T8602C CHRONOTHERM®IVDELUXE PROGRAMMABLE THERMOSTATS
Installer Setup
Number (Press
Time A key to
Select
change)
Not Used.
1 thru 3
Heating cycle
rate.
Not Used.
5 thru 12
Adaptive
Intelligent
Recovery™
control.
Degree
temperature
display
Not Used.
Clock format.
Not Used.
17 thru 23
Outdoor
temperature
display (models
with OT
terminals).
Not Used.
25 thru 32
Minimum off
time for the
compressor.
Temperature
range stops in
heating.
Temperature
range stops in
cooling.
Not Used.
69-1670
Table 3. Thermostat Installer Setup Options.
Factory Setting
Display
4
6
6—6 cph used for
conventional heat
13
0
Adaptive Intelligent
Recovery™
control is activated
(system starts
early so setpoint is
reached by start of
program period).
14
0
Temperature is
displayed in °F
15
16
0
12-hour clock
format.
24
0
No outdoor
temperature is
displayed.
33
5
5 minute minimum
off time for the
compressor.
34
90
Highest heating
setpoint setting.
35
45
Lowest cooling
setpoint setting.
36
(Press A or ▼ key to change)
Description
Display
1,3 or 9 1— 1 cph used for radiant
1
1
1
1
0 thru 4
40 to 89
46 to 99
6
Other Choices
Description
floor heat, gravity system
3— 3 cph used for hot water
systems or high
efficiency furnaces
9— 9 cph used for electric
heat systems
Conventional recovery
(system starts recovery at
programmed time).
Temperature is displayed
in °C
24-hour clock format.
Outdoor temperature is
displayed. Needs a
C7089B1000 Outdoor
Temperature Sensor to
operate.
Minimum number of minutes
(0 thru 5) the compressor is
off between calls for the
compressor.
Temperature range (1°F
increments) of heating
setpoint settings.
Temperature range (1°F
increments) of cooling
setpoint settings.
Actual
Setting