7.12 Fault finding Installation Page Delivery Contents Wiring diagrams Page Unpacking Important note Preparation for mounting Installation of Vokera time clock Fitting the flue External controls Connecting the gas & water Condensate outlet Electrical connections Exploded diagrams Page Table 1 Commissioning...
Page 3
INTRODUCTION The Vokera Eclipse 216 ESS & 226 ESS are central combustion air intake that can be rotated – horizontally – heating condensing boilers, which - by design - through 360 degrees for various horizontal or vertical incorporates full sequence electronic ignition, circulating applications.
SECTION 1 DESIGN PRINCIPLES AND OPERATING SEQUENCE PRINCIPLE COMPONENTS SAFETY DEVICES When the appliance is in use, safe operation is A fully integrated electronic control board ensured by: featuring electronic temperature control, a high limit thermostat that interrupts the continuous air/gas modulation, anti-cycle operation of the burner;...
2.12 PUMP DUTY Fig. 3 shows the flow rate available – after allowing for pressure loss through the appliance – for system requirements. When using this graph apply only the pressure loss of the system. The graph is based on 20°C temperature differential. 0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 Litres Per Hour (x100)
BS 5440 PART 1 FLUES BS 5440 PART 2 FLUES AND VENTILATION BS 5449 PART 1 FORCED CIRCULATION HOT WATER SYSTEMS BS 6798 INSTALLATION OF BOILERS OF RATED INPUT NOT EXCEEDING 60kW BS 6891 LOW PRESSURE INSTALLATION PIPES BS 7074 PART 1 APPLICATION, SELECTION, AND INSTALLATION OF EXPANSION VESSELS AND ANCILLARY EQUIPMENT FOR SEALED WATER SYSTEMS AIR SUPPLY...
litres of expansion from within the system, generally ELECTRICAL SUPPLY this is sufficient, however if the system has an The appliance is supplied for operation on 230V unusually high water content, it may be necessary @ 50Hz electrical supply, it must be protected to provide additional expansion capacity (see 6.19).
The top flue outlet permits both horizontal and Fig. 7 vertical flue applications to be considered, alternatively, the Vokera twin flue system can be Take the large black gasket - supplied with the utilised if longer flue runs are required.
Page 10
NOTE Seal the flue assembly to the wall using cement or a suitable alternative that will provide You must ensure that the entire flue system is satisfactory weatherproofing. The interior and properly supported and connected. exterior trim can now be fitted. Seal the flue assembly to the wall using cement or a suitable alternative that will provide satisfactory weatherproofing.
Page 11
4.5.3 TWIN FLUE SYSTEM Insert the exhaust connection manifold onto the The Vokera twin flue system enables greater flue appliance flue outlet. distances to be achieved (see 2.8) than that of the Place the silicone seal (supplied with twin standard concentric flue system.
4.5.3.3 VERTICAL TERMINATION (see fig. 11) The twin flue system must be converted to the dedicated concentric flue kit for termination. The vertical terminal is supplied with a built-in converter box and cannot be shortened. A 130mm hole is required for the passage of the concentric terminal through the ceiling and/or roof.
ELECTRICAL CONNECTIONS NOTE The electrical supply must be as specified in 3.7. It will be necessary to hold the valve with one A qualified electrician should connect the electri- spanner whilst tightening with another. cal supply to the appliance. If controls - external to the appliance - are required, a competent 4.6.1 GAS (see fig.
Vokera appliances. cold and hot as detailed in 5.7. Open all radiator or Vokera Ltd. cannot comment on the suitability of any heating valves and the appliance flow & return service other such product with our appliances.
OPERATING PARAMETERS The Eclipse boiler is supplied with built-in parameter defaults (see 2.11), the following procedure can be used if any parameters require to be adjusted or changed. Press the MODE button until a FIXED decimal point appears in LED 1 (see fig. 16). Press the STEP button until the desired parameter is shown in LED 1.
It is the law that any servicing work is carried out Inspect all joints for signs of leakage and repair by a competent person such as a Vokera engineer, if necessary. an approved service agent, British Gas, or other Refer to the commissioning section and/or re- CORGI registered personnel.
the appliance, remove the appliance casing as PRESSURE GAUGE (see fig. 20) described in section 4.8.1. Drain the water content Carry out component removal procedure as de- from the appliance via the safety valve. Ensure scribed in 6.4. some water absorbent cloths are available to Remove pressure gauge locking screw, located catch any residual water that may drip from the on manifold, and withdraw the pressure gauge...
Replace in the reverse order. Please note, ensure Housing all seals are in good condition, taking care to P.C.B. ensure they are replaced correctly. Cover Securing nuts Fig. 22 Spark Gas valve outlet electrode connection 6.11 GAS VALVE (see fig. 23) Carry out component removal procedure as de- scribed in 6.4.
