Outback Power Systems FLEXware16 Amp Maximum 250VAC Product Manual page 3

Amp maximum 30vdc/250vac rated relay and din mount base with led

Advertisement

TWO WIRE START
GENERATOR
HOOK UP
GENERATOR
12V RELAY
NO
COM
NC
There are two screw terminals for each relay contact. Each
can handle up to 8 amps. They are tied together internally.
COM 11 and COM 21 are the common relay connections.
Either can be used for loads under 8 amps. If the load
exceeds 8 amps, use both COM 11 and COM 21.
NO 14 and NO 24 are normally open relay connections.
Use both 14 and 24 terminals for loads exceeding 8 amps.
NC 12 and NC 22 are normally closed relay connections.
Use both 12 and 22 terminals for more than 8 amps.
NOTE: If a load exceeds 8 amps, use both screw terminals for any
given relay contact to distribute the current and avoid overloading
the screw terminal.
Terminal screw torque – 0.5 Nm (4.4 inch lbs)
FX INVERTER/CHARGER
INVERTER
ON/OFF
AUX +
AUX -
XCT -
XCT +