9

Error messages

The following list contains the error messages for the LCD display.
Device
Device
Device
Device
Device
Device
Device
Device
Device
Device
Device
Communication
Sensor 1
Sensor 1
Sensor 1
Sensor 1
OI/TTF300-EN
Device
DIAG.
Source of Error
Status
NO.
F
1
Device defective.
S
2
Above/below ambient
temperature.
F
3
EEPROM defective.
M
4
Electronics overload.
F
5
Memory error.
I
7
HMI inserted.
I
8
Device write-protected.
I
9
EEPROM busy.
F
12
Sensor input defective
(communication).
Sensor input defective
F
13
(error).
F
14
Sensor input defective
(ADC error).
C
32
Diagnostic simulation mode No error, diagnostic info,
F
34
Measuring error.
F
35
Sensor short-circuit.
F
36
Wire break.
F
37
Above sensor range.
TTF300
Error messages
Error correction
Replacing the device.
Check environment,
possibly reposition
measuring point.
Replacing the device.
Reset to factory settings,
notify service of error
message.
Reset to factory settings,
notify service of error
message.
Status info, no error.
Status info, no error.
Status info, no error.
Replacing the device.
Replacing the device.
Replacing the device.
measurement OK.
Sensor
Check sensor connection.
Check sensor connection.
Check sensor connection.
Check measuring limits.