Initial Power Up
With power applied the
FAULT LED will flash
quickly to indicate the
software version then flash
more slowly(once per
second) during warm up
(60 Seconds). Warm up
can be bypassed by
pressing either button. In
normal operation the
FAULT LED will be off.
Addressable Operation After Warm Up
After warm up the fault LED
should be off AND ZERO led on.
If valid serial commands are
received by the 103P then the
ZERO LED will flash as
commands are transmitted.
Setting Pellistor Head Current
Press and hold the UP button
until the 360 LED is illuminated.
Release the button and the LED
will flash.
180.0
T106P V2
Set Address
UP
0V
T106P V2
Set Address
UP
0V
T106P V2
Set Address
UP
0V
mV
Page 6 of 9
OLIVER
TOCSIN 106P
U N I V E R S A L P E L L I S T O R
D R I V E P C B
A N A L O G U E O R
A D D R E S S A B L E O U T P U T
CHASS
+24V
B
4101
A
GND
mA
DOWN
360
mA-
mA+
CHASS
+24V
B
4101
A
GND
mA
DOWN
360
mA-
mA+
CHASS
+24V
B
4101
With the LED flashing connect a
A
GND
multimeter as indicated to read the
mA
pellistor head current. Note the meter
DOWN
will read half the head drive current.
Use the UP - DOWN buttons to
increase or decrease the set point.
360
mA-
mA+
(Fault LED flashes on every button
press.)
For MK3 and MK5 IGD pellistors
set to 180mV.+/- 2mV.
For MK6 and Type B IGD Pellistors
set to 85mV +/-3mV
Note the preset head operating point
will be indicated on the 106 label
Press and hold either button until the
LED goes off to return to normal
operation.