting wires between the indoor and outdoor units.
Page 18
ELECTRICAL WIRING Wired Wall Controller Heat Pump Applications • Heat pump operation requires connection of 2 RV termi- • Low voltage interconnect wiring must be at least nals between outdoor unit to indoor unit. See Figure 22, 18 AWG. Page 19 . Reversing valve is energized in cooling mode •...
CABINET RE-ASSEMBLY Re-Assemble Cabinet Figure 23 Replace (Tighten) Top, Bottom And Center Cabinet Screws Verify system is leak-free and all piping has been properly installed before reassembling cabinet. Loosen top screws See Figure 23 . Slide cabinet slotted holes over upper and lower cabinet screws.
CONDENSER OPERATION S1CV / S1HV IOM’s Sequence of Operation S1CV / S1HV Condenser Operation • EMI Series condensers are designed to operate with EMI • When indoor control is placed in Cooling Mode, with Series air handlers. set point temperature below room temperature, compressor, outdoor fan, and indoor blower energize.
Page 22
CONDENSER OPERATION • As temperature of indoor space moves closer to set point compressor, indoor, and outdoor motors adjust speeds to reduce rate of indoor temperature change and avoid passing set point. As temperature of indoor space moves farther from set point compressor, indoor, and outdoor motors adjust to increase rate of indoor temperature change and remain close to set point.
INITIAL START-UP Unit Operation is dependent on room temperature. It may Controller Operation be necessary to warm room before testing unit’s cooling • Controller operates unit in cooling, heating (when abilities. equipped) dry or auto changeover mode. Before Starting The Unit •...
UNHV CONTROLLER Figure 25 Hand Held Remote Operation Press to turn unit on or off. Press and hold for 2 seconds to transmit all settings to unit-mounted POWER controller Press to toggle through operating modes — MODE Cool, Heat, Auto changeover, Dry or Fan modes. Normal operation —...
WIRED WIRED WALL CONTROLLER Figure 26 Wired Wall Control Wired Wall Control Operation Wired Controller Button Selections POWER Press to turn unit on or off. MODE Press to toggle through operating modes — Cool, Dry, Fan, Heat or Auto Changeover Normal operation —...
Page 26
WIRED WIRED WALL CONTROLLER Table 6 7-Day Programming Options For CAHV Item Setting Values Overview To access: Press and hold PROGRAM and CLOCK buttons simultaneously for 3 seconds; use arrow keys to select position; save selection and exit by repeating the button press. Quick copy —...
SETTING THE CONTROLLER Table 7 Confi guration Mode For UNHV Air Handlers Possible Dis- Factory Item Value Overview play Settings (fl ashing) To access: Press MODE and PROG together for 5 seconds, repeat to exit; automatically exits after 20 seconds idle Fahrenheit Select temperature scale for display and operating Temperature...
Page 28
SETTING THE CONTROLLER Table 8 Programming Schedule (When Using 7-Day Programming) To copy the settings from any day to the entire week: 1) Select the day to be copied. 2) Simultaneously press the “FAN” and “PROG” buttons for three sec- onds.
HAND HELD CONTROLLER OPERATION When power is fi rst applied to control or after power outage Room Air Sampling there is three (3) minute delay before compressor or If room air sampling feature has been enabled in confi gu- electric heat will energize. Protects unit from short cycling ration, after the fan has been off for selected time, it will due to loss of power.
Page 30
HAND HELD CONTROLLER OPERATION Optional ELECTRIC HEAT Operation • Compressor starts, electric heat also energizes after 30 second delay, thus two-stage heating. (Non heat pump condenser units only and UNHV) For operation with electric heat only, control must fi rst be •...
Page 31
HAND HELD CONTROLLER OPERATION Pre-Programmed Run Mode • Fan operates continuously at low speed while in Dry mode. Feature allows setpoint temperature to be changed accord- ing to pre-programmed set point and time of day settings. • In order to prevent short cycling, there is 2 minute minimum on time for both cooling and heating.
WIRED WALL CONTROL OPERATION When power is fi rst applied to control or after power outage Place set-point temperature below room temperature. there is 3 minute delay before compressor or electric heat • Electric heater will switch off and indoor fan remains energize.
CONTROLLER FEATURES Short Cycle Protection (ASCT) Electronic control incorporates anti-short-cycle timer (ASCT) feature designed to protect compressor from short cycling. ASCT is activated immediately following off cycle of outdoor unit. Once room temperature is satisfi ed and outdoor unit switches Off, ASCT will not allow outdoor unit to restart until 3 minute time period has elapsed.
MAINTENANCE WARNING Figure 27 Remove The Front Grille Electrical shock hazard. Before removing access Grille screws panels, verify all power is disconnected from the unit. Failure to follow these instructions could result in death or serious injury. Have service performed by a qualifi ed service agency. Annual system check is recommended.
This is DC voltage, use proper scale on the meter. Wiring Requirements Electric heat applications EMI Ductless Series air handlers are designed to operate Units with electric heat utilize control relay located on air with EMI Ductless Series condensers. handlers control board in control box.
Page 37
Condensate pumps are recommended when it is not possible to gravity drain condensate from indoor unit. • EMI heat pump systems utilize a reversing valve is that is energized in the cooling mode. Maximum lift for pumps will vary. Consult pump •...
FREQUENTLY ASKED QUESTIONS Q: The condenser will not start although indoor unit appears normal. What should I do? A: Check Breaker Q: How long will the fan run? A: While the unit is in cooling or heating and auto fan mode is selected, Fan speed is determined by microproces- sor, speed adjustment is made according to room and set- point temperatures.
TEST UNIT PERFORMANCE DATA SHEET NOTICE Test Unit Performance Data sheet is provided for use by qualifi ed service professional in event there is concern with unit. For our Technical Service Department to better serve you, please complete. Have this information ready when calling. It is important to include Model Number, Serial Number, and Date of installation.
Need help?
Do you have a question about the UNHV09 and is the answer not in the manual?
Questions and answers