Other Printouts; Troubleshooting - Vector V4.1 Installation & Commissioning Manual

Table of Contents

Advertisement

Print options cont'd
4. PRINT DEVICE PARAMETERS. Prints device information in the form
This print will report all devices assigned to the panel selected.
With one option above chosen, select the required panel and loop number on the network by scroll-
ing the panel number from 00 to 15, and scrolling the loop number 1 - 4. The selection should default
to the local panel. Press button 5 to print . Press menu button to exit.

Other printouts

The printer will print all alarms and faults (if selected) in real time in the form:-
**********FIRE**********
FIRE PANEL 00
TYPE MAN
MANUAL CALL POINT TEXT MESSAGE HERE
Test mode . When test mode is used the printer will record the devices tested:-
TEST
TEST
Maintenance check. When this engineering mode is used, the printer will record devices with an ana-
log value above the threshold selected, They are printed as the display is manually scrolled.
Maintenance P00 OPT Ana 34
Maintenance P00 ION Ana 32
P00 refers to the panel number , Ana 34 refers to the analog value returned by the device.

Troubleshooting

The printer will not print :- is there paper available, is the printer address correct. Are dil switch op-
Comms disconnected:-
'Printer supply' led out:-
Vector printer
Installation and Commissioning Manual.
001 OPT
address type
SMOKE DETECTOR GROUND FLOOR
text message.
LOOP 01
ZONE 04
ADDRESS 020
ADD 020 MAN ZONE 04 22:43 04/01
ADD 019 OPT ZONE 04 22:41 04/01
tions set correctly. Is panel V4.0 or above, is paper correctly installed.?
(i.e. coating upwards).
Is PCB connected correctly.
Check supply fuse
ZONE 01 G****
zone
22:48 04/01
groups