AHRI RJNL-B Installation Instructions Manual page 10

Package heat pumps featuring earth-friendly r410 refrigerant
Table of Contents

Advertisement

Model RJNL-Series
1
Cooling Performance
Gross Cooling Capacity Btu [kW]
2
EER/SEER
Nominal CFM/ARI Rated CFM [L/s]
ARI Net Cooling Capacity Btu [kW]
Net Sensible Capacity Btu [kW]
Net Latent Capacity Btu [kW]
3
IEER
Net System Power kW
Heating Performance (Heat Pumps)
High Temp. Btuh [kW] Rating
System Power KW / COP
Low Temp Btuh [kW] Rating
System Power KW / COP
Compressor
No./Type
5
Outdoor Sound Rating (dB)
Outdoor Coil—Fin Type
Tube Type
Tube Size in. [mm] OD
Face Area sq. ft. [sq. m]
Rows / FPI [FPcm]
Refrigerant Control
Indoor Coil—Fin Type
Tube Type
Tube Size in. [mm]
Face Area sq. ft. [sq. m]
Rows / FPI [FPcm]
Refrigerant Control
Drain Connection No./Size in. [mm]
Outdoor Fan—Type
No. Used/Diameter in. [mm]
Drive Type/No. Speeds
CFM [L/s]
No. Motors/HP
Motor RPM
Indoor Fan—Type
No. Used/Diameter in. [mm]
Drive Type/No. Speeds
No. Motors
Motor HP
Motor RPM
Motor Frame Size
Filter—Type
Furnished
(No.) Size Recommended in. [mm x mm x mm]
Refrigerant Charge Oz. [g]
Weights
Net Weights lbs. [kg]
Ship Weights lbs. [kg]
NOTES:
1. Cooling Performance is rated at 95° F ambient, 80° F entering dry bulb, 67° F entering wet bulb. Gross capacity does not include the effect of fan motor heat. AHRI capaci-
ty is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Units are certified in accordance with the Unitary Air Conditioner
Equipment certification program, which is based on AHRI Standard 210/240 or 360.
2. EER and/or SEER are rated at AHRI conditions and in accordance with DOE test procedures.
3. Integrated Part Load Value is rated in accordance with AHRI Standard 210/240 or 360. Units are rated at 80° F ambient, 80° F entering dry bulb, and 67° F entering wet
bulb at AHRI rated cfm.
4. Outdoor Sound Rating shown is tested in accordance with AHRI Standard 270.
10
B120DM/C120DM
B120YL/C120YL
125,000 [36.62]
125,000 [36.62]
11.1/NA
11/NA
4000/4000 [1888/1888]
4000/4000 [1888/1888]
120,000 [35.16]
120,000 [35.16]
91,600 [26.84]
91,600 [26.84]
28,400 [8.32]
28,400 [8.32]
11.6
11.6
10.91
10.91
109,000 [31.94]
109,000 [31.94]
9.39/3.4
9.39/3.4
69,000 [20.22]
69,000 [20.22]
8.79/2.3
8.79/2.3
1/Scroll
1/Scroll
88
88
Louvered
Louvered
Rifled
Rifled
0.375 [9.5]
0.375 [9.5]
28.8 [2.68]
28.8 [2.68]
2 / 22 [9]
2 / 22 [9]
TX Valves
TX Valves
Louvered
Louvered
Rifled
Rifled
0.375 [9.5]
0.375 [9.5]
15.75 [1.46]
15.75 [1.46]
4 / 15 [6]
4 / 15 [6]
TX Valves
TX Valves
1/1 [25.4]
1/1 [25.4]
Propeller
Propeller
2/24 [609.6]
2/24 [609.6]
Direct/1
Direct/1
8000 [3775]
8000 [3775]
2 at 1/2 HP
2 at 1/2 HP
1075
1075
FC Centrifugal
FC Centrifugal
1/15x15 [381x381]
1/15x15 [381x381]
Belt/Variable
Belt/Variable
1
1
3
2
1725
1725
56
56
Disposable
Disposable
Yes
Yes
(6)2x18x18 [51x457x457]
(3)2x18x18 [51x457x457]
(3)2x18x24 [51x457x610]
(3)2x18x24 [51x457x610]
496 [14062]
496 [14062]
1193 [541]
1185 [538]
1273 [577]
1265 [574]
B120YM/C120YM
125,000 [36.62]
11/NA
4000/4000 [1888/1888]
120,000 [35.16]
91,600 [26.84]
28,400 [8.32]
11.6
10.91
109,000 [31.94]
9.39/3.4
69,000 [20.22]
8.79/2.3
1/Scroll
88
Louvered
Rifled
0.375 [9.5]
28.8 [2.68]
2 / 22 [9]
TX Valves
Louveredd
Rifled
0.375 [9.5]
15.75 [1.46]
4 / 15 [6]
TX Valves
1/1 [25.4]
Propeller
2/24 [609.6]
Direct/1
8000 [3775]
2 at 1/2 HP
1075
FC Centrifugal
1/15x15 [381x381]
Belt/Variable
1
3
1725
56
Disposable
Yes
(3)2x18x18 [51x457x457]
(3)2x18x24 [51x457x610]
496 [14062]
1193 [541]
1273 [577]