Download Print this page
B.E.G. luxomat PD2-M-2C-11-48V Installation And Operating Instructions

B.E.G. luxomat PD2-M-2C-11-48V Installation And Operating Instructions

Occupancy detector

Advertisement

Quick Links

LUXOMAT
Installation and Operating Instruction for B.E.G. - occupancy detector PD2-M-2C-11-48V-3A-SM/-FC and PD2-M-2C-11-48V-RR-SM/-FC
1. Mounting preparation
Work on the 230 V mains supply may only be carried out by
qualified professionals or by instructed persons under the direc-
tion and supervision of qualified skilled electrical personnel in
accordance with electrical regulations.
Disconnect supply before installing!
The device is not suited for safe disconnection of the mains
supply.
When in Master/Slave mode of operation, the Master-
appliance must always be installed at the location where there
is least daylight.
3a. Hardware configuration SM
Position LED's
40
LED 1 green
LED 2 red
LED 3 white
4a. Position potentiometers and DIP-Switches SM
Potentiometer 3
Potentiometer 2
Potentiometer 1
1
40
OFF
VA
Surface mounting
LED
DIP 1
Fully automatic/semi automatic mode
DIP 2
LED ON/OFF
DIP 3
Change between corridor mode and standard mode
The DIP switch settings are
using the remote control.
overriden
5. DIP-Switch functions
DIP-
ON
switch
1
Semi automatic mode
2
LED OFF
3
Corridor mode
DIP
1 2 3
OFF
ON
®
2a. Installation LUXOMAT
Having connected up the wires in accordance with regula-
tions, secure the detector with 2 screws as per the illustration
above. In order to assemble the detector outside, the PD2-IP54
base-plate, which is available as an accessory, must be
mounted between the detector and the surface on which it is
to be installed.
3b. Hardware configuration FC
Position LED's and potentiometer
LED 1 green
1 2
3
LED 2 white
LED 3 red
4b. Position DIP-Switches FC
Time Channel 2
Time Channel 1
Lux Channel 1
2
3
ON
OFF
ON
HA
DIP
COR
DIP 1
DIP 2
DIP 3
The DIP switch settings are
Corridor function: After deactivation by an external push
OFF
button, the detector switches off and returns to automatic mode
after 5 sec.
Fully automatic mode
The DIP settings are enabled again by:
LED ON
• Adjusting the DIP switches when closed
Standard mode
• Reset with test sun setting at the potentiometers
• Reset when open
PD2-M-2C-11-48V
®
PD2-M-2C-11-48V-SM
The detector must be installed on a solid
and level surface. There is no need for
frames.
For mounting remove lens (turn anticlock-
wise). Fasten the mounting pod to the
ceiling.
2
1
3
1
2
3
Potentiometer 1
Lux Channel 1
Potentiometers 2
Time Channel 1
Potentiometers 3
Time Channel 2
1
2
False ceiling
mounting
Fully automatic/semi automatic mode
LED ON/OFF
Change between corridor mode and standard mode
overriden
using the remote control.
2b. Installation LUXOMAT
Having connected up the cables in accordance with regula-
tions, the detector is inserted into the opening as shown in the
drawing opposite and fixed into position with the assistance
of the spring clip.
120 60 50
A
40
30
15
5
10
6. Putting into operation / Settings
16 10
5
Self test cycle
2
After an initial 60-second self-test cycle, the LUXOMAT
1
TEST
30
15
PD2-M-2C-11-48V is ready for operation.
Potentiometer 1 - Adjustment twilight-switch for
2000
channel 1
1200
600
The switch-on value for the light can be set at
200
between 10 and 2000 Lux. Using the potenti-
40
ometer, the luminance set points can be set as
desired.
Symbol :
Symbol
:
Determining the current brightness
Set potentiometer 2 to the „Test" setting. The
120 60 50
green LED lights up permanently as soon as
A
40
the value set at the potentiometer "Lux" dropps
30
15
below the current measured brightness.
5
10
Potentiometer 2 - Adjustment follow-up time
16 10
channel 1 "Light"
5
2
Symbol TEST: Test mode, reacts on motion only.
1
TEST
Every movement switches on the light for a pe-
30
15
riod of 2 seconds, switching it off for a period
of 2 seconds. The time can be set infinitely vari-
2000
ably at between 15 sec. and 16 minutes.
1200
600
The potentiometer settings are overriden using the remote
200
40
control.
Potentiometer 3 - Follow-up time for appliance-
3
120 60 50
A
control
DIP
40
30
The time can be set infinitely variably at between
15
5
10
5 minutes and 120 minutes. After 15 minutes
OFF
the switch-on delay is activated. This is around
5 min. If there are not detected any further
16 10
5
ON
movements within this period, the switch-on delay
2
starts again.
1
TEST
30
15
Symbol
:
Symbol A:
2000
1200
Alarm impulse
600
In order to set off an alarm impulse, at least 3
200
40
movements within 9 sec. have to be detected.
EN
PD2-M-2C-11-48V-FC
®
A circular opening of diameter
68 mm must first of all be pro-
duced in the ceiling.
®
Night operation
Day/Night operation
Impulse = 2.5 sec.
Alarm impulse = 2 sec.

Advertisement

loading

Summary of Contents for B.E.G. luxomat PD2-M-2C-11-48V

  • Page 1 PD2-M-2C-11-48V LUXOMAT ® Installation and Operating Instruction for B.E.G. - occupancy detector PD2-M-2C-11-48V-3A-SM/-FC and PD2-M-2C-11-48V-RR-SM/-FC 1. Mounting preparation 2a. Installation LUXOMAT ® PD2-M-2C-11-48V-SM 2b. Installation LUXOMAT PD2-M-2C-11-48V-FC ® Work on the 230 V mains supply may only be carried out by The detector must be installed on a solid A circular opening of diameter qualified professionals or by instructed persons under the direc-...
  • Page 2 120 60 50 16 10 7. Reset and default settings Option: Remote control IR-PD-2C 8. Putting into operation of the remote control IR-PD-2C (optional) TEST 1. Default settings If the potentiometers are in the 16 10 2000 Check Battery: B.E.G. 1200 B.E.G.
  • Page 3 11. Explanation of the remote control button 13. Switch-off threshold brightness 16. Fully automatic and semi automatic mode functions (see functions IR-PD-2C) 1. If the switch-on threshold has been modified by the poten- tiometer or remote control, the switch-off threshold stored 11a.
  • Page 4: Wiring Diagram

    19. Technical data PD2-Master-2C-11-48V 21. Wiring diagram 22a. PD2-M-2C-11-48V-SM – Connections Sensor and power supply in one case Standard operation with Master-2 channels-11-48 V-detector Power supply: 11-48 VAC/DC ~/– Power consumption: < 1W  11-48V Ambient temperature: -25°C to +50°C ...