PARAMETER TABLE FOR EM300(LX) with V/I & Pt100-TC input
PARAMETER
DESCRIPTION
ALARMS (folder with "rE1" label)
HA1 (!)
Higher ALarm. Maximum temperature alarm. Temperature value
(considered as absolute value) which if gone above triggers the alarm
signal.
Lower ALarm. Minimum temperature alarm. Temperature value
LA1 (!)
(considered as absolute value) which if gone below triggers the alarm
signal.
ALARMS (folder with "AL" label)
Alarm Fan differential. Alarm differential.
AFd
PAO (!)
Power-on Alarm Override. Alarm exclusion time after instrument
start-up, after a power failure.
Temperature Alarm Override. Temperature alarm signal delay
tAO
time.
tP
silences alarm using button
COMMUNICATION (folder with "Add" label) LX MODELS ONLY
LX
MODELS
LX
MODELS
SEE
EM300
T
SEE
EM300
T
ONL
ONL
Y
Y
SEE
SEE
EM300
EM300
T
T
V/I
V/I
MODELS
MODELS
ONL
ONL
NOTE 1: ndt parameter has range n/y/int int=whole numbers.
NOTE 2: LdL has range -99...HdL or -99.9...HdL or -999...HdL
according to ndt parameter setting HdL has range -LdL...100 or
-LdL...100.0 or -LdL...1000 according to ndt parameter setting
CONFIGURA
TION (folder with "CnF" label)
CONFIGURA
TION (folder with "CnF" label)
Selection of probe type
H00 (!)
H03
Minimum value of voltage / current input
H04
Maximum value of voltage / current input
rEL
Device version. Read only parameter.
Reserved. Read only parameter.
tAb
COPY CARD (folder with "Fpr" label)
LX
LX
MODELS
MODELS
SEE EM300 TABLE above
ONL
ONL
Y
Y
* DEFAULT column: for these parameters the default depends
on the model.
(!) CAUTION!
• If one or more parameters marked with (!) are modified, the device must be switched off after the modification and then switched back on
•PLEASE NOTE: We strongly recommend that you switch the instrument off and on again each time parameter configuration is changed in order to prevent malfunction-
ing of the configuration and/or ongoing timings.
EM300(LX)
LX
MODELS
ONL
LX
MODELS
ONL
LX
MODELS
ONL
LX
MODELS
ONL
ABLE above DISPLA
Y (folder with "
ABLE above DISPLA
Y (folder with "
ABLE above
ABLE above
Y:
Y:
LX
LX
MODELS
MODELS
R R A A N N G G E E ( ( V V / / I I ) )
Y
Y
LA1...150.0
-50.0...HA1
Y
Y
1.0...50.0
0...10
0...250
n/y
diS" label)
diS" label)
NOTE 3:
NOTE 3:
the dro parameter is
the dro parameter is
not present
not present
§§§
-99.0...100.0
(ndt= y)
-999...1000
(ndt= int)
as above
/
/
ONL
ONL
Y
Y
(§) Pt100/TC model
R R A A N N G G E E ( ( P P t t 1 1 0 0 0 0 ) )
DEFAULT*
VALUE**
LA1...1999
*
(§) 1200
-328...HA1
*
(§) -200
1.0...50.0
2.0
0...10
0
0...250
0
n/y
y
NOTE 3:
NOTE 3:
the dro
the dro
parameter is
parameter is
present
present
(§) Jtc/HtC/Pt1
(§) 2
not present
*
not present
*
/
/
/
/
§§§
010/05/01 for VOLTAGE INPUT
420/020 for CURRENT INPUT
U.M.
°C/°F
°C/°F
°C/°F
hours
min
flag
num
C/°F
C/°F
/
/
5/6