Module Specifications - GE IC670ALG620 Datasheet

Rtd 4 channel isolated 3 or 4 wire input
Table of Contents

Advertisement

Analog Input Module
RTD Input Module

Module Specifications

Module Characteristics
Number of Channels
Scan time
Fault detection
Normal mode rejection
Common mode rejection
Common mode voltage
Normal mode voltage
Isolation:
User input to logic, user input to frame
ground.
Channel to Channel
Current drawn from BIU power supply
Digital Resolution
Operating temperature range
Channel Characteristics
RTD types
Resistance ranges
Accuracy , at 25 C
Temperature sensitivity (0 to 60C)
Maximum lead resistance
Keying Locations
Optional keying locations for the RTD Module are:
Four 3-wire and/or 4-wire RTDs
60 Hz: approximately 210 milliseconds per point
50 Hz: approximately 230 milliseconds per point,
Open RTD, input short, underrange, overrange, and high/low alarm
60dB, at 50/60 Hz, 100% span
120 dB at 50/60Hz, 100 ohm imbalance
250 Vrms (350 VDC or peak AC)
100% overrange DC or peak AC operational
28 VDC or peak AC maximum
1500 VAC for 1 minute, 250 VAC continuous.
250 VAC continuous.
190 mA maximum
15 bits plus sign
0 to 55 Degrees C ambient
10, 25, 100, and 1000 ohm platinum
10 and 100 ohm copper
100, 50, and 120 ohm nickel
604 ohms and 1000 ohms nickel/iron
0 to 500 ohms
0 to 3000 ohms
RTD: +/–0.15% of reading, +/–0.3 to 0.5 degree Celsius, depending
on type
+/–0.004% of reading, +/–1.5µV per C referred to input
5 ohms per lead