Connecting Sensors - Viessmann VITOLIGNO 300-P Installation Instructions Manual

Table of Contents

Advertisement

Making the electrical connections

Connecting sensors

Note
Check existing hydraulic components (see service instructions, chapter "Matching
the control unit to the heating system") and assign slots accordingly.
1
9
1 2 3
1 2
A
B
A Outside temperature sensor
B Buffer cylinder temperature sensor,
top
C Buffer cylinder temperature sensor,
bottom
D Cylinder temperature sensor
E Flow temperature sensor M1
Installation point for outside temper-
ature sensor
■ North or north-western wall, 2 to
2.5 m above ground level; in multi-
storey buildings, in the upper half of
the second floor
■ Not above windows, doors or ventila-
tion outlets
14
(cont.)
M1
9
5
1 2
1 2
1 2
C
D
F Cylinder temperature sensor (in
conjunction with a solar thermal sys-
tem)
G Collector temperature sensor (in
conjunction with a solar thermal sys-
tem)
■ Not immediately below balconies or
gutters
■ Never render over
Outside temperature sensor connec-
tion
2-core lead, up to 35 m long with a cross-
section of 1.5 mm
So
So6
2
5
2/6
1 2
1 2
E
F
2
G