Vent Pipe Material; Vent Pipe Length & Diameter - Nordyne *TC Installation Instructions Manual

Two-stage condensing gas furnaces with fixed & variable speed blowers
Table of Contents

Advertisement

For 1- pipe installations, install vent piping as described in
this section and provide air for combustion and ventilation
according to pages 7 - 10. Table 2 contains the maximum
length of vent and combustion air piping for either type
of installation.
Category IV appliances operate with positive vent pressure
and therefore require vent systems which are thoroughly
sealed. They also produce liquid condensate, which is
slightly acidic and can cause severe corrosion of ordinary
venting materials. Furnace operation can be adversely
affected by restrictive vent and combustion air piping.
The inducer assembly on this furnace can be rotated to
vent the flue products out of the left or right side of the
furnace. This increases the flexibility of which direction
the vent pipe can exit the furnace.
In Canada, all plastic vent pipes and fittings including
any cement, cleaners, or primers must be certified as a
system to ULC S636. However this requirement does not
apply to the finish flanges or piping internal to the furnace.
Vent Pipe Length & Diameter
In order for the furnace to operate properly, the combustion
air and vent piping must not be excessively restrictive.
• The venting system should be designed to have the
minimum number of elbows or turns.
• All horizontal runs must slope upwards from the furnace
at 1/4 inch minimum per running foot of vent.
• Transition to the final vent diameter should be done as
close to the furnace outlet as practical.
• Always use the same size or a larger pipe for combustion
air that is used for the exhaust vent.
Vent Pipe Material
Vent and combustion air pipe and fittings must be one of
the following materials in the list and must conform to the
indicated ANSl/ASTM standards. Cement must conform
to ASTM Standard D2564 for PVC and Standard D2235
for ABS. PVC primer must meet standard ASTM F656.
When joining PVC piping to ABS, use PVC solvent cement.
(See procedure specified in ASTM Standard D3138)
Materials
Standards
Schedule 40PVC ..............................
D1785
PVC-DWV ..........................................
D2665
SDR-21 & SDR-26 ............................. D2241
ABS-DWV ..........................................
D2661
Schedule 40 ABS ............................... F628
Foam/Cellular Core PVC .................... F891
Table 2 indicates the maximum allowable pipe length for
a furnace of known input rate, when installed with piping
of selected diameter and number of elbows. To use the
table, the furnace input rate, the centerline length and the
number of elbows on each pipe must be known.
When estimating the length of vent runs, consideration
must be made to the effect of elbows and other fittings.
This is conveniently handled using the idea of "equivalent
length". This means the fittings are assigned a linear
length that accounts for the pressure drop they will cause.
For example: a 2" diameter, long radius elbow is worth
the equivalent of 2.5 feet of linear run. A 90 degree tee
is worth 7 ft.
The equivalent lengths of tees and various elbows are
listed in Table 2. Measure the linear length of the vent run
'-
:
'
_
'
D_E
LENGTH (ft._
FURNACE
FURt,_^t'E.,
,.,,.,
'
_
_
_,,ith 1 long radius elb,',w**
with 1 long radius elbow on each pipe**
MODELS
, .....
iNSTALLATION
OUTLET
OUTLET
NLET t OUTLET
INLET/OUTLET
z" ulamel:er
_" ulamel:er
z" ulamel:er
3" Diameter
Upflow
90
90
90
90
60,000
Horizontal
50
90
50
90
Downflow
30
90
30
90
,
Upflow'
90
.
90
90
I
90
80,000
Horizontal
'
30
'
90
'
30
9O
I
I
I
I
Downflow
30
90
30
90
100,000
1201000
Upflow
60
90
Horizontal
30
90
Downflow
30
90
Horizontal
I
N/A
'
90
60
90
30
90
25
90
N/A
90
Downflow
"
N/A
"
90
" N/A
:
90
*NOTES:
1. Subtract 2.5 ft. for each additional 2 inch long radius elbow, 5 ft. for each additional 2 inch short radius elbow, 3.5 ft. for each additional 3
inch long radius elbow, and 7 ft. for each additional 3 inch short radius elbow. Subtract 5 ft for each 2" tee and 8 ft for each 3" tee. Two 45
degree elbows are equivalent to one 90 degree elbow.
2. This table applies for elevations from sea level to 2,000 ft. For higher elevations, decrease pipe lengths by 8% per 1,000 ft of altitude.
Table 2. Vent Pipe Lengths
11

Advertisement

Table of Contents
loading

This manual is also suitable for:

*tl

Table of Contents