LonWorks. Switch 3 (SW3) on the board is used to set
protocol and baud rate. Switches 1 and 2 (SW1 and SW2)
are used to set the board's network address. See Fig. 62
and 63 for protocol switch settings and address switches.
The third party connection to the RTU Open controller is
through plug J19. See Fig. 64 for wiring.
PROTOCOL
DS8
BACnet MS/TP
Unused
(Master)
Modbus
Unused
(Slave)
N2
Unused
(Slave)
LonWorks
Unused
NOTE:
DS = Dip Switch
BACnet MS/TP SW3 example shown
Baud Rate Selections
BAUD RATE
9600
19,200
38,400
76,800
Fig. 63 − RTU Open Address Switches
Fig. 64 − Network Wiring
SW3 Protocol Selection
DS7
DS6
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
DS2
DS1
OFF
OFF
ON
OFF
OFF
ON
ON
ON
Fig. 62 − RTU Open SW3 Dip Switch Settings
C10815
C10816
NOTE: Power must be cycled after changing the SW1−3
switch settings.
Refer to the RTU Open v3 Integration Guide for more
detailed information on protocols, third party wiring, and
networking.
DS5
DS4
DS3
OFF
ON
OFF
ON
ON
OFF
OFF
ON
ON
OFF
ON
OFF

Local Access

Wall Mounted Equipment Toucht Interface
The Equipment Touch interface is a wall mounted
interface used to connect to the RTU Open controller to
access the control information, read sensor values, and
maintenance. This is an accessory interface that does not
come with the RTU Open controller. You wire the
Equipment Touch interface to the RTU Open controller's
J13 local access port. There are 2 password protected
levels in the display (User and Admin). See the
Equipment Touch Installation and Setup Guide for more
information. See Appendix A for navigation and screen
content.
Field Assistant
Field Assistant is a computer program included with the
purchase of the Tech Tool Kit (USB-TKIT). This is a field
Tech Tool to set-up, service, or download application
software to the RTU Open controller and includes a USB
Link Cable. The link cable connects a USB port to the J12
local access port. The Field Assistant's menu structure is
similar and functions the same as i−Vu
Fig. 65.
RTU Open Controller Troubleshooting —
Communication LEDs: The LEDs indicate if the
controller is speaking to the devices on the network. The
LEDs should reflect communication traffic based on the
baud rate set. The higher the baud rate the more solid the
LEDs will appear. See Table 14.