Installation Premises; Discharge Of Flue Gases - Kelvinator KHG950SS2 User And Installation Instructions Manual

Table of Contents

Advertisement

Installation premises

For proper operation of a gas appliance, the air necessary for the combustion of the
gas must be able to flow into the room naturally. The air must flow into the room
directly through openings in the outside walls. These openings must have an
3
unobstructed cross-section must be no less than 2m
/hfor each kw of power(see total
power in kw on the appliance nameplate).
This opening must be constructed so that it will not be
obstructed from indoors or out and placed close to the floor,
preferably on the side opposite to that on which the flue
gases are discharged. If it is not feasible to provide these
openings in the room where the appliance is installed. The
necessary air may be taken from an adjacent room,
provided that:
·this room is not a bedroom or a hazardous environment;
·this room is not in a vacuum;
·the ventilation between the room where the appliance is
installed and the adjacent room is guaranteed by permanent
openings.

Discharge of flue gases

Gas cooking appliances must discharge their flue gases
through hoods connected directly to flues or the outdoors.
If it is not possible to install the hood ( fig. B) an electric
fan must be installed on the outside wall or the window of
the room, provided it is possible for the ventilation opening
to be increased in proportion to the delivery rate of the fan (fig. C). For a kitchen, the
delivery rate of this electric fan must guarantee an hourly air exchange of 3-5 times
its volume. In both instances, the use of flues already used by other appliances to
discharge the flue gases is forbidden.
11

Advertisement

Table of Contents
loading

This manual is also suitable for:

Khg640ss2

Table of Contents