Water Supplies - Rheem 613050 Owner's Manual And Installation Instructions

Electric heavy duty water heater
Hide thumbs Also See for 613050:
Table of Contents

Advertisement

This water heater must be installed in accordance with this advice to be covered by the Rheem
warranty.
This water heater is manufactured to suit the water conditions of most public reticulated water supplies.
However, there are some known water chemistries which can have detrimental effects on the water heater
and its operation and / or life expectancy. If you are unsure of your water chemistry, you may be able to
obtain information from your local water supply authority. This water heater should only be connected to a
water supply which complies with these guidelines for the Rheem warranty to apply.
CHANGE OF WATER SUPPLY
The changing or alternating from one water supply to another can have a detrimental effect on the operation
and / or life expectation of a water heater cylinder, a temperature pressure relief valve and a heating unit.
Where there is a changeover from one water supply to another, e.g. a rainwater tank supply, bore water
supply, desalinated water supply, public reticulated water supply or water brought in from another supply,
then water chemistry information should be sought from the supplier or it should be tested to ensure the
water supply meets the requirements given in these guidelines for the Rheem warranty to apply.
ANODE
The vitreous enamel lined cylinder of the water heater is only covered by the Rheem warranty when the total
dissolved solids (TDS) content in the water is less than 2500 mg/L and when the correct colour coded anode
is used. If an incorrect colour coded anode is used in the water heater, any resultant faults will not be
covered by the Rheem warranty. In addition, the use of an incorrect colour coded anode may shorten the life
of the water heater cylinder.
The correct colour coded anode must be selected and fitted to the water heater in accordance with the
following advice and the
heater cylinder.
The changing of anodes must be carried out by a qualified person.
Note: Some water analysis reports may state the conductivity of the water rather than the level of total
dissolved solids. Conductivity, measured in microsiemens per centimetre (µS / cm), is directly proportional to
the TDS content of the water. TDS, in mg / L, is approximately 70% of the conductivity in µS / cm.
40
150
(60)
(215)
Green
Black

WATER SUPPLIES

Anode Selection chart
Total Dissolved Solids
0 – 40 mg/L
40 – 150 mg/L
150 – 400 mg/L
400 – 600 mg/L
600 – 2500 mg/L
2500 mg/L +
400
600
TOTAL DISSOLVED SOLIDS (TDS) mg/L
(CONDUCTIVITY - μS/cm)
(570)
(860)
Warranty applies to a vitreous-enamel-lined
water heater cylinder if the correct coloured
anode is used for the TDS of the water
ANODE SELECTION
on page 9 for the Rheem warranty to apply to the water
Anode colour code
Green
Green or Black
Black
Black or Blue
Blue
Blue (no cylinder warranty)
Blue
9
2500
(3570)
Blue
Above 2500 mg/L,
no warranty applies