Heat - Panasonic WH-UD09HE5-1 Operating Instructions Manual

Air-to-water hydromodule + tank
Hide thumbs Also See for WH-UD09HE5-1:
Table of Contents

Advertisement

Available languages

Available languages

Menus
For installer
Menu
6.1

Heat

To set various water & ambient
temperatures for heating.
16
Default Setting
Setting Options / Display
Water temp. for heating ON /
Outdoor temp. for heating OFF /
T for heating ON /
Outdoor temp. for heater ON
Water temp. for heating ON
Heating ON
temperatures in
Compensation curve
compensation curve
or direct input.
Water temp. for heating ON Compensation curve
Input the 4
temperature points
X axis: -5 °C, 15 °C
(2 on horizontal X
Y axis: 55 °C, 35 °C
axis, 2 on vertical Y
axis).
• Temperature range: X axis: -15 °C ~ 15 °C, Y axis: See below
• Temperature range for the Y axis input:
1. If High water temperature is NO: 20 °C ~ 55 °C
2. If High water temperature is YES & Back up heater is enabled: 25 °C ~ 65 °C
3. If High water temperature is YES & Back up heater is disabled: 35 °C ~ 65 °C
4. If connected outdoor is FLAT model: 20 °C ~ 60 °C
• If 2 zone system is selected, the 4 temperature points must also be input for Zone
2.
• "Zone 1" and "Zone 2" will not appear on the display if only 1 zone system.
Water temp. for heating ON Direct
Temperature for
35 °C
heating ON
• Min. ~ Max. range is conditional as follows:
1. If High water temperature is NO: 20 °C ~ 55 °C
2. If High water temperature is YES & Back up heater is enabled: 25 °C ~ 65 °C
3. If High water temperature is YES & Back up heater is disabled: 35 °C ~ 65 °C
4. If connected outdoor is FLAT model: 20 °C ~ 60 °C
Outdoor temp. for heating OFF
Temperature for
24 °C
heating OFF