Manual Transfer To Bypass - IPM balancedpower plus Installation And Operation Manual

10-300 kva
Table of Contents

Advertisement

3.6 UPS Operating Procedures (continued)
3.6.3
3.6.3.3
10. This message indicates that the
Maintenance Bypass Shutdown procedure is
complete.
11. You may turn off the UPS CONTROL
switch. This message appears briefly.

Manual Transfer to Bypass

12. Press
and
13. Press
to obtain this screen.
14. Press
to manually transfer input to
reserve power source. This will inhibit retransfer
and light the Transferred to Bypass and
Retransfer Inhibited LED's. It will also change
the "Inv Running" on the screen to "Wait Rexfr."
BP+2.9X
11/95
UPS Maintenance Menu (continued)
SBS Maintenance Menu (continued)
to obtain this screen.
Page 3.31
SECTION III
Operation
Bypass/
Shutdown
Complete
You may
turn off
UPS control
Man Transfer
/Retransfer
Inv Running
Confirm
Yes=UP No=DN
Man Transfer
/Retransfer
Inv Running