H series online UPS LCD 1-3KS/L ’ ’ ’ PDF 文件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn...
Page 2
The address of service center has been detailed on the warranty card. Note: POCASA reserves the right to make changes to product described in this manual at any time and without notice for reasons of improvement.
Contents 1. Brief introduction-------------------------------------------------------------------------------------------------------------------4 1.1. Technology introduction-----------------------------------------------------------------------------------------------------4 1.2. System and model description--------------------------------------------------------------------------------------------5 1.3. Description of commonly used symbols---------------------------------------------------------------------------------5 1.4. Appearance--------------------------------------------------------------------------------------------------------------------6 1.5. Product specification and performance---------------------------------------------------------------------------------8 2. Installation----------------------------------------------------------------------------------------------------------------------------8 2.1. Unpacking and inspection--------------------------------------------------------------------------------------------------9 2.2. Safety notes--------------------------------------------------------------------------------------------------------------------9 2.3. The description of front panel and display lamp---------------------------------------------------------------------10 2.4.
1. Brief introduction 1.1. Technology introduction ● This UPS is a sophisticated piece of equipment with 16 bit Microprocessor and advanced software programming technology, high frequency SPWM is created to control the inverter of UPS. This simplifies the control circuit, enhances the stability of UPS, also enables the UPS to have enhanced real-time performance that makes UPS respond the variety of external environment rapidly and insure that the control circuit is compact and reliable.
This manual is applicable to the following models: 1) H1KS, H2KS, H3KS are standard models with inbuilt battery. 2) H1KL, H2KL, H3KL are long backup time models, which are able to connect with the external battery bank.
Turn off the UPS Idle or shut down the UPS Alternating current source(AC) Direct current source(DC) Protective ground Alarm silence Overload indication Battery check Recyclable Do not dispose with ordinary trash 1.4. Appearance Front display panel PDF 文件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn...
H2/3KL rear panel 1.5. Product specification and performance 1.5.1. General specification (standard models) Model H1KS(L) H2KS(L) H3KS(L) Voltage 220VAC Input Frequency 46Hz-54Hz/56Hz-64Hz Amperage(maximum) Power rating 1KVA/0.7KW 2KVA/1.4KW 3KVA/2.1KW Output Voltage 220VAC (±2%) Frequency 50/60Hz±0.2 Batteries Number and type 3*12V7AH/None 8*12V7AH/None 8*12V7AH/None 1.5.2.
2.1. Unpacking and inspection 1). When unpacking the UPS, please pay attention to the packing mode and the annex in which includes user-manual, warranty card, input power cable, output wiring socket. There should also have an external battery connection cable if the model of your equipment is of long backup type. 2).
2.3. The description of front panel and display lamp Description of the front panel LCD panel section ● The first line is the numeric section, and is consisted of two small numeric sections and the related unit section on the right side. It is used to display the numerical value of the certain item on the second line. ●...
When you press and hold the button for some time again, it will turn to static output status. 2.4. UPS input connection When connect power cable, please use suitable socket with over-current protection. The rating for H1KS(L) should be above 6A, for H2KS(L) should be above 12A, for H3KS(L) should be above 16A.
UPS input connection 2.5. UPS output connection 1). Output of H1KS(L) use socket only, please directly plug the load cable into the output socket. 2). Output of H2KS(L) and H3KS(L) not only provide socket but also offer high-currency output wiring socket, which make output wiring become easy.
UPS output connection 2.6. External battery connection 1). Choose correct battery voltage according to the model The batteries can't be more or less connected, otherwise UPS will work abnormal or be damaged. Battery voltage for H1KL is 36VDC; for H2KL is 96VDC; for H3KL is 96VDC. 2).
A. First connect battery group in series and ensure correct battery voltage. B. Extended battery cable must be connected to battery first (do not connect to UPS first; otherwise there will be danger of (electric shock). Red cable connect with battery anode “+” and black cable connect with cathode”...
on front panel. 3.1.5. UPS self-test/mute test operation 1). When UPS is on utility mode, press and hold the FUNCTION button for 1 second, the buzzer will sound once every 4 seconds, the LED lights light around at the same time as the UPS runs self-testing, and it will last for 10 seconds.
Page 16
Utility mode Green LED is on, LCD status figure shows block "LINE" and "BATTERY" and "INV". 1). If the INPUT letters in the item section (the second row on LCD display) flashes, it indicates the line and neutral are incorrect. 2).
Page 17
3). You can test UPS back up function by disconnecting the utility. 4). If the INPUT letters in the item section (the second row on LCD display) flashes, it means the input voltage or frequency is beyond the extension. 3.2.3. Fault mode The front panel indication and display is as following: Fault mode Red LED is on.
Page 18
3.2.5. Communication port Intelligent slot This series is equipped with an intelligent slot for web power (optional accessory) or other optional card to achieve remote management of the UPS through internet/intranet. Please contact your local distributor for further information, RS232 Interface The following are the descriptions and pin assignment of RS232 DB-9 port: Baud rate: 2400bps Data bit: 8 bit...
Page 19
The following are the pin assignment and the descriptions of AS400 card: PIN1:UPS failure (normally open, active close) PIN2:Summary PIN3:Ground PIN4:Remote shutdown PIN5:Common PIN6:Bypass active (relay close) PIN7:Battery low PIN8:UPS On (relay close) PIN9:Utility Power failure (normally open, active close) AS400 Interface 3.2.6.
4. Notes for battery disposal and battery replacement ● The battery of standard unit is of valve regulated, maintenance free. It can attain expectant life only by keeping frequent charging. Regardless of UPS on or off when UPS connects to utility power, the battery is charged all the time and UPS offers protection for over-charge and over-discharge.
7. Batteries contain hazardous voltage and current. Battery maintenance such as the battery replacement must be carried out by qualified personnel who are knowledgeable about batteries. No other persons should handle the batteries. 5. Troubles shooting The following messages are the messages that users would find on UPS when it meets some problem, with the use of such messages, users can know where the problems are and how to deal with such problems.
Page 22
When you contact the service center, please provide the following information: ● Model No. and the serial No. of the UPS; ● The date when the problem arose; ● Complete description of the problem, including the LED display, alarm warning, and power condition and load capacity.
information. Appendix: EMC grade standards H series UPS are manufactured according to the following: EMC international grade standard: PDF 文件使用 "pdfFactory Pro" 试用版本创建 www.fineprint.cn...