6.16 HYDRAULIC MANIFOLD ASSEMBLY (see 6.18 CONDENSE PRESSURE SWITCH (see fig. 29) fig. 28) Carry out component removal procedure as Carry out component removal procedure as de- described in 6.4. scribed in 6.4. Unclip and remove the air chamber cover. Refer to figure 27 for an exploded view of the Disconnect the electrical wiring and pressure manifold and its internal components.
side. Replace in the reverse order, ensuring that all seals and insulation panels are undamaged and in good condition. Fig. 30 6.20 EXPANSION VESSEL (see fig. 1) Due to the compact design of this appliance, removal and/or replacement of the expansion vessel may require the appliance to be removed from the wall, if this is deemed impractical, an external expansion vessel may be fitted to the...
SECTION 7 CHECKS, ADJUSTMENTS, AND FAULT FINDING CHECKING APPLIANCE OPERATION CHECKING/ADJUSTING FAN SPEED To check the fan speeds, you must first access When carrying out any repairs or servicing to the appliance, the relevant commissioning and/or the engineer mode. The fan speed should only be set-up procedure must be undertaken to ensure changed or adjusted by the commissioning the continued safe operation of the appliance.
when ‘H’ is displayed in LED 1, press the 7.4.1 MINIMUM SETTING MODE button until LED 1 shows an alternating With the boiler operating at minimum output the cursor (see fig. 32); reading should be 8.6% (+/- 0.2%). If the CO when the digit is to the left, LED 2 shows the first reading is correct, proceed to 7.4.2.
LED 1 STATUS CODES LED 1 LED 2 Reason for lockout When the boiler is operating normally (without Internal fault (PCB) fault), LED 1 displays the current status of the Internal fault (PCB) boiler whilst LED 2 will normally display the Internal fault (PCB) relevant outlet temperature.
7.10 EXTERNAL FAULTS LED 1 shows 2 Before carrying out any fault-finding or component LED 2 shows Reason replacement, ensure the fault is not attributable to Standby any aspect of the installation. Purge For example external wiring fault, service valves Ignition closed, gas supply turned off, etc.
Connect test leads between the Neutral & Earth 7.12.1 FAULT FINDING TESTS connections at the appliance input board (see If a lockout code is displayed on LED’s 1 & 2, fig.15). The meter should read approximately 0 please refer to 7.6 for the cause of the lockout. –...
Page 26
7.12.3 FAULT FINDING TEST ‘1’ TEST1 SWITCH ON ELECTRICAL SUPPLY TO BOILER IS THERE 230V AT PLUG M5 ON INPUT BOARD? CHECK INCOMING SUPPLY IS THERE 230V AT PLUG M6 ON INPUT BOARD? CHECK FUSE ON IS THERE INPUT BOARD 230V AT PLUG X1 (L &...
Page 27
7.12.5 FAULT FINDING TEST ‘2’ TEST 2 PUMP FAULT 230V ON TERMINALS P & N OF PLUG X1 230V AT F1 FUSE ON L & N OF PUMP MAIN PCB OK REPLACE REPLACE REPLACE CHECK FUSE CONTINUITY PUMP 7.12.6 FAULT FINDING TEST ‘3’ TEST 3 FAULT IS "5"...
(part no. 201 or 202) EXTERNAL CONTROLS IMPORTANT (see 8.1) Isolate the appliance from the electrical supply Vokera recommend the use of the “S” plan system and remove the casing as described in 4.8.1. of controls (see fig. 34B). However the “Y” plan...
Page 29
Fig. 34 Fig. 34A “Y” plan installations are only possible with the addition of an external relay as above. The switching contacts of the relay must be suitable for 24vac at 100ma, the relay coll must be suitable for 24vac “S”...
Page 30
FUNCTIONAL DIAGRAM Fig. 35 R.T. Room thermostat Led alarm (blink red) Fusibile 2 AF F.se/I.E. Spark/sense electrode Pump Gas valve solenoids Flow thermistor (NTC) RL3V 3 way relay Return thermistor (NTC) P.S. Pressure switch (NC) Led OK (green) Supplied By www.heating spares.co Tel. 0161 620 6677...
SECTION 10 L.P.G. INSTRUCTIONS For details of converting boilers to LPG please refer to the instructions supplied with the relevant conversion kit. 10.1 TECHNICAL DATA Inlet pressure 37 mbar 37 mbar Maximum gas rate 2,49 l/per hr. 4,08 l/per hr. Minimum gas rate 0,72 l/per hr.
check that the correct value is still being obtained. If not, repeat the above procedure; press the RESET button to exit the appliance engineer mode. Remove the analyser test probe from the analysis test point and refit cap. Refit the air chamber cover.
Need help?
Do you have a question about the Eclipse 216 ESS and is the answer not in the manual?
Questions and answers