13. Check-Test
Start (cont'd)
After Startup (cont'd)
DANGER: The gas burner in this direct gas-fired system is designed and equipped to provide
safe and economically controlled complete combustion. However, if the installation does not
permit the burner to receive the proper supply of combustion air, complete combustion may
not occur. The result is incomplete combustion which produces carbon monoxide, a poisonous
gas that can cause death.
Always comply with the combustion air requirements in the installation codes and operating
instructions. The amount of air over the burner must be within the specified range. The burner
profile plates are set at the factory to match CFM requirements. Do not adjust the burner
profile plates without contacting a factory representative. FAILURE TO PROVIDE PROPER
COMBUSTION AIR CAN RESULT IN A HEALTH HAZARD WHICH CAN CAUSE PROPERTY
DAMAGE, SERIOUS INJURY, AND/OR DEATH. Direct-fired installations should provide for
air changes as required by the applicable installation codes.
ADDENDUM SECTION
Installation Instructions for Optional Screened Air Hood for
Outdoor Units (Options AS2, AS6, AS7) and Filter Sections
for Indoor Units (Options AW3, AW6)
CAUTION: It is
recommended that the
inlet to the outside air
hood NOT be facing into
prevailing wind.
TABLE Identifying Options by ITEM and Application
ITEM
Page 24
recommended that the tempered makeup air entering the building be
tested at its point of discharge from the heating unit. The table below
shows limits for various substances including carbon monoxide.
Certified, portable detector tubes may be used; follow the manufacturer's
instructions.
Limits Based on Eight-Hour Exposure and a Five-Day Week (Guide Only)
Substance
Acetaldehyde
Carbon Dioxide
Carbon Monoxide
Formaldehyde
Nitrogen Dioxide
Sulphur Dioxide
Note: At 100°F rise the CO
All of these air inlet accessories are designed to be attached directly to the
system cabinet. To prevent damage, it is recommended that the system be set
in its permanent location before installing the air hood or filter cabinet option.
All are shipped separately; installation requirements depend on the size (see
below).
See Paragraph 6 for the dimensions of these optional accessories.
Provide a minimum of 14" (356mm) clearance from the bottom of the air hood
to the mounting surface.
Options
Description
Outdoor Screened Air Hood
AS2, AS6,
1
with and without filters
AS7
Outdoor Screened Air Hood
AS2, AS6,
2
with and without filters
AS7
Indoor Filter Cabinet with
AW3,
3
Filters
AW6
Percent
PPM
.001
10
.250
2500
.001
10
.000025
0.25
.0001
1
.00005
0.5
concentration will be about 2500 ppm.
2
For Sizes
Installation Requirements
Factory Assembled; Field Installed -
1-20, 1-40, 1-50,
Follow instructions on page 25.
1-65, 2-80, 2-120
Field Assembled and Installed -
3-180, 3-260
Follow instructions pages 25 to 28.
Factory Assembled; Field Installed -
All
Follow instructions on page 25.