Clearance to Combustibles:
Side:
Rear:
Ceiling:
Discharge End:
(FRONT)

6.0 Operating Procedures:

6.01 Inspect heater orifice, Fuel inlet and base for signs of liquid fuel or oil
contamination. If present, DO NOT USE HEATER. Have a qualified technician
disassemble LPG supply line and components to remove liquid fuel or oil before
use.
6.02 Place heater on secure level surface. Heater must be positioned such that it is not
directly exposed to wind, water, spray, rain and/or dripping water.
6.03 Connect LPG supply hose with first stage regulator assembly to a 20 or 40 LB.
approved cylinder. (First stage regulator should take bottle pressure down to
10 to 35 PSI.) Connect to heater by either a quick disconnect fitting or 9/16"
Left Hand threaded fitting. Tighten all connections.
Locate LPG gas cylinder at least 6Ft. from heater, in a position away from the
Direct path of radiant heat from the heater.
6.04 Turn on the fuel at cylinder and recheck all fittings for possible leaks using a soap
solution. Tighten any leaks found and retest. Never use a match to check for leaks.
NOTE: the longer the fuel hose length the longer period of time to purge the hose
of air from the initial hookup.
6.05 TO IGNITE: First depress and turn rotary knob, located on the back of heater
base, too the HIGH position, first detent. Kneeling behind heater (DO NOT
STAND OVER HEATER) Second, depress and hold the brass button on the safety
shut off valve located under the heaters ceramic head in the middle of the base.
While still holding down on the brass button, push down on the igniter button
repeatedly until the heater ignites. Continue holding the safety valve button in for
approximately one minute to heat the thermocouple. When the thermocouple is hot
enough, release the safety valve button and the heater will stay lit. If the heater
goes out, turn off the fuel valve and the tank valve and wait for five minutes and
repeat lighting procedure.
6.06 Alternate lighting procedures: A long match may be inserted through the opening
in the heater shield on the left side in lieu of the piezoelectric igniter while observing
all other safety precautions. Once the heater has been lit, you can adjust the heat
output to the desired setting.
6.07 To turn heater off: First turn off the fuel supply at the bottle. This burns off excess
fuel in the supply hose and lowers line pressure. When the heater flame goes out,
turn the rotary knob to the off position. Let the heater cool down and you can
18"
18"
48"
48"
5
Rev.#7 11-01-06