DIN left or DIN right (right-/left-handed opening) The operating instructions are handed over together with the sliding door driving mechanism. They serve as sup- S 3000 one-wing porting material for the user in case of questions as to S 3000 two-wing the professional use and as a basis for the mechanic on ...
(optional) 2.5 Terminal 2.5.4 Parameter settings The parameters are preset at works according to your requirements and to the relevant standards. Parameter modifications must only be carried out by authorised staff. Improper modifications of the pa- rameter values will exclude any liability of the manufac- turer for damages resulting therefrom.
Example: PS mode >Closing time< >Display after pressing <+> key Use the <E> key to acknowledge the selected pa- >Standard display, PS inactive< rameter. (Use the <P> key to abort the process) Parameter 61 = select 1. >Display of the current p arameter value< >Display PS mode <...
2.6 Technical data 4.0 Assembly Supply voltage: 230V~ 50/60Hz Only authorized technical staff is allowed to carry out the assembly of the driving mechanism. The compulsory in- (optional) 120V~ 50/60Hz struction on our premises is the basis for proper assem- ...
External interlocking fucntion (K1/LOC [10,11/12,13] ) 5.3 Fault clearance during putting into opera- tion procedure module 3 A mutual interlocking with an external door is possible. If a fault occurs, all previous technical modifications will As soon as one door is open/opened, the locking moni- have to be checked.
7.0 Maintenance / Safety check According to the professional association direc- A due safety check of the S 3000 is indicated by the yel- tives BGR 232, power-operated windows, doors and low LED at the motor unit and/or the terminal. The gates must be checked for safe operation before their maximum checking interval is 12 months .
9.0 Parameters 9.1 Parameter list Terminal / RS232 Designation Designation Designati on Designation W orks min. max. Unit Works setting min. max. Terminal RS232 Terminal RS232 setting T ime PARTLY Time PARTLY 51 Special function Special function OPEN OPEN Time Time COMPLETELY Teach-in run with- Teach-in run with-...
9.2 Explanations regarding parameter list Time The time the door remains in OPEN position; unit seconds. Width The width is the travel path of the door from CLOSE position to OPEN position; unit millimeters. Running-in zone The driving unit has two running-in zones – one before reaching the CLOSE position and one before reaching the OPEN position.
Page 11
In case in any change in speed, a new teach-in run must be carried out ! Travelling speed in OPEN direction. The parameter value should be between 100 and 150. This Parameter 21 : means a speed of approx. 520 mm/s, depending on the door weight. In case of any change in speed, a new teach-in run must be carried out! Parameter 22 : Travelling speed in CLOSE direction.
Page 12
Parameter 51: Special functions: special input SI 0 – no function 1 – input (NO contact) SI activated – emergency opening in case of interlocking; door OPENS and remains in this position, until SI is deactivated. This opening of the door is indicated by an acoustic signal.
Page 13
Parameter 77 Activation lock time closing time 2 0 – normal mode 1 – closing time mode Parameter 78 Activation lock time closing time 3 0 – normal mode 1 – closing time mode Example : The motion sensor Outside is locked from 6 p.m. until 8 a.m. 1